Inlet and Outlet Shape-Optimization of Natural Circulation Building Ventilation Systems

Inlet and Outlet Shape-Optimization of Natural Circulation Building Ventilation Systems. Energy Postgraduate Conference 2013. Department of Mechanical Engineering, University of Stellenbosch, Stellenbosch, Western Cape Provence, South Africa. Preface. What is a

brigit
Télécharger la présentation

Inlet and Outlet Shape-Optimization of Natural Circulation Building Ventilation Systems

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Inlet and Outlet Shape-Optimization ofNatural Circulation Building Ventilation Systems Energy Postgraduate Conference 2013 Department of Mechanical Engineering,University of Stellenbosch, Stellenbosch, Western Cape Provence, South Africa

  2. Preface • What is a • Natural Circulation Building Ventilation System? Source: Natural draft cooling flow diagram (Cunningham, Mignon and Thompson 1987)

  3. Introduction • Normal air conditioning use refrigerants to cool air to desired temperatures. • It normally has a power of between 4 to 8 kW. • ESKOM currently charges a mean of 100c/kWh for electricity. • An alternative solution to achieve thermal tempering in a building is to use natural circulation Source: Amana heating and air conditioning

  4. Introduction (cont.) • Example of such a natural circulation ventilation system is a Solar Chimney Augmented Passive Downdraught Evaporation Cooling (SCAPDEC) system.

  5. Objectives • Develop inlet and outlet configurations for a SCAPDEC system. • Test these configurations in real atmospheric conditions, i.e. exposed to precipitation and wind. • Develop a 2 dimensional theoretically model of the system with incorporated inlet and outlet configuration loss coefficients. • Use CFD software to obtain results on the same domain. • Compare the theoretical results with the experimental results to determine optimized shapes. • Compile design guidelines for such a system.

  6. Theory • Four inlet and outlet configurations have been tested. • Open-ended and extruding end configuration for comparative purposes. • Cone and DSI-design inlet configuration aimed to funnel wind into PDEC. • Whirlybird and DSO-design protects against rain and fowl. • DSO-design no moving parts. Figure 1: Inlet configurations Figure 2: Outlet configurations

  7. Theory • Proposed discretization scheme of PDEC with cone inlet configuration for two dimensional theoretical model. • This domain will also be incorporated into the CFD model. • Two dimensional approach used to obtain more accurate results. • One-dimensional model could not capture subtle changes. Figure 3: Discretization scheme

  8. Results Test 1 • Initial testing consisted of four tests: • High draft, no wind. • High draft, high wind. • Low drat, high wind. • No draft, high wind. • Test 1: Open ended inlet, no wind. • Test 2: DSI-design inlet, no wind. • Test 3:DSI-design inlet, with wind. Test 2 Test 3

  9. Discussion and Conclusion • Open ended inlet and outlet configuration performed best, but does not protect against rain and fowl. • Initial testing shows DSI-design configurations to have significantly lower loss coefficient than cone and extruding end configurations, for all four administered tests. • DSO-design configuration and whirlybird showed similar results and are the only two viable outlet configurations. • Further optimization planned on DSI- and DSO-design configurations. • Configurations will be tested on full-scale SCAPDEC system.

  10. Thank you JJ Swiegers Department of Mechanical Engineering,University of Stellenbosch,Stellenbosch, Western Cape Province, South Africa 15664155@sun.ac.za