An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Finite State Machine in DCS G. De Cataldo, CERN CH-INFN Ba, A. FrancoINFN Bari

  2. The TPC and HMPID have already approached and (partially) implemented a FSM CS. As given examples, let’s see the HMPID prototype PVSS JCOP FW, SMI++, CAEN OPC, Simens OPC WN200 Workstation CAEN SY1527 PLC S7 PLC S7 C6F14 Circulation Low Voltage High Voltage Physical parameters Cooling Gas G. De Cataldo, CERN CH-INFN Ba, A. FrancoINFN Bari Kracow - LEB 2000 - 11-15/9/2000 G. De Cataldo, A.Franco; INFN-Bari - 14

  3. A possible HV State Diagram OFF The yellow states are automatically left when all the related actions are accomplished. GO_STANDBY (Config Name) RESET The GO_STANDBYcommand provides to the HV control program the “Name” of the configuration to be downloaded. CONFIG ERROR GO_OFF STATES OFF: The HV power supply is switched ON but no VH is on the channel output; STANDBY: all the board and channel parameters have been configured but no VH are on the channel output ON: after the HV Ramp Up, all the enabled channels have the set Voltage on the output. ERROR: alarm conditions, e.g.:over-current, over-voltage,over-temperature,……, push the control system in the ERROR state. Once the alarm condition is removed and the operator acknowledgement is given, then it will be possible to issue the RESET command and restart the system Alarm Conditions HVSS Configured ! STAND BY All Modules are in STANDBY ! GO_ON RMdw RMup RESET ON All Modules are in READY ! GO_RDWn G. De Cataldo, CERN CH-INFN Ba, A. FrancoINFN Bari

  4. HMPID DCS State Diagram OFF GO_STANDBY (Config Name) RESET The GO_STANDBY command provides to the control system the “Name” of the configuration to be downloaded. ERROR CONFIG GO_OFF Alarm Conditions All Sub System are Configured ! STAND BY All Sub System are in STANDBY ! During the Count Down to READY State, to operate safely the detector, the READY commands to all the sub systems are dispatched according to a defined sequence. This synchronization is ensured by the DCS control program. GO_READY Count Down to READY Count Down to STANDBY All DCS Sub Systems are READY ! READY GO_RDWn G. De Cataldo, CERN CH-INFN Ba, A. FrancoINFN Bari

  5. HMPID DCS Control & Device Units Architecture SMI Control Unit HMPID DCS Working in progress SMI Device Unit Advanced Status HVPS1 HMPID DCS PLC S300 Hardware Device HV LV LCS COOL GAS Phis. Par Cooling System Gas System HVMod 1 LVSctr 1 LCSMod 1 HVPS1 LVPS1 LCSMain LVPS1 CAEN SY1527 WIENER PL500F8 PLC S300 PLC S300 G. De Cataldo, CERN CH-INFN Ba, A. FrancoINFN Bari

  6. THE HMPID DCS DEVICE LOCATION HMPID PLC T,P HV, SY2527 We are here Bld 581 HMPIDDCS workstation G. De Cataldo, CERN CH-INFN Ba, A. FrancoINFN Bari