Chapter 6 NEMA Products Training Session

Chapter 6 NEMA Products Training Session. SMF Fractional HP Manual Motor Starter Page 6/3 to 6/4. Class SMF Fractional HP Starters are provided with Melting Alloy Overloads, and the used on AC single-phase motors up to 1 HP.

kyra-franco
Télécharger la présentation

Chapter 6 NEMA Products Training Session

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Chapter 6 NEMA Products Training Session

  2. SMF Fractional HP Manual Motor Starter Page 6/3 to 6/4

  3. Class SMF Fractional HP Starters are provided with Melting Alloy Overloads, and the used on AC single-phase motors up to 1 HP. Manual Starters are used when the motor is in sight of the controller (Guideline @ 50ft.) Applications: Fans, conveyors, pumps and small machine tools. SMF Fractional Motor Starters

  4. Product Class SMF: Open Type NEMA Type 1B General Purpose Flush Mounting (No Enclosure Provided) NEMA Type 1 General Purpose Enclosure, Surface Mounting. NEMA Type 3R, 4, & 12 Fractional Horsepower Manual Starters

  5. SMF Fractional Horsepower Manual Motor Starters

  6. MMS & MRS Fractional HP Switches Page 6/5 to 6/6

  7. Class MMS & MRS Fractional HP Switches provide ON-OFF control where overload protection is not required. These switches are rated for use on 3-phase motors up to 10 HP @ 460V. Manual Switches are used when the motor is in sight of the controller (Guideline @ 50ft.) Applications: Fans, conveyors, pumps and small machine tools. MMS & MRS Manual Switches

  8. Product Class MMS & MRS: Open Type NEMA Type 1B General Purpose Flush Mounting (No Enclosure Provided) NEMA Type 1 General Purpose Enclosure, Surface Mounting. NEMA Type 3R, 4, & 12 Fractional Manual Switches

  9. MMS & MRS Fractional Horsepower Switches

  10. Class 11 Manual Motor Starter

  11. Product Class 11 Family: Open Type 3RV NEMA Type 1 NEMA Type 7 & 9 Class I Flammable gasses may ignite Group C & D list of chemicals Class II Combustible dust Group E, F & G list of metals, carbons, grain NEMA Type 3 & 4, NEMA Type 7 & 9 Manual Starters & Switches

  12. Manual Starters & Switches

  13. Manual Starters & Switches

  14. Manual Starters & Switches

  15. Across the line provide local control only. 1Ø, 2Ø or 3Ø up to 15HP @ 460 V Ambient compensation Bimetal prevents nuisance tripping Built-in Phase loss trip, protects Motors Can be used for Type E application (self-protected Combo Starter). Saves Money! Manual Starters & Switches

  16. LVP low voltage protection optional. Reduces Potential injuries. Meets OSHA ON/OFF handle lock out with visible trip indicator. Prevents unauthorized entry Short Circuit trip at 13 times FLA for rated current. Test trip function. UL listed CSA Certified, and CE Manual Starters & Switches

  17. Product Nomenclature 11AD3B Class Enclosure Type Model 3RV Power Poles Size FLA 1,2,..

  18. Applications include: Grinders Power Saws Conveyors Fans Pumps Blowers Machinery Manual Starters & Switches

  19. Field Modifications LVP mounted on the right Shunt trip mounted on the right Front Plug-in or side mounted Auxiliary Contacts Pilot lights for NEMA 1 only Red, Green or Amber, 24-600V Manual Starters & Switches

  20. Manual Starters & Switches Q & A

  21. Manual Starter

  22. Open Contactors & Starters

  23. What is the Difference: Between A Short Circuit & An Overload ? Overload Relays

  24. What Is A Short Circuit? An Extreme Amount Of Current Usually Caused By A Fault To Another Phase Or To Ground. Fault Currents Can Exceed Several Thousand Amps For A Very Short Period Of Time Which Can Cause Very Extensive Equipment Damage. Fault Currents May Even Reach Up To 200,000 Amps On Some Systems. Overload Relays

  25. What Is An Overload? 1. An Operating Condition Where The Load Current Exceeds Normal Operation. 2. A Motor That Is Overloaded May Draw 6 Times Its Normal Operating Current (Full Load Current). 3. An Overload For Even Several Minutes May Cause Severe Motor Damage. Overload Relays

  26. What Are The Differences Between … A Fuse Or A Circuit Breaker And An Overload Relay? Overload Relays

  27. Short Circuit Protection Devices Fuses - One Time Use Only Magnetic Circuit Breakers - Reusable After Reset Overload Protection Devices Time Delay Fuses -One Time Use Only Overload Relays- Able To Reset ThermalMagnetic Circuit Breakers- Also Able To Reset Overload Relays

  28. How Overload Relays Work Monitors Over-current Condition On Motor Power Leads Indirectly Thermal Type Overload Relay Directly Magnetic or Electronic Type Overload Relay Turns Off Control Circuit During Overload Condition OL Relay NO Contact Turns Off Motor Starter Coil Circuit Overload Relays

  29. Overload Relays

  30. Bimetal Overload

  31. Bimetal Temp Comp. OLR

  32. Electronic OLR

  33. Electronic OLR

  34. OLR Class 10, 20, 30

  35. Motor Starter Circuit

  36. Non-Combination and Combination Starters

  37. Enclosed NEMA StartersProduct Lines • Non-Combination Starters • Class 14 (full voltage non-reversing) • Class 22 (full voltage reversing) • Class 30 (full voltage two-speed) • Combination Starters • Class 17 (full voltage non-reversing with disconnect) • Class 18 (full voltage non-reversing with circuit breaker) • Class 25 (full voltage reversing with disconnect) • Class 26 (full voltage reversing with circuit breaker) • Class 32 (full voltage two-speed with either DISC or CB) • Contactors • Class 40 (full voltage non-reversing) • Class 43 (full voltage reversing)

  38. Class 14 Non-Combination Starters on Pages 10 – 14.

  39. Enclosed NEMA StartersNon-Combination Starter Products Class 14 Non-Combination Starter

  40. Heavy Duty Industrial Construction Enclosure Types: NEMA 1 Lift-Off Type “Clamshell” (Manufactured with TOX process) NEMA 1, 4x, 7&9, 12 (field convertible to 3/3R) Hinged Standard Width and Extra Wide Enclosures Removable Door/Cover Siemens offers ten NEMA Size Starters from Size 00 up to Size 8 rated 900HP 600V. Siemens also offers three Heavy Duty Half-Size Starters in 1 ¾, 2 ½ & 3 ½ for Cost and Space Savings. Overloads - ESP100 and Bimetal Ambient Compensated Pilot Device Mounting Holes in enclosures Enclosed NEMA StartersNon-Combination Starter - Features and Benefits

  41. Factory & Field Modifications Pages 6/71 to 6/87. Control Power Transformer (CPT) Pilot Devices Control Relays Control Fuses Auxiliary Contacts Meters (Hinged Enclosures Only) Terminal Blocks Etc… Enclosed NEMA StartersNon-Combination Starter - Features and Benefits

  42. Enclosed NEMA Starters Non-Combination Starter Nomenclature 1 4 B S A 3 2 B A X X Class Size Model Current Range (ESP only) Power Pole / Enclosure Size Enclosure Type Coil Suffix

  43. Enclosed NEMA StartersNEC Requirement for Combination Starter NEC 430 requires that Motors have: Disconnect Short Circuit Protective Device Controller Overload Protection

  44. Class 17 & 18 Combination Starters on Pages 15 – 24.

  45. Enclosed NEMA Starters Combination Starter Products Class 17 Combination Starter

  46. Enclosed NEMA Starters Combination Starter Products Class 17 Combination Starter Class 18 Combination Starter

  47. Enclosed NEMA Starters Combination Starter Products Class 25 Combination Starter Class 26 Combination Starter

  48. Enclosed NEMA Starters Combination Starter Products Class 32 Combination Starter

  49. Enclosed NEMA Starters Combination Starter Products Fiberglass enclosure Explosion proof enclosure Combination Starters

  50. Heavy Duty Industrial Construction Manufactured with TOX process on Most Enclosures Standard Width and Extra Wide Enclosures Four Enclosure Types: NEMA 1, 4x, 7&9, 12 (field convertible to 3/3R and 4) Removable Door Disconnect Types are Field Convertible to Fusible Disconnects 100KA Amp Fault Protection with Class R Fuses to 600V or MCP (Mag Only) to 480V Panel Pre-Drilled for 230V or 600V Fuses Enclosed NEMA StartersCombination Starter - Features and Benefits