1 / 10

Lesson 21: Alternator Capabilities and Mechanical Power Control

Lesson 21: Alternator Capabilities and Mechanical Power Control. ET 332b Ac Motors, Generators and Power Systems. Learning Objectives. After this presentation you will be able to: Explain the power balance in and alternator. Identify the operating region of an alternator’s capability curve.

grady
Télécharger la présentation

Lesson 21: Alternator Capabilities and Mechanical Power Control

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Lesson 21: Alternator Capabilities and Mechanical Power Control ET 332b Ac Motors, Generators and Power Systems Lesson 21_et332b.pptx

  2. Learning Objectives • After this presentation you will be able to: • Explain the power balance in and alternator. • Identify the operating region of an alternator’s capability curve. • Explain how a governor controls mechanical power input to an alternator • Compute governor droop. Lesson 21_et332b.pptx

  3. Power Balance in Alternators Alternator Ratings Alternators rated in kVA or MVA at a specified power factor Typical: 100 kVA, 480 V at 80% power factor Active power supplied by prime mover Reactive power determined by machine excitation Lesson 21_et332b.pptx

  4. Power Balance in Alternators Prime mover sized to handle largest active power load expected plus losses Maximum active power load occurs When Fp =1.0 so Srated= Pout Generally Most alternators supply reactive power also so Fp changes up to approximately 80% leading Prime Mover :Diesel Engine Lesson 21_et332b.pptx

  5. Alternator Capability Curve Reactive power output limited by machine excitation system Operating Range In this diagram + kVARs are delivered - kVARs are absorbed. 80% lead 80% lag Lesson 21_et332b.pptx

  6. Mechanical Power Input Control Governor - electromechanical speed control used to maintain constant speed as machine power load changes Power transfer between parallel alternators is controlled by change in prime-mover power input and speed. If speed remains constant, then torque increases as developed power increases n= constant Mechanical Power In Speed Increasing Torque Electric Power Out Torque Lesson 21_et332b.pptx

  7. Governor Characteristic and Speed Regulation Governor Speed Regulation Where nnl = no-load speed of machine (rpm) nrated = rated machine speed (rpm) frated = rated frequency (Hz) fnl = no-load frequency (Hz) Prime-mover Governor Characteristic – relates speed (frequency) change to alternator power output Lesson 21_et332b.pptx

  8. Governor Characteristic Curve fnl and nnl 61.2 Hz 3672 rpm rated f and n 60 Hz 3600 rpm GD f (Hz) n (rpm) rated P out 0 0 500 kW P (kW) Governor Droop-the slope of the governor control characteristic. Units - Hz\W or Hz\kW or Hz\MW Formula Lesson 21_et332b.pptx

  9. Governor Characteristic Curve Example Example 21-1: Find the speed regulation and the governor droop for the machine that has the curve shown 61.2 Hz 3672 rpm 60 Hz 3600 rpm GD f (Hz) n (rpm) 0 0 500 kW P (kW) Lesson 21_et332b.pptx

  10. End Lesson 21: Alternator Capabilities and Mechanical Power Control ET 332b Ac Motors, Generators and Power Systems Lesson 21_et332b.pptx

More Related