1 / 35

Product Introduction 9390 40-160 kVA

Eaton 9390 Presentation Index. SnapshotSpecificationsDesign

Leo
Télécharger la présentation

Product Introduction 9390 40-160 kVA

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


    1. Product Introduction 9390 40-160 kVA

    2. Eaton 9390 Presentation Index Snapshot Specifications Design & Characteristics Paralleling Battery solutions Eaton Technologies HotSync ABM ESS Efficiency Accesories

    4. Eaton 9390 40-160kVA Rating: 40; 60;80;100;120; 160kVA Input: 3ph; 380/400/415V Nominal; 50/60Hz Output: 3ph; 380/400/415V; 50/60hz Connectivity: Wide options with X-slots High power performance: Efficiency 94% at nominal load Output power factor 0.9 Input ITHD < 5% Graphical LCD Technology PWM controlled IGBT technology Transformerless State-of-art design Compact, lightweight, space-saving Can operate as frequency converter Can operate as power conditioner (no battery) Combine this slide with #5Combine this slide with #5

    5. Eaton 9390 40-160kVA 9390 range 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA 160 kVA

    6. EATON 9390 40-160kVA 40; 60; 80kVA 380/400/415V 100; 120; 160kVA 380/400/415V

    7. Serviceability 100% Front Access Unit can be backed up against wall or into a corner Mean time to repair (MTTR) less than 30 minutes (worldwide) Power modules are field replaceable units Fan tray is a field replaceable unit Power module component repair in remote countries Mean time before failure (MTBF) calculated to be: >150 thousand hours in RT mode w/bypass Comprehensive service plans

    9. 9390 Input Specification No. of phases: 3 phases + Neutral Rectifier rated input voltage: 380 /400 / 440 VAC Nominal Tolerance +10 -15% at 100% nominal load (zero battery discharge at low end) -30%... +20% of nominal maximum input voltage window Frq: 45-65Hz; 50 or 60Hz 3Hz (nominal) Bypass input voltage 380 /400 / 440 VAC Nominal -15%... +10% Input power factor: 0.99 Input current THD: 3-5% Lets work on this slide Better way to show it!! Elina did it in a rush.. Without thinking it.. Too much.. Lets work on this slide Better way to show it!! Elina did it in a rush.. Without thinking it.. Too much..

    10. 9390 Output Specification No. of phases: 3 phases (+Neutral) inverter rated output voltage 220; 230; 240VAC 3VRMS Rated output frq: 50 or 60Hz (configurable) Variation: 3Hz (default); configurable! Slew rate: 1Hz/s (default); configurable! Voltage THD <3% (linear load); 5% reference non-linear load Crest factor: 3 Nominal power factor 0.9 Range: 0.7 lagging 0.9 leading Short circuit capability (@inverter): 240A 300ms (80kVA) / 480A 300ms (160kVA)

    11. 9390 DC Circuit Specification Typical DC-link Voltage 620VDC Battery Specification: 40 Block VRLA 12V batteries per string Maximum total battery voltage 569VDC Battery cut-off voltage 1.75/1.67VPC Typical runtimes with 0.8 output PF

    13. Design Characteristics

    14. Typical System Main Circuit: 9390 80kVA w MBS

    15. EATON 9390 Dimensions

    16. EATON 9390 Mechanical Design Transformerless design : Compact, lightweight, space-saving Front to top cooling Cool air is draw in via the front door, warm air is exhausted out the top of the unit Fan tray assembly blows cool intake air up through the power modules

    17. Cabling EATON 9390 40-80kVA

    18. Cabling EATON 9390 120-160kVA

    19. Reliable Upgradability through Eaton Paralleling Technologies - HotSync EATON HotSync Paralleling Technology Enables synchronization without communication line between the UPS Eliminates single point of failure Work in this one!Work in this one!

    20. HotSync Paralleling Technology EATON Powerware Hot Sync - Increasing Availability Accurate parallel UPS load share without communication Available to Powerware 3-ph UPS at power range 8kVA ?

    21. 9390 Battery Solutions Powerful battery converter technology allows flexible extent runtimes without need for external chargers External battery cabinet solutions Line and match!! Battery Specification: 40 Block VRLA 12V batteries per string Maximum total battery voltage 569VDC Battery cut-off voltage 1.75/1.67VPC ReWork.. Main message: our desing is highly configurableReWork.. Main message: our desing is highly configurable

    22. Battery Management Advanced Battery Management Advanced charging algorithms to significantly extend battery life compared to traditional charging method Automatic and periodic self tests for battery circuitry Temperature compensated charging available (option) Explain more the second bullet point!!Explain more the second bullet point!!

    23. User Interface Add in more detail with is displayed. E.g., metering, event history log, add the # of languages we have.Add in more detail with is displayed. E.g., metering, event history log, add the # of languages we have.

    24. User Access and Communications

    25. User Access and Communication

    27. 9390 Accessories External battery cabinets and rack systems System parallel modules (SPM) Sync Control External (manual) bypass switches Software and communications options

    28. External Battery Cabinet (Large)

    29. EBC Dimensions

    30. Battery breaker box ( 250 A )

    31. SPM Cabinet 4* 40-80 kVA 1023540 SPM9390-80-4

    32. Tie Cabinet 3* 100-120 & 3* 160 kVA 1024506 9390 Tie Cabinet 3x160 kVA 1024687 9390 Tie Cabinet 3x120 kVA

    33. SyncControl 100-160 kVA 1024635 Powerware 9390-100-U-4X1 (Sync Control SUPPORT) 1024636 Powerware 9390-120-N-4X1 (Sync Control SUPPORT) 1023298 Powerware 9390-120-U-4X1 (Sync Control SUPPORT) 1023299 Powerware 9390-160-N-4X1 (Sync Control SUPPORT)

    34. Distribution systems: IT International standard IEC 60364: I : no point is connected with earth (isolation), except perhaps via a high impedance. T : direct connection with earth, independent of any other earth connection in the supply system In Europe: 400 Volts 50 Hz 380 Volts 50 Hz 415 Volts 50 Hz

    35. 9390 40-160 kVA IT -model

More Related