1 / 20

Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li. Structural Design. Current Footprint – 60’x80’. Notes - Footprint. Cut and fill enough to fill hole without extra soil left over Strip footing Soil – mostly clay Minimum 5’ from boundaries

jadzia
Télécharger la présentation

Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Health Clinic – Las Mercedes, HondurasJanelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

  2. Structural Design

  3. Current Footprint – 60’x80’

  4. Notes - Footprint • Cut and fill enough to fill hole without extra soil left over • Strip footing • Soil – mostly clay • Minimum 5’ from boundaries • Allow space for latrine

  5. Current Floor Plan

  6. Notes - Plan • Use spaces on exterior – optimize sunlight • Kitchen on right – minimize distance to latrine • Sink near shower – minimize piping • Delivery near kitchen for access to hot water (as opposed to being connected to Recovery) • 8’ hallways for easy maneuverability (i.e. moving beds, etc.) • 2 entrances – main (to waiting area) and kitchen (to load supplies/easy access to latrine)

  7. Other Notes • Roof – corrugated tin and corrugated translucent material (optimize sunlight) • 10’ walls • Materials: CMU (8”x8”x16”), rebar, poured concrete base, wood beams for roof support system • Sketch-up Model

  8. Next steps • Convert to metric • Determine optimal base depth for cut and fill • Design roof structure • Determine loads • Find North for solar panel/roof design

  9. Standard Solar Powered System Design

  10. Our System 6 x Isofoton 75 Watt solar panel WyckomarUV-250 UV water filters Xantrex 40 amp + 30 amp charge controller 600 watt power inverter 12 V 115 amp hr Nautlius deep cycle battery 3 x Low powered laptops Sunfrost Vaccine Refrigerator Thin-Lite DC fluorescent lights

  11. Location of Load componets 30 watt lights 13 watt lights Battery /Charge Controller/Inverter Storage 13 watt lights Vaccine Fridge 13 watt lights/Laptops

  12. Calculations for Total Power Consumption Total power consumption = Σ Appliance Wattage rating * Hours used/day *Total number of Appliance

  13. Sizing the solar panel Monthly Averaged Insolation Incident On A Horizontal Surface (kWh/m2/day) Solar panels are tested at 1000 W/m at 25 ⁰ C The solar panel should be able provide the required wattage at both the summer and winter hours For temperature ranges between 25⁰ and 40⁰ C, the power output is close to linear http://www.reuk.co.uk/Effect-of-Temperature-on-Solar-Panels.htm] 75 watt panels = 75/1000 = 0.075 % efficiency At lowest solar isolation of 4.13 kWh/m2/day produces 4.13 * 0.075 = 310 watts per panel Total number of panels needed = Total power consumption/watts per panel = 1760/310 = 5.6 panels ≈ 6 panels minimum To compensate for cloudy days and system losses, 7-8 solar panels may be necessary

  14. Sizing the battery system Nautilius Deep cycle are rated at 115 amp hrs and 12 volts for a total of 1380 watt hrs Although deep cycles can be discharged to 80 %, they have a much larger cycles is discharged at lower percentages This is a graph comparing cycles of discharge vs. discharge %

  15. We want both a long lifespan for our system and also the power the solar fridge for several days if there are consecutive cloudy or rainy days/solar panel malfunctions Aiming for optimally 20 % discharge rate, each battery would be able to provide 0.2* 1380 = 276 Watt hours Number of batteries needed = Total wattage/ Watt hour per battery = 1760 /276 = 6.3 ≈ 7 batteries After 2 days, total watt hours available = (0.8)2 * 7 * 1380 = 6048 watt hrs This can still provide 16 days of the vaccine fridge running by itself At 20% discharge rate, the batteries will last for 2500 cycles. Assuming 1 cycle per day for each battery = 2500/365 = 6.8 years before replacement. This will probably be 6 years, due to some over discharging.

  16. Sizing the Charge controller The charge controller prevents the batteries from overcharging/discharging, maintains the rates of charging/discharging, keeps power from batteries from going back into solar panels, and also converts the variable voltage from the solar panels into a steady voltage For 75 watt solar panel, should be at 75 watts/12 volts = 6 amps, however this current can spike up to 8 amps. For our solar system, 7 * 8 amps = 56 amps. Thus we could use two charger controllers, a 40 amp and a 30 amp charge controller.

  17. Sizing the Inverter A 600 watt system will have enough capacity to power 5 amp tools, fans, and also our needs for a water filter, and laptops. The water filter = 30 watts 3 laptops total = 24 watts The 600 watt system will exceed our daily needs but will allow greater expansion of AC appliances.

  18. Choosing the laptop Netbooks are very power efficient The Dell mini 9 makes if easy to upgrade RAM and hard drive The solid-state hard drive is less likely to fail Linux drive Operating System can be re-installed and rebooted from a USB drive, and thus making system recovery very easy

  19. Choosing the Vaccine Fridge Sunfrost energy specifications Energy Consumption (12 volt) making 2.2 kg ice/day .38 kWh/day @ 32° C (90° F) Running Current: 4.5 amps for 12 volt system, 2.3 amps for 24 volt system Starting Current: 15 amps for 12 volt system, 7.5 amps for 24 volt system

  20. The Sunfrost Fridge: • has been approved by the World Health Organization • is very power efficient • can maintain a fridge temperature of 3° C at a large range of temperatures