Potential Pathways for Coliform Contamination

hollye
Télécharger la présentation

Potential Pathways for Coliform Contamination

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


    1. Potential Pathways for Coliform Contamination

    2. Fixing Positive Coliform Results

    3. Fixing Positive Coliform Results Adopt the mentality that every positive coliform result has a source. Thoroughly investigate to determine potential sources. Do not flush and disinfect the entire system following a positive routine result.

    4. Fixing Positive Coliform Results Understand that repeat samples are intended to determine whether coliform contamination is widespread or isolated. Take repeat samples at the correct locations. Review past monitoring results to see if there are any trends.

    5. Fixing Positive Coliform Results If the system uses sodium hypochlorite for disinfection, review: procedures for replacing or freshening-up the hypochlorite feed solution chlorine residual monitoring frequency in the distribution system locations for chlorine residual monitoring expiration date of test kit chemicals water usage records, particularly peak usage vs. chlorine feed and contact time

    6. Investigative Sampling If after thoroughly inspecting the system for potential pathways for the coliform contamination you still have not identified a source, take investigative samples of the: water source storage tank each section of the distribution system Check the box on the the bacteriological sampling form that the samples are “special” or “investigative”.

    9. If Potential Coliform Source Cannot Be Identified Shutdown the system if a source cannot be found. Flush and disinfect the storage tank and distribution system completely if a source cannot be identified. If the source is determined to be contaminated, disinfect it obtaining a free chlorine residual of 100 mg/L.

    10. If Potential Coliform Source Cannot Be Identified Premix your chlorine solution in a container. Pour the solution into the well through a hose which the hose is being raised and lowered through the water. Hold the chlorine in the source for at least 24-hours. Pump the well or flush out the spring box until the chlorine residual is 1 mg/l or less.

    14. Disinfection of the Distribution System To disinfect the distribution system chlorinate the source and pump or feed the water into the system. Let the water run out of each tap until a chlorine odor is detected. Hold the chlorinated water in the distribution system for at least 24-hours. Keep the chlorinated water out of nearby surface water.

    15. Start your search at the well house.

    16. Check the well casing to see if its properly sealed

    17. An incomplete repair may be a source

    20. Can surface water runoff infiltrate around the well casing?

    21. Seal any cracks in the concrete pad around the casing. Pad should extend above grade and slope away from the casing. Hand pump pad should have a drain that discharges to grade at least 100 feet away.

    23. Surface water runoff into vaults associated with the water system is another potential pathway for contaminates

    24. Surface water runoff and sediment has potentially contaminated the filter Avoid putting anything that must be maintained in a vault.

    26. Can surface water pond about the well casing?

    27. Is the casing sealed to prevent dirt and runoff from entering?

    28. Is the well subject to flooding or is it under the direct influence of surface water?

    29. Is there a septic system or other source of coliforms within 100 feet of the well?

    30. Is there a vault toilet within 100 feet of the well?

    31. A vault toilet you would be proud to take Mom to.

    32. Storage tanks are common source of contamination. If sediment accumulates in the tank, periodic cleaning and disinfecting is necessary.

    33. An overflow that is not properly screened provides a pathway for rodents and other small animals. At least a #4 mesh screen sandwiched between flanges should be installed.

    34. If possible, overflow should terminate 12 to 24 inches above grade to make it more for rodents to tamper with the screen.

    35. Divert surface water runoff away from storage tank access hatches

    36. Keep access hatch locked or otherwise secured

    37. Keep hatch covers well above grade and ensure their covers are sealed with a gasket

    38. Remove tall vegetation around the well that your sample containers may brush against

    39. Debris accumulated in the well house may be a source of contamination Maintain the structure to prevent rodents from living in it

    40. Properly seal all abandoned wells

    43. Stagnant water due to excessive storage volume may cause grown of heterotrophic (noncoliform) bacteria.

    44. Corrosion inside very old tanks will affect the quality of the water

    45. Provide a separate water line with backflow prevention on it to meet fire demands

    46. Cross Connections Has the water system pressure dropped below 20 psi shortly before the positive coliform result due to: water line break high water demand (e.g., opening of a hydrant to fill fire engines) Are backflow preventors installed on all potential cross connections?

    47. A reduced pressure backflow preventor should be installed on lawn irrigation lines Backflow preventors should be tested annually to ensure they are functioning properly

    48. Are vacuum breakers installed on all hose bibs?

    49. Install vacuum breakers with manual drains to prevent the tap from freezing

    53. Do shop sink faucets have built in backflow preventors?

    54. Springs

    55. Check isolation and air relief valves on the line from the spring to the site to determine whether they are impacted by runoff or soil erosion

    56. Ensure storage tank hatch is not subject to surface water runoff

    57. Check that the access hatch is bolted closed and sealed with a gasket

    58. The vent must be screened to keep insects out

    59. Does the spring also supply wildlife or cattle troughs?

    60. Are total separate water lines run for drinking vs. wildlife/cattle?