1 / 16

ASHRAE Standard 206-2013

ASHRAE Standard 206-2013. Method of Testing for Rating of Multi-Purpose Heat Pumps for Residential Space Conditioning and Water Heating Wayne Reedy Oak Ridge National Laboratory. Background.

shelby
Télécharger la présentation

ASHRAE Standard 206-2013

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ASHRAE Standard 206-2013 Method of Testing for Rating of Multi-Purpose Heat Pumps for Residential Space Conditioning and Water Heating Wayne Reedy Oak Ridge National Laboratory

  2. Background • Development of standard was supported by ORNL as part of the U.S. Department of Energy’s effort to facilitate market penetration of multifunction heat pumps. • In order to achieve an instantly recognizable, authoritative document, a test standard was requested of ASHRAE, which in turn established a Standard Project Committee to develop Standard 206

  3. SPC 206 Included Representation From All Industry Segments • Committee was made up of 15 voting members, representing manufactures, testing laboratories, electric utilities, and a university; AHRI was a non-voting member.

  4. SCOPE Standard 206 applies to electrically powered unitary heat pump equipment that provides both space conditioning and water heating functions, and may include other functions, such as dehumidification and/or ventilation.

  5. SCOPE • Standard 206 addresses air-source, water-source, ground water-source, ground-source closed loop, and direct geoexchange equipment. • It applies to air-source equipment rated below 19,000 W (65,000 Btu/h), and water-source, ground water-source, ground-source closed loop, and direct geoexchange equipment rated below 40,000 W (135,000 Btu/h).

  6. SCOPE • Standard 206 addresses single-capacity, dual-capacity, and variable-capacity equipment • Provides for up to 7 modes of equipment operation • Space conditioning only • Dedicated water heating • Dehumidification+space conditioning • Dehumidification • Space conditioning+water heating • Dehumidification+space conditioning+water heating • Dehumidification+water heating

  7. SCOPE • Space conditioning may be heating or cooling • Dehumidification may be during summer or winter • Dedicated water heating may be during summer or winter, with the heat source being either indoor or outdoor

  8. SCOPE • Test procedure covers packaged, split, mini-split, and triple split equipment configurations • Refrigerant-to-water HX may be internal or external to a heat pump section or water storage tank • Specifies refrigerant and water line lengths/configuration for all options

  9. Standard 206 is an extension of and consistent with: • ANSI/ASHRAE Standard 37 • Methods of Testing for Rating Electrically Driven Unitary Air- Conditioning and Heat Pump Equipment (Steady-State Performance) • ANSI/ASHRAE Standard 116 • Methods of Testing for Rating Seasonal Efficiency of Unitary Air Conditioners and Heat Pumps

  10. Standard 206 is also consistent with: • AHRI Standard 210/240 • Standard for Unitary Air-Conditioning and Air-Source Heat Pump Equipment • ANSI/AHRI/ASHRAE ISO Standard 13256-1 • Water-source heat pumps - testing and rating for performance - • Part 1: Water-to-air and brine-to-air heat pumps • AHRI Standard 870 • Standard for Performance Rating of Direct GeoExchange Heat Pumps • ANSI/ASHRAE Standard 118.2 • Method of Testing for Rating Residential Water Heaters

  11. Standard 206 should replace: ANSI/ASHRAE Standard 137 Methods of Testing for Efficiency of Space-Conditioning/Water- Heating Appliances that Include a Desuperheater Water Heater and various waivers from DOE’s Central Air Conditioner and Central Air Conditioning Heat Pump Test Procedure

  12. Calculation procedure is a bin process based on: • Water heating load • Space latent load • Space sensible load

  13. Performance Descriptors • Three performance descriptors are used to completely describe the performance of the combined appliance: • Combined appliance space conditioning performance for the cooling season; • Combined appliance space conditioning performance for the heating season; • Combined appliance water heating performance on an annual basis. • In all cases, the descriptor ends in a subscript “ca” to designate “combined appliance”.

  14. Performance Descriptors • Air-source equipment • SEERca • HSPFca • EFwca • Water-source equipment • EERca • COPca • EFwca

  15. STATUS: • Approved as an ASHRAE standard 6/26/2013 • Available from ASHRAE in paper or electronic form • Includes an excel spreadsheet to perform calculations

  16. QuestionsComments