An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. PowerScale 10-50kVA Maximize your availability

  2. Contents • Range • Features and Performance • Mechanical Construction • Battery Configuration • External Batteries – Battery Cabinet • Connectivity • Options and accessories

  3. Range Technology : On-Line, transformer less Power range : 10 ,15, 20, 25,30 ,40,50 kVA (3ph/3ph) Rated at PF : cosphi 0.9 Type A Type B Type C

  4. Features and performance • Generalities • LCD Display • Input PFC • Input THDI • Efficiency • Active Power vs cosphi

  5. Features and performance • True on-line double conversion (VFI) • Power Factor 0.9 • High efficiency (up to 95.5%) • Input PFC: 0.99 @ 100% load • Input THDi < 3 % • Parallelable up to 20 units • Electronic and manual bypass • Manual/Automatic Battery test • Fan speed temperature regulated • Easy to install, service and manoeuvre • Flexible battery autonomy space within 3 different cabinets size (A,B,C) • Single or Dual input feed • RS 232 + 4 potential free input contacts • SNMP card slot / Pot. Free Output card slot • Multi language LCD display E/S/D/F/P • Wide Input voltage windows <@100% load(-23% / +15%) <@80% load (-30% / +15%) <@60% load (-40% / +15%) Generalities Cab C Cab B Cab A

  6. BATTERY Features and performance LCD Display ON / OFF LINE 2 BY PASS RESET ENTER ON / OFF LINE 1 INV ALARM Most important info available at first glance LCD Display

  7. Features and performance 0.99 0.99 0.985 0.96 Input PF (%) Load (%) Input PFC Advanced Booster PFC circuit to provide near-unity Input PF even with partial loads. • Benefits: • No phase compensation filter required • Respect power grid regulations • Energy savings • Reduced TCO

  8. Features and performance THDi Input THD versus load Advanced Booster PFC circuit to provide Flat THDi Curve even with partial loads. • Benefits: • No gen-set oversizing • Small cable/fuses/breakers size • No extra heating of transformers • Unique electrical performance • Reduced TCO

  9. Features and performance Efficiency Flat Efficiency Graph Results in low losses at PARTIAL and FULL load Redundant UPS Systems operating typically at 25-75% of the rated load. • Energy Savings • Reduced TCO

  10. Mechanical Construction • SNMP Card • Pot.free output contacts • (optional) Overview: Cabinet A • RS232 • Pot.free Input contacts • Multidrop LCD Display Parallel kit Air inlets By-pass fuse Battery fuse Rectifier fuse Manual By-pass Castors UPS disconnect I/O connection

  11. Mechanical Construction Overview: Cabinet A Display Board CPU board • Rectifier • Booster • Battery charger • Inverter Battery bank

  12. Mechanical Construction • SNMPCard • Pot.free output contacts • (optional) Overview: Cabinet B • RS232 • Pot.free Input contacts • Multidrop LCD Display Parallel Kit Air inlets Battery fuse By-pass fuse Rectifier fuse Manual By-pass UPS disconnect Castors I/O connection

  13. Mechanical Construciton Overview: Cabinet B Display Board CPU board • Rectifier • Booster • Battery charger • Inverter Battery bank

  14. Mechanical Construciton Overview: Cabinet C LCD Display Removeable Front Panel No Access from Rear Side Air inlets Castors

  15. Parall. Kit Mechanical Construciton RS 232 Pot.free Input Contacts Multidrop Overview: Cabinet C • SNMP • Card and Pot. Free output contacts • (optional) Rectifier fuse By-pass fuse Battery fuse Manual By-pass UPS disconnect I/O connection

  16. Battery Configuration Battery shelves, trays and links Type A Type B Type C

  17. Standard Cabinet C Battery Configuration Battery shelves & trays Cabinet C (25, 30,40,50kVA) • 2 Shelves are delivered with the empty cabinet • Additional Shelves and Trays are OPTIONAL. • Possible configurations: • 2 x 48 x 7/9Ah • 3 x 48 x 7/9Ah • 1 x 48 x 28Ah Shelves (Standard)

  18. Battery Configuration Battery shelves & trays Cabinet C (25, 30,40,50kVA) OPTION 04-1475: Battery shelves and trays for 2 x 48 x 7/9Ah Kit consisting of: 2 x shelves 16 x trays (6 x 7/9Ah batt / tray)

  19. Battery Configuration Battery shelves & trays Cabinet C (25, 30,40,50kVA) OPTION 04-1476: Battery shelves and trays for 3 x 48 x 7/9Ah Kit consisting of: 4 x shelves 24 x trays (6 x 7/9Ah batt / tray)

  20. Battery Configuration Battery shelves & trays Cabinet C (25, 30,40,50kVA) OPTION 04-1477: Battery shelves and trays for 1 x 48 x 28Ah Kit consisting of: 2 x shelves 16 x trays (3 x 28Ah batt / tray)

  21. Battery Configuration Caracteristics (1) Source: PowerScale Product Specifications Doc: 04-1206_S10_NW_TDSPS_10-50kVA_GB_101021 (2)

  22. Battery Configuration Caracteristics (2)

  23. Battery Configuration How to order INTEGRATED Batteries from Newave • Type of Batteries offered by Newave SA • 7Ah: Panasonic (normal life) • 9Ah: YUASA (normal life) • 28Ah: Panasonic (long life 10Y) • Principles: • Subsidiaries and Partners calculate the exact number of battery per string that the application requests and order number of blocks accordingly (minimal number acc to Product Specifications) • Newave delivers the UPS with integrated batteries mounted and tested, as requested • Battery blocks in PowerScale price list include shelves, trays and battery links (items 04-1203; 04-1204; 04-1472; 04-1473; 04-1474) PO-Form detail

  24. Battery Configuration Autonomy Table 10kVA Note: Backup times are approximate and may vary with battery type, configuration, battery age, temperature etc.

  25. Battery Configuration Autonomy Table 15kVA Note: Backup times are approximate and may vary with battery type, configuration, battery age, temperature etc.

  26. Battery Configuration Autonomy Table 20kVA Note: Backup times are approximate and may vary with battery type, configuration, battery age, temperature etc.

  27. Battery Configuration Autonomy Table 25kVA Note: Backup times are approximate and may vary with battery type, configuration, battery age, temperature etc.

  28. Battery Configuration Autonomy Table 30kVA

  29. Battery Configuration Autonomy Table 40kVA

  30. Battery Configuration Autonomy Table 50kVA

  31. External Batteries – Battery Cabinet Battery Cabinet In case of external battery requirment, an external battery cabinet will be made available in March 2011. More information will be available early 2011 Announcement

  32. Connectivity Optional Standard - included • RS232 on Sub-D9 port • Input Dry Contacts: • Remote shut down • Generator ON • Programable Input: Customer IN1 • Temp Sensor for Battery • 12VDC Source • RJ 45 for Multidrop • A. SNMP/USHA Card (Slot) • B. Optional Card • (Dry contact and USB port: Item nr 00-9737) • Output Dry Contacts: • Common Alarm • Load on Bypass • Battery low • Load on Inverster • Mains Failure • USB port

  33. Options and Accessories Available in price list • SNMP slot card (web enabled) • Shutdown software • Potential free output contact slot card, including USB port • Parallel kit (one additionnel PCB + one parallel adapter) • Parallel cables of different lenghts • Back feed protection • Temperature probe On special request • Emergency Shut Down • I/O Transformer for galvanic isolation or voltage adaptation, special I/O configuration

  34. Sales Availability Ex Works Availability • 10kVA Cabinet A and B • 15kVA Cabinet A and B • 20kVA Cabinet A and B • 25kVA Cabinet B • 25kVA Cabinet C • 30,40,50kVA Cabinet C • Battery Cabinet January 2011 March 2011 • Documentation • Sales Presentation • Product Flyer • Technical Specifications • Price List • PO-Form • User Manual (at delivery)