UNINTERRUPTIBLE POWER SUPPLIES. JOHN LIGUORI CONSULTING ENGINEER MSEE, PE. PRESENTED TO THE IEEE LONG ISLAND CONSULTANT’S NETWORK 9/6/06. UNINTERRUPTIBLE POWER SUPPLIES.

jsutherland
Télécharger la présentation

UNINTERRUPTIBLE POWER SUPPLIES

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. UNINTERRUPTIBLE POWER SUPPLIES JOHN LIGUORI CONSULTING ENGINEER MSEE, PE PRESENTED TO THE IEEE LONG ISLAND CONSULTANT’S NETWORK 9/6/06

  2. UNINTERRUPTIBLE POWER SUPPLIES • THIS PRESENTATION IS FOR INFORMATIONAL AND EDUCATIONAL PURPOSES ONLY. IT DOES NOT CONTAIN ALL INFORMATION REQUIRED, AND IS NOT INTENDED TO BE USED FOR THE SPECIFICATION OR DESIGN OF UNINTERRUPTIBLE POWER SUPPLIES (UPS) OR UPS SYSTEMS.

  3. UNINTERRUPTIBLE POWER SUPPLIESOUTLINE • INTRODUCTION • POWER DISTURBANCES • UNINTERRUPTIBLE POWER SUPPLIES • GENERAL DISCUSSION • SUMMARY • REFERENCES • QUESTIONS

  4. INTRODUCTION • PURPOSE • WHAT IS AN UNINTERRUPTIBLE POWER SUPPLY? • WHY USE A UPS?

  5. PURPOSE • THE PURPOSE OF THIS PRESENTATION IS TO DISCUSS THE DIFFERENT TYPES OF UNINTERRUPTIBLE POWER SUPPLIES AVAILABLE, WHAT THE UPS PROTECTS AGAINST, THE COMPONENTS OF A UPS, AND ISSUES REGARDING SELECTION AND SIZING. • THE DIFFERENT TYPES AND CAUSES OF POWER DISTURBANCES ARE DISCUSSED, AS WELL AS WHAT THE POWER UTILITY, THE ORIGINAL EQUIPMENT MANUFACTURER, AND YOU, CAN DO TO MINIMIZE THEIR EFFECT.

  6. WHAT IS AN UNINTERRUPTIBLE POWER SUPPLY? • AN UNINTERRUPTIBLE POWER SUPPLY (UPS) IS A DEVICE THAT HAS AN ALTERNATE SOURCE OF ENERGY THAT CAN PROVIDE POWER WHEN THE PRIMARY POWER SOURCE IS TEMPORARILY DISABLED • THE SWITCHOVER TIME MUST BE SMALL ENOUGH TO NOT CAUSE A DISRUPTION IN THE OPERATION OF THE LOADS

  7. WHY USE A UPS? • PROTECTS AGAINST MULTIPLE TYPES OF POWER DISTURBANCES • ONLY DEVICE THAT PROTECTS AGAINST AN OUTAGE • OFFERS PROTECTION AGAINST • EQUIPMENT NOT OPERATING PROPERLY • COMPUTER AND EQUIPMENT DAMAGE • DATA LOSS • TIME AND EXPENSE TO RECOVER BACK TO WHERE YOU WERE, IF EVEN POSSIBLE

  8. POWER DISTURBANCES • CAUSES • TYPES • DURATION • RESULTING PROBLEMS • COMMENTS • WHAT THE POWER UTILITY CAN DO • WHAT THE ORIGINAL EQUIPMENT MANUFACTURER (OEM) CAN DO • WHAT YOU CAN DO • PROTECTIVE DEVICES

  9. CAUSES OF POWER DISTURBANCES • STORM ACTIVITY – LIGHTNING, WIND, ICE • OBJECTS COMING IN CONTACT WITH POWER LINE AND TRIPPING BREAKER – TREE BRANCHES, ANIMALS, OTHER • UTILITY FAULT CLEARING • CONSTRUCTION ACTIVITY • ACCIDENTS – MOTOR VEHICLE, OTHER • EQUIPMENT FAILURE • OVERLOADING • LOAD SWITCHING • NON-LINEAR LOADS • POOR GROUNDING • ESD

  10. TYPES OF POWER DISTURBANCES • INTERRUPTION • SAG, UNDER VOLTAGE • SURGE, OVER VOLTAGE • VOLTAGE FLUCTUATION • FREQUENCY VARIATION • SPIKES / TRANSIENTS • IMPULSIVE • OSCILLATORY • WAVEFORM DISTORTION • DC OFFSET • HARMONICS • INTERHARMONICS • NOTCHING • NOISE • VOLTAGE IMBALANCE

  11. DURATION OF POWER DISTURBANCES • INSTANTANEOUS - ½ CYCLE (8 1/3 ms) OR LESS • MOMENTARY - ½ CYCLE TO 3 SEC • TEMPORARY - 3 SEC TO 1 MIN • SUSTAINED - GREATER THAN 1 MINUTE

  12. CLASSIFICATION OF PROBLEMS RESULTING FROMPOWER DISTURBANCES • DISRUPTIVE • EQUIPMENT DOES NOT OPERATE AS INTENDED • DISSIPATIVE • EQUIPMENT EXPERIENCES REPEATED STRESSES THAT LEAD TO FAILURE LATER FOR NO APPARENT REASON • DESTRUCTIVE • EQUIPMENT FAILS AT THE INSTANT THE DISTURBANCE OCCURS

  13. PROBLEMS RESULTING FROMPOWER DISTURBANCES • DATA ERRORS • DATA LOSS • BLOWN FUSES • TRIPPED BREAKERS • INTERFERENCE WITH CONTROL OF LOADS • OVERLOADED NEUTRAL CONDUCTORS • MOTORS • HEATING • SPEED VARIATION • STALLING • AUDIBLE NOISE • VIBRATION • TRANSFORMERS • HEATING • AUDIBLE NOISE • VIBRATION

  14. POWER DISTURBANCES - COMMENTS • NOT ONLY IS MODERN EQUIPMENT MORE SUSCEPTIBLE TO POWER DISTURBANCES, BUT THE EQUIPMENT ITSELF GENERATES MORE DISTURBANCES • ALL LOADS, FROM LARGE POWERFULL MOTORS AND INDUSTRIAL EQUIPMENT TO SMALL, SENSITIVE ELECTRONIC COMPONENTS, ARE CONNECTED TO THE SAME POWER GRID

  15. WHAT THE POWER UTILITY CAN DO TO MINIMIZE THE EFFECT OF POWER DISTURBANCES • INSTALL STORM RESISTANT WIRING • USE INFRA RED SCANNING TO DETECT WEAK SPOTS IN POWER LINES • INSTALL REMOTE CONTROLLED RADIO SWITCHES TO RESTORE POWER QUICKLY • CLEAR TREE LIMBS AWAY FROM POWER LINES

  16. WHAT THE OEM CAN DO TO MINIMIZE THE EFFECT OF POWER DISTURBANCES BUILD EQUIPMENT CONTAINING ONE OR MORE INTERNAL PROTECTIVE DEVICES • SURGE PROTECTIVE DEVICES • LINE FILTERS • ISOLATION TRANSFORMER • BATTERY OR CAPACITOR BACK UP TO INCREASE RIDE THROUGH TIME

  17. WHAT YOU CAN DO TO MINIMIZE THE EFFECT OF POWER DISTURBANCES • BUY EQUIPMENT THAT HAS INTERNAL PROTECTIVE DEVICES • FOR EXAMPLE, BATTERY BACK UP FOR ANY APPLIANCE THAT CONTAINS A CLOCK • USE ONE OR MORE EXTERNAL PROTECTIVE DEVICES • SURGE PROTECTORS • LINE FILTERS • ISOLATION TRANSFORMER • VOLTAGE REGULATING LINE CONDITIONER • UPS

  18. PROTECTIVE DEVICES OTHER THAN UPS • SURGE PROTECTIVE DEVICES – SPD’S PROTECTS AGAINST SPIKES OF LIMITED ENERGY • METAL OXIDE VARISTORS – MOV • DIODES • GAS TUBES • LCR FILTERS • HYBRIDS • LINE FILTERS FILTERS OUT HARMONICS, TRANSIENTS AND NOISE • ISOLATION TRANSFORMER ELIMINATES DC OFFSET AND NOISE • VOLTAGE REGULATING LINE CONDITIONER AUTOMATICALLY ADJUSTS FOR UNDER AND OVER VOLTAGES • CONSTANT VOLTAGE TRANSFORMER - CVT • MOTORIZED VARIAC

  19. POWER DISTURBANCESANDPROTECTIVE DEVICES

  20. UPS • ARCHITECTURES • WAVEFORMS • INVERTER TECHNOLOGY • COMPONENTS • SWITCHOVER TIME • ADVANTAGES / DIS-ADVANTAGES • SIZING • BATTERY SAFETY

  21. UPS ARCHITECTURES • LINE INTERACTIVE • ON-LINE

  22. BLOCK DIAGRAMLINE INTERACTIVE UPS AUTOMATIC SWITCH CRITICAL LOAD (AC) AC SUPPLY BATTERY CHARGER INVERTER DC TO AC BATTERY AC FAIL

  23. BLOCK DIAGRAMON-LINE UPS AUTOMATIC SWITCH CRITICAL LOAD (AC) AC SUPPLY CONVERTER AC TO DC INVERTER DC TO AC BATTERY INVERTER FAIL

  24. BLOCK DIAGRAMLAPTOP COMPUTER POWER SUPPLY CRITICAL LOAD (DC) AC SUPPLY CONVERTER AC TO DC CONVERTER DC TO DC BATTERY

  25. UPS WAVEFORMS • TRUE SINEWAVE • MODIFIED SINEWAVE • SQUARE WAVE

  26. UPS WAVEFORMS

  27. INVERTER TECHNOLOGY FOR TRUE SINEWAVE • PULSE WIDTH MODULATION - PWM • LINEAR AMPLIFIER • RESONANT INVERTER

  28. BLOCK DIAGRAMPWM INVERTER DC POWER CRITICAL LOAD (AC) HIGH FREQUENCY GENERATOR PULSE WIDTH MODULATOR BASE / GATE DRIVE TRANSISTOR BRIDGE TRANSFORMER FILTER REFERENCE SINEWAVE GENERATOR COMPARISON AMPLIFIER

  29. BLOCK DIAGRAMLINEAR AMPLIFER INVERTER DC POWER CRITICAL LOAD (AC) SINEWAVE OSCILLATOR TRANSFORMER OSCILLATOR AMPLIFIER COMPARISON AMPLIFIER POWER AMPLIFIER

  30. BLOCK DIAGRAMRESONANT INVERTER DC POWER CRITICAL LOAD (AC) SQUARE WAVE GENERATOR SWITCH DRIVE TRANSISTOR SWITCHES TRANSFORMER LC RESONANT TANK FILTER (OR FERRORESONANT)

  31. UPS COMPONENTS • CONVERTER - AC TO DC • SPD - PROTECTS AGAINST SPIKES AND TRANSIENTS • BATTERY • STORED ENERGY DEVICE - PROTECTS AGAINST INTERRUPTIONS • INVERTER – DC TO AC • WAVEFORM SYNTHESIS – PROTECTS AGAINST DC OFFSET AND INTERHARMONICS • FILTER – PROTECTS AGAINST HARMONICS, NOTCHING AND NOISE • VOLTAGE REGULATOR – PROTECTS AGAINST SAGS, SURGES AND FLUCTUATIONS • MONITOR AND CONTROL HARDWARE / SOFTWARE

  32. SWITCHOVER TIME • A TYPICAL SWITCHOVER TIME 2 – 4 ms ONE QUARTER CYCLE OR LESS FOR SOME EQUIPMENT THIS IS NOT TOLERABLE

  33. ADVANTAGES / DIS-ADVANTAGES OF THE DIFFERENT UPS ARCHITECTURES • LINE INTERACTIVE ADVANTAGES • AC TO DC CONVERTER / BATTERY CHARGER DOES NOT HAVE TO PROVIDE FULL LOAD POWER (POTENTIALLY CHEAPER) • LESS STRESS ON DC TO AC INVERTER SINCE IT RUNS AT NO LOAD UNTIL UPS SWITCHES TO BATTERY POWER (POTENTIALLY CHEAPER) • ON-LINE ADVANTAGES • ZERO SWITCHOVER TIME FROM MAIN LINE TO BATTERY POWER • ALWAYS ISOLATED FROM POWER DISTURBANCES ON THE MAIN LINE

  34. SIZING THE UPS • EQUIPMENT RATINGS FOR LOADS • OBTAIN RATINGS FROM NAMEPLATE OR SPEC SHEET • ENERGY USAGE MAY BE SPECIFIED IN VOLT AMPS (VA) OR WATTS (W) AND IN VALUES THAT ARE EITHER MAXIMUM OR NOMINAL • (VA) AND (W) ARE RELATED VIA THE POWER FACTOR • TOTAL UPS LOAD MUST NOT EXCEED THE UPS VOLT AMP (VA) RATING • TOTAL UPS LOAD MUST NOT EXCEED THE UPS WATT (W) RATING • OVERSIZE / DERATE TO ADD LIFE • RUNTIME CHARTS

  35. UPS SIZING – EXAMPLE SPREADSHEET

  36. BATTERY SAFETY • MAINTENANCE • INSPECT PERIODICALLY • REPLACE AS NEEDED • RISKS • ACID • ELECTRIC SHOCK • BURN • FLYING, MOLTEN METAL (EYES) • INJURIES RESULTING FROM CARRYING HEAVY BATTERY PACKS • DISPOSAL • DISPOSE OF PROPERLY • RECYCLE WHENEVER POSSIBLE

  37. GENERAL DISCUSSION • DOES A UPS OFFER COMPLETE PROTECTION? • DO YOU THINK “POWER DISTURBANCES WON’T HAPPEN TO YOU” ? • MISCELLANEOUS

  38. DOES A UPS OFFER COMPLETE PROTECTION? • SOME POWER DISTURBANCES MAY EXCEED THE HANDLING CAPABILITY OF THE UPS • UPS FAILURE

  39. DO YOU THINK “POWER DISTURBANCES WON’T HAPPEN TO YOU” ? • POWER DISTURBANCES OCCUR FREQUENTLY, THOUGH MANY ARE SMALL AND WITHOUT CONSEQUENCE • AN ON-LINE UPS CAN PROTECT AGAINST MORE SIGNIFICANT POWER DISTURBANCES WHEN THEY DO OCCUR • THE COST OF NOT HAVING A UPS CAN EASILY EXCEED THE COST OF A UPS

  40. MISCELLANEOUS • MANY RETAIL UPS FOR COMPUTER APPLICATIONS ARE LINE INTERACTIVE • MANUFACTURERS AND BUILDING CODES DO NOT ALLOW EXTENSION CORDS OR SURGE SUPPRESSORS TO BE USED WITH A UPS

  41. SUMMARYTHINGS TO CONSIDER WHEN SPECIFYING A UPS • POWER QUALITY • ARCHITECTURE - LINE INTERACTIVE OR ON-LINE • WAVEFORM - SQUARE, MODIFIED SINE, TRUE SINE • IMMUNITY TO DISTURBANCES OTHER THAN OUTAGE • RUN TIME WITH AN OUTAGE • RELIABILITY • AUDIBLE NOISE • MONITOR AND CONTROL HARDWARE / SOFTWARE • LOCAL / REMOTE CONTROL • INITIAL COST • MAINTENANCE COST • WARRANTY

  42. REFERENCES • IEEE STANDARD 1100-2005 RECOMMENDED PRACTICE FOR POWERING AND GROUNDING SENSITIVE ELECTRONIC EQUIPMENT • IEEE STANDARD 1159-1995 RECOMMENDED PRACTICE FOR MONITORING ELECTRICAL POWER QUALITY