Technical Session “Lightning Protection” Highlights & Conclusions. Ahmed Zeddam France Telecom. Technical Session “Lightning Protection” Agenda. Risk assessment for structure R. Pomponi, Telecom Italia Risk assessment for services A. Zeddam, France Telecom Risk regarding safety

palti
Télécharger la présentation

Technical Session “Lightning Protection” Highlights & Conclusions

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Technical Session“Lightning Protection”Highlights & Conclusions Ahmed Zeddam France Telecom

  2. Technical Session“Lightning Protection”Agenda • Risk assessment for structure • R. Pomponi, Telecom Italia • Risk assessment for services A. Zeddam, France Telecom • Risk regarding safety P. Day, Telstra • Experimental result C. Fonseca Barbosa, CPqD

  3. Highlights from Presentation 1“Risk assessment for structures” • IEC 62305-2 standard gives an exhaustive risk assessment for structures, its contents and connected services • This standard should be used for protection need evaluation of the exchange or customer’s buildings and remote site • Critical points: • Risk evaluation for loss of service • Protection factor PM due to flashes near the structure • Necessary clarification and/or improvement: • Protection factor values PZ due flashes near the service are missed for 1 kV equipment resistibility • PSPD values for SPDs installed on shielded cables • Induction loop between two equipment inside the structure is missed

  4. Highlights from Presentation 1“Risk assessment for structures” • IEC 62305-2 standard gives a risk assessment for services following the same approach for structures • This standard should be used for protection need evaluation along the service and structures where the service is entering (customer’s buildings, centres and remote site….) • Critical points: • Some parameters needed for the risk assessment are till now contained in IEC 62305-5 • For the time being, application only to the Telecom line protection (IEC 62305-5) • Necessary clarification and/or improvement: • Shielding factor for internal & external wiring • Protection factor values P'Z due flashes near the service are missed for 1 kV equipment resistibility • PSPD values for SPDs installed on shielded cables • Global approach : service + structure

  5. Highlights from Presentation 3“Risk regarding safety” • Draft IEC 62305-2 is a good basis for the preparation of K.risk and determining the risk associated with a telecommunications service • Further work needs to be performed to accurately calculate the risk associated with the introduction of the remote telecommunications earth • The factor Lc used to determine the collection area needs rationale and validation. It is critical to an accurate calculation • The linkage between PX and LX needs to be established and appropriate loss values determined for domestic telecommunications equipment

  6. Highlights from Presentation 4“Experimental results” • Shielding factors and protective effect of SPD applied to telecommunication lines can be assessed from simply equations derived from travelling wave theory. • The wave form of current induced into a short circuited loop by lightning is identical to the inducing current. • The time derivative of the surge current that flows through a service of an installation struck by lightning is only a few percent of the lightning current’s di/dt. • The experimental site with rocket triggered lightning of Cachoeira Paulista - Brazil is a relevant source of information in order to revise the existing standards on lightning protection and to develop new ones.

  7. Conclusion • IEC /TC 81 has recently produced new series of standards on Lightning Protection regarding the structures and services • These standards can be used by ITU-T SG 5 for the amendment or development of Recommendations • Some clarification and/or improvement are sill necessary , particularly for IEC 62305-2 standard • SG5 has relevant source of information based on experimental results in order to revise the existing standards on lightning protection • SG5 will continue its liaison with IEC TC 81 in order to improve the knowledge on lightning protection and develop new standards