0 likes | 0 Vues
Discover the PFMF370u2011400 3u2011Line 400u202fA EMI Filter at Premier Filters. Engineered for heavy-duty industrial applications, this high-capacity filter delivers exceptional electromagnetic interference suppression, ensuring reliable performance of sensitive equipment. With a robust 400u202fA current rating, it offers powerful noise reduction and compliance with stringent regulatory standards. Enhance your systemu2019s efficiency and stabilityu2014trust Premier Filters' advanced EMI filtration solutions to safeguard your operations.<br>
E N D
LIFT BRACKETS, 2x C E B 330(13) PFMF370-400-3 3-LINE + GND SCIF/TEMPEST FILTER D EMI SPECIFICATIONS A GASKETED OUTPUT COMPARTMENT PFMF370-400 MAX VOLTAGE: 0-277/0-480VAC MAX CURRENT: 400A/LINE D FREQUENCY: 50/60HZ OPERATING TEMP.: -40 TO 65C HIPOT (L-G): 2200VDC (PRIOR TO INSTALLING DISCHARGE RESISTORS) DISCHARGE VOLT. (@277V): <30V IN 30S MTG HOLE 0.4"(10.2), 6x VOLT. DROP: <2% MAX AT FULL RATED UNITY LOAD OVERLOAD: 140% RATED CURRENT FOR 15 MINUTES 305(12") PERFORMANCE: 100dB (14KHZ TO 40GHZ) MANUFACTURED IN ACCORDANCE WITH THE FOLLOWING STANDARDS: MTG LEGS, 2x (REMOVABLE) 203(8") MIL-STD-220 MIL-F-15733 MIL-STD-810 CONFORMS TO UL STD 1283 GROUND STUD LV DIRECTIVE NOTES: 1. 2. 5025116 CONDUIT CUTOUTS BY END USER. FILTER IS BIDIRECTIONAL. IF INSTALLING FILTER INTERNAL TO SCIF RUN POWER INPUT WIRING INTO FILTER EMI GASKETED OUTPUT COMPARTMENT. MODEL AMPS TERMINAL DIMENSIONS - MM (IN) WEIGHT LBS(KG) A B C D E PFMF370-400-3 400 2xM16 1422 750 406 660 800 550 (250) (56) (29.5) (16) (26) (31.5) SPECIFICATIONS SUBJECT TO CHANGE