An Electrically Isolated UPS System with Surge Protection

Department of Electrical and Computer Engineering Part IV Project. An Electrically Isolated UPS System with Surge Protection. Presented by: Thusitha Mabotuwana Duleepa Thrimawithana Supervisors : Mr. Nihal Kularatna Dr. Patrick Hu. Presentation Outline. Project background

indra
Télécharger la présentation

An Electrically Isolated UPS System with Surge Protection

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Department of Electrical and Computer Engineering Part IV Project An Electrically Isolated UPS System with Surge Protection Presented by: Thusitha Mabotuwana Duleepa Thrimawithana Supervisors : Mr. Nihal Kularatna Dr. Patrick Hu

  2. Presentation Outline • Project background • Transients and transient protection • Current protection mechanisms and drawbacks • A new transient minimisation scheme • Supercapacitors as energy storage devices • System we have implemented • Power stage design and control • Results • Future developments • Conclusions

  3. Project Background • Immense damage caused to electronic equipment by heavy lightning. • Current low cost UPS systems have limited protection. • Systems with good protection schemes are very costly and bulky – not suitable for domestic use.

  4. Project Goals • Design and develop a new UPS topology with complete isolation between supply and load. • Investigate possibilities of using supercapacitors for energy storage in UPS.

  5. What are Transients? • Forms of transients • Spikes (in excess of 6000V in less than 200µs) • Surges (about 20% over nominal line voltage. Lasts for about 15-500ms) • Sags (similar to surges. But under-voltage condition) • Electrical impulse noise (high frequency interference) • Blackouts and brownouts (total or short-duration power loss)

  6. What is Transient Protection? • Protection of user devices from whatever that happens at the primary power sources or in the environment.

  7. Current UPS Systems

  8. Our Tasks and Specifications • Investigate possibilities of using supercapacitors for power transfer while maintaining complete isolation. • Design a UPS with the following specifications: • Input voltage – 230VAC at 50/60Hz • Output voltage – 230VAC at 50Hz • Output regulation – ±5% • Output power – 100W • Common and differential mode isolation Common mode surge Differential mode surge Diagrams reproduced from Kularatna, N. (1998) Power Electronics Handbook. Boston, Newnes.

  9. System Overview

  10. Why Supercapacitors? • Properties of supercapacitors • Very high capacitance (even 1000F) • High power density • Virtually unlimited number of charge-discharge cycles • No toxic substances like in conventional batteries • Low energy density • High ESR Extracted from Prophet, G. (2003). EDN. Supercaps for Supercaches, January, 53-58

  11. New Concept for Surge Minimisation

  12. New Concept for Surge Minimisation (cntd..) Energy Pump Inverter and Load Charge Transfer Unit

  13. Our System

  14. Energy Pump • Current controlled forward converter topology was used. • Simple and economical design • Less number of exposed components to the main supply • Provide electrical isolation

  15. Energy Pump (cntd…)

  16. Charge Transfer Unit • Transfers power to the inverter while maintaining isolation. • Banks are switched so that the discharging bank is not connected to the input. • Supercapacitor banks cycle through charging-standby-discharging cycles.

  17. Charge Transfer Unit (cntd…) 3rd bank (Discharging) 2nd bank (Standby) 1st bank (Charging)

  18. Charge Transfer Unit (cntd…) • Charge transfer unit output waveforms: Output waveform Charging logic Discharging logic 1V ripple 2V ripple

  19. Charge Transfer Unit (cntd…) • Load regulation characteristics when tested with the commercial inverter confirmed supercapacitors’ capability to transfer energy.

  20. Charge Transfer Unit (cntd…) • Discharge time for a supercapacitor bank of 0.2F based on load variations:

  21. Inverter • Needed a single stage sine wave inverter. • Some techniques we looked at: • PWM • PAM • Square wave • Resonant • Decided to implement a single stage PWM push-pull scheme.

  22. Inverter (cntd…)

  23. Inverter (cntd…) • Inverter output characteristics with a 25W load:

  24. Inverter (cntd…) • Load regulation characteristics:

  25. System Cost

  26. Future Developments • Develop a commercial prototype • Consider use of cheaper supercapacitors with higher capacitance. • Optimise inverter and energy pump modules. • Consider a compact FPGA or DSP implementation strategy.

  27. Conclusions • A method of energy transfer using supercapacitors has successfully been implemented. • Complete supply-load isolation has been achieved using three supercapacitor banks with dynamic transfer. • Sine wave inverter based on a 1kHz PWM has been implemented. • Charger has been implemented using a forward converter with current mode control.

  28. Questions?