1 / 19

Sizing of district heating substations and optimum maintenance of

Sizing of district heating substations and optimum maintenance of domestic hot water circuits in Sweden Janusz Wollerstrand Lund Institute of Technology Department of Energy Sciences Sweden. Topics. Balancing of DHW circulation circuits

bryson
Télécharger la présentation

Sizing of district heating substations and optimum maintenance of

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Sizing of district heating substations and optimum maintenance of domestic hot water circuits in Sweden Janusz Wollerstrand Lund Institute of Technology Department of Energy Sciences Sweden

  2. Topics • Balancing of DHW circulation circuits • Dynamic sizing of control valves in domestic hot water (DHW) heaters • Heat exchanger operation at overload condition • Practical experiences

  3. A district heating substation and secondary circuits in a residential building

  4. Tindoor 21-22ºC 55ºC A district heating substation and secondary circuits in a residential building

  5. 50ºC Tindoor 21-22ºC 55ºC A district heating substation and secondary circuits in a residential building 50ºC

  6. Connecting scheme of the domestic hot water circulating system in a large university building. Temperatures at end-points and some short-cuts resulting in low temperature in one of branches shown. 54,1 (short-cut) 45,3 too low temperature 50,7 47,7 too low temperature 51,1 55,6 N S 51,0 DH-substation and DHWC-pump 51,2 51,3 53,5 (short-cut)

  7. Thermostatic balancing valve Temperature registration Thermostatic balancing valve installed at the end point of DHW circuit

  8. Connecting scheme of the domestic hot water circulating system in a large university building. Thermostatic balancing valves installed resulting in equalized temperature level in the circuit. 50,4 50,4 50,1 48,6 still too low temperature 51,1 56,4 N S 50,8 DH-substation and DHWC-pump 50,7 50,9 51,3 52,1

  9. Strongly reduced valve size as a consequence of dynamic sizing being employed. Valve actuator Replaced valve Heat exchanger Source: C. Forslund, Gävle Energy AB, Gävle New valve

  10. Reasons for oversizing of control valves in practice: • overestimated design load values for DH substation • overestimated operating conditions of the substation • round up of the valve size in case of discrepancy between the calculated size and the available size (almost always) • dynamics of the system not taken to consideration

  11. Dynamic sizing of control valves in domestic hot water heaters – field measurements DH water flow rates in a hot tap water heater with different control valve sizes. The peak flow rate increases by increased valve size but at small loads the flow rate remains mainly unchanged Position changes of control valve in a hot water heater with varying valve size (field measurements performed by Gävle Energy AB)

  12. Dynamic sizing of control valves in domestic hot water heaters as employed in Gävle, Sweden Source: C. Forslund, Gävle Energy AB, Gävle

  13. Outgoing hot water temperature and primary return temperature from a heat exchanger vs. hot water flow when the primary flow is limited. If mixing of the hot and the cold DHW at the tap is taken to account, 20% overload at 45ºC DHW temperature is possible

  14. Domestic hot water (DHW) temperature measured at the outlet of the heater while short overload condition occurs Valve position DHW temperature DHW circul. temperature

  15. Domestic hot water temperature measured at the tap during morning hours in a hotel

  16. Theoretical flow characteristic of a control valve of logarithmic type. Control ratio: 1:100, kvs=10 m3/h. Logarithmic valve with kvs=10 m3/h size and the control ratio 1:100, with the o pening ratio limited to 50%, acts as a nearly logarithmic valve with kvs=1 m3/h and the control ratio 1:10 Adaptive limiting of capacity of existing control valve instead of replacing the valve by a smaller one − a promising solution

  17. Number of flats with size of control valve employed in tap water heaters for a large group of residential buildings in Gävle, Sweden

  18. Short tappings often do not coincide when hot water circulation is working well (the left picture) but are likely to coincide otherwise (the right picture).

  19. Conclusions • Dynamic sizing of control valves works well in practice • The choice of the size of control valve strongly depends on proper functioning of DHW circulation • Adaptive adjustment of control valve capacity − optimum solution • Do not relay on DHW circulation return temperature as a minimum temperature of the circuit

More Related