1 / 8

ND10 LOW IMPEDANCE RESTRICTED DIFFERENTIAL EARTH FAULT

ND10 LOW IMPEDANCE RESTRICTED DIFFERENTIAL EARTH FAULT. PROTECTIVE FUNCTIONS. 50/51 Phase overcurrent 50N/51N - 87NHIZ. Residual overcurrent or high impedance restricted differential ground fault 64REF Biased restricted differential ground fault BF Breaker Failure.

flower
Télécharger la présentation

ND10 LOW IMPEDANCE RESTRICTED DIFFERENTIAL EARTH FAULT

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ND10 LOW IMPEDANCE RESTRICTED DIFFERENTIAL EARTH FAULT

  2. PROTECTIVE FUNCTIONS • 50/51 Phase overcurrent • 50N/51N - 87NHIZ. Residual overcurrent or high impedance restricted differential ground fault • 64REF Biased restricted differential ground fault • BF Breaker Failure

  3. 64REF – MOST COMMON APPLICATIONS • Like every differential protective function 64REF is largely adopted in case of high selectivity needs. • Common applications are generator protection and transformer protection. G ~ 64REF 64REF

  4. BEFORE ND10 – 87NHIZ ONLY STABILIZING RESISTOR • SEVERAL CONS • Design • Large cubicle • Connections • Low liability • External devices NAXX 3 CT’s Low leakage reactance type according to IEC Class PX, TPS or BS Class X 87N METROSIL 50 51 3 CT’s Phase Currents EXPENSIVE SOLUTION

  5. ND10 – ONE DEVICE ONLY CT Residual current ND10 50 51 3 CT’s Phase Currents CHEAPER SOLUTION

  6. ND10 – 64 REF LOW IMPEDANCE FROM SAME INPUTS • Separate inputs for phase current and current from earth connection. • Earth overcurrent and biased restricted earth fault protective functions both contemporaneously performed. • Phase overcurrent protective function from same 3 CT’s set. ND10 64 REF 50N 51N 50 51 RELIABLE SOLUTION

  7. ND10 – MANY ADVANTAGES • Biased 64REF is internally calculated. • Easy connections. • RS and METROSIL design is not required. • No one external device is needed for stabilization. • Smaller cubicles. ND10 64 REF 50N 51N 50 51 EASIEST SOLUTION in case of EARTH FAULT DIFFERENTIAL FUNCTION

  8. Piazza Federico Mistral, 7 20139 Milano (MI) ITALY Tel: +39.02.5749571 Fax: +39.02.57403763 e-mail: thytronic@thytronic.it company web site: www.thytronic.it products web site: www.pro-n.it External Market Support Oscar Ornago tel. +39.02.57495753 e-mail: o.ornago@thytronic.it

More Related