An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Overhead Conductors

  2. DayCor® Technology • DayCor® Technology is used to detect Corona Particle Discharge and Arcing • on electric grid components. • It offers you: • Early warnings of potential future failures. • Pinpointing & Visualizing the coronaeffect. • Decision ability to determines the health of your critical systems components • Prioritize your particle discharge maintenance challenges • Day time work • DayCor® Technologysaves you by avoiding costly • unscheduled outages and failures

  3. -V e e + E field e UV Ph UV Ph UV Ph e + e e + e e Corona Effect Corona is a luminous partial discharge due air ionization. The DayCor® camera pinpoints the exact source’s location by visualizing the UV photons, coming out of it. UV Photon Natural Air molecule Free Electron, coming out from the source Corona Source

  4. Bi-Spectral Imaging Combined Mode Visible only display Pinpointing the exact corona’s location UV only mode

  5. UV-IR complimentary technologies Live End Corona Dead End Corona Corona spots using UV technology No corona on IR picture

  6. Voltage Stress Related Failures • Overloads • Design • Manufacturing results • Mutual Influence

  7. EnvironmentRelated Failures • Contamination • Birds damages • Water Tree Conversion

  8. Water Trees • Water migration into the insulation leads to water trees. • Water Trees lead to decreased insulation resistance and very slight increase in leakage current. • Water Trees do not directly produce failure. • Water Trees lead to electrical trees which produce Partial Discharge and ultimate failure.

  9. Water Tree Conversion • The high electric field caused by voltage surges result in power dissipation in the water channels existing in insulation sufficient to raise the temperature of the water and increase pressure in the water tree channel. • This phenomena generates cavities sufficient to support partial discharge HMWPE Insulation XLPE Insulation Electrical Treeing

  10. Water Tree Conversion • Each occurrence at which PD occurs causes the size and geometry of the insulation void to change. Lowering the PD inception and extinction voltages. • When PD extinction voltage drops below system nominal voltage, PD’s are continuous leading to electrical tree formation and ultimate insulation failure

  11. Hardware Related Failures Broken Strand

  12. IEEE Standard 400-2001 Notes “Partial discharge measurement is an important method of assessing the quality of the insulation of power cable systems…”

  13. The Corona Process

  14. Why Test for Partial Discharges? • Partial discharge testing can detect: –Insulation defects that may have occurred during cable system installation or at the manufacturing process –Insulation deterioration due to normal service operating conditions • Partial discharge testing is a PREDICTIVE qualitative analysis tool that can warn from a potential upcoming system failure. • Partial discharge testing is Non Destructive Testing method • Partial discharge test results can be trended over time.

  15. Can it be damaged by corona? AN, RI, TVI concern? Decision Chart Corona- where? Critical component? Yes No Material type Critical location? No Yes No Photons per Minute Yes No Low<1000 Corona intensity? 1000<Medium<5000 Yes High> 5000 Schedule repair or replacement Monitor for additional signs Repair or replace ASAP Repair or replace ASAP

  16. Power Line losses New York State Public Service Commission AEP – American Electric Power * Yearly average corona loss at sea level based on 20% rain / 2% snow/ 78% fair weather conditions

  17. Don’t Stop The Line…