An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. NSF SEEDM workshop, May 2-3, 2011 Thermal Aware Data Management in Cloud based Data Centers Ling Liu College of Computing Georgia Institute of Technology

  2. Thermal aware Computing Era • Power density increases • Circuit density increases by a factor of 3 every 2 years • Energy efficiency increases by a factor of 2 every 2 years • Effective power density increases by a factor of 1.5 every 2 years [Keneth Brill: The Invisible Crisis in the Data Center] • Maintenance/TCO rising • Data Center TCO doubles every three years • Three-year cost of electricity exceeds the purchase cost of the server • Virtualization/Consolidation is a 1-time/short term solution [Uptime Institute] • Thermal management corresponds to an increasing portion of expenses • Thermal-aware computing and management solutions becoming prominent • Increasing need for thermal awareness

  3. [VarsamopoulosGupta 2008]

  4. Thermal aware Task Scheduling in Data Centers • Given a total task C, how to divide it among N server nodes to finish computing task with minimal cooling energy cost ? • Self-Interference and cross-interference lead to the temperature rise of inlet air, should be minimized • Environment interference(room temperature) is not critical • Task scheduling in spatial domain [VarsamopoulosGupta 2008]

  5. Cooling Cost aware Scheduling [VarsamopoulosGupta-2008]

  6. Energy Saving by Dynamic Load Distribution Increasing the range of changes in the rack heat load • Heat load distribution of [30 kW, 5 kW, 5 kW, 20 kW] in the case study only needs 1.7 m/s (9,726 CFM) cooling air flow • It is 19% less than the uniform distribution needs • This could save ~$189,000 annually in typical real world data centers Temperature Contours Around Racks: [15,15,15,15] kW with 2.1 m/s [30,5,5,20] kW with 1.7 m/s [Yogendra Joshi, Georgia Tech/CERCS]

  7. Think Globally, Act Locally Make a server heat load-Inlet T variation matrix Run simulations for a range of velocities A Matrix Numerically Where, server I load Minimum load (startup) Max. load (full utilization) Max. inlet T allowed by ASHRAE Vary the heat loads sequentially at servers for a chosen unit cell and monitor the max. server inlet T Experimentally • Modifications: • Blocks of servers can be identified with same effect or no effect on the inlet T. • This will give insights on the sparsity of this matrix. • Reduce the computational work. Advantage: The simulations run for different velocities are not required for the experimental approach. [Yogendra Joshi, Georgia Tech/CERCS] ]

  8. 11 41 16 46 An Example VCRAC = 5m/s 37.5% decrease in Facilities Energy Consumption (For the same heat dissipation) 68% increase in allowed heat dissipation (For the same CRAC velocity) [Yogendra Joshi, Georgia Tech/CERCS]

  9. Pertinence of Thermal Maps in Data Center Management • Given an equipment utilization layout, find the temperature around the room • Create a collection of thermal maps or a function to “predict” thermal behavior of a task assignment • Use collection to decide on job placement (temporally and spatially) [VarsamopoulosGupta 2008]

  10. Thermal-aware Data Management [Adapted from VarsamopoulosGupta 2008]

  11. Thermal aware data management • Task profiling • CPU utilization, I/O activity etc • Equipment power profiling • CPU consumption, disk consumption etc • Heat recirculation modeling • Task management technologies Need for a comprehensive research framework