1 / 11

Project 2007-01 Underfrequency Load Shedding PRC-006, 007 and 009

Project 2007-01 Underfrequency Load Shedding PRC-006, 007 and 009. Bob Millard Reliability First staff Reliability Standards Workshop April 29-30, 2008. Overview Underfrequency Load Shedding Project 2007-01. Revise 3 standards related to Underfrequency Load Shedding ( UFLS ):

judyw
Télécharger la présentation

Project 2007-01 Underfrequency Load Shedding PRC-006, 007 and 009

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Project 2007-01Underfrequency Load SheddingPRC-006, 007 and 009 Bob Millard ReliabilityFirst staff Reliability Standards Workshop April 29-30, 2008

  2. OverviewUnderfrequency Load Shedding Project 2007-01 • Revise 3 standards related to Underfrequency Load Shedding (UFLS): • PRC-006: Develop & Document Regional Reliability Organization UFLS Program • PRC-007: Assure Consistency with Regional UFLS Programs • PRC-009: Analyze & Document UFLS Performance Following an Underfrequency Event Note: PRC-008, UFLS Maintenance & Testing was transferred to Project 2007-17 NERC Standards Workshop 4/29, 30/08

  3. UFLS SDT RosterUnderfrequency Load Shedding Project 2007-01 • Dana Cabbell — Southern California Edison Co. (Chair) • Paul Attaway — Georgia Transmission Corporation • Brian Bartos — Banders Electric Cooperative • Larry E. Brusseau — Midwest Reliability Organization • Jonathan Glidewell — Southern Co. Transmission • Geral Keenan — Bonneville Power Administration • Robert W. Millard — ReliabilityFirst Corporation NERC Standards Workshop 4/29, 30/08

  4. UFLS SDT Roster (Continued)Underfrequency Load Shedding Project 2007-01 • Steven Myers — Electric Reliability Council of Texas • Mak Nagle — Southwest Power Pool • Robert J. O'Keefe — American Electric Power • Philip Tatro — National Grid • Robert Williams — Florida Municipal Power Agency • David Taylor — NERC NERC Standards Workshop 4/29, 30/08

  5. ObjectiveUnderfrequency Load Shedding Project 2007-01 • Eliminate “fill-in-the-blank” characteristics RRO responsibilities (currently present in PRC-006) • Determine whether UFLS “program” requirements should be continent-wide and/or regional (related to PRC-006 and 007) • Consider effectiveness & infra structure existing • Consider implementation concerns • Determine how to address event reporting (currently in PRC-009) NERC Standards Workshop 4/29, 30/08

  6. Current DirectionUnderfrequency Load Shedding Project 2007-01 • Various combinations of “load steps” & “frequency set points” can achieve objective. • Current programs repeatedly studied for effectiveness. • Changing to one “program” would take time & money. • APPROACH - Identify performance characteristics/requirements for developing regional reliability standards. NERC Standards Workshop 4/29, 30/08

  7. Regional Performance RequirementsUnderfrequency Load Shedding Project 2007-01 • Direct development of Regional Standards for implementing automatic UFLS to arrest & recover declining system frequency. Each Regional Standard shall address the following UFLS performance requirements: • Frequency decline shall be arrested at no less than 58.0 Hz. • Frequency shall not remain below 58.5 Hz for greater than 10 seconds, cumulatively, and shall not remain below 59.5 Hz for greater than 30 seconds, cumulatively. NERC Standards Workshop 4/29, 30/08

  8. Regional Performance CharacteristicsUnderfrequency Load Shedding Project 2007-01 • Frequency overshoot resulting from operation of UFLS relays shall not exceed 61.0 Hz for any duration and shall not exceed 60.5 Hz for greater than 30 seconds, cumulatively. • Bulk Electric System voltage during and following UFLS operations shall be controlled such that the per unit Volts per Hz (V/Hz) will not exceed 1.18 for longer than 6 seconds cumulatively, and will not exceed 1.10 for longer than 1 minute cumulatively. • Functional Entities responsible for developing, analyzing and implementing the “program” shall be identified. NERC Standards Workshop 4/29, 30/08

  9. Current DirectionUnderfrequency Load Shedding Project 2007-01 • Analysis & reporting of an “event” is not unique to UFLS • Past standards required “event” information be submitted to NERC • ERO responsible for System oversight • APPROACH – Administer “event” through ERO Rules of Procedure and relationship with Regional Entities NERC Standards Workshop 4/29, 30/08

  10. Status & Schedule • Draft standard ready to post for 45 day comment period • Response to comments and repost as appropriate • Provide direction for development of Regional Standards early 2nd quarter 2008 • Propose completion of Regional Standards approximately 18 months later • Process through NERC and FERC – available for formal implementation 2 – 2 ½ yrs from now NERC Standards Workshop 4/29, 30/08

  11. Questions?Underfrequency Load Shedding Project 2007-01 • Dana Cabbell (Chair), Southern California Edison Co. • dana.cabbell@sce.com • David Taylor, NERC Standards Coordinator • David.Taylor@nerc.net NERC Standards Workshop 4/29, 30/08 11

More Related