RÉUNION UPDEA

RÉUNION UPDEA. Abidjan 3 - 4 Juin 2010.

tavi
Télécharger la présentation

RÉUNION UPDEA

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. RÉUNION UPDEA Abidjan 3 - 4 Juin 2010

  2. DÉFINITION DE LA MAINTENANCELa maintenance est l’ensemble de toutes les actions techniques, administratives et de management durant le cycle de vie d’un bien destinées à le maintenir ou à le rétablir dans un état dans lequel il peut accomplir la fonction requise.NF EN13306X60-319de juin 2001

  3. STRATÉGIE DE MAINTENANCE ADOPTÉE PAR LA STEG

  4. POLITIQUEDE LA MAINTENANCE DES TRANSFORMATEURS

  5. PÉRIODICITÉ D’ENTRETIEN DES TRANSFORMATEURS L’entretien des transformateurs et auto transformateurs toutes marques confondues est effectué une fois par an. Certains transformateurs et auto transformateurs vétustes peuvent nécessiter un entretien plus fréquent, la décision revient aux exploitants pour décroître la périodicité retenue. L’analyse d’huile des transformateurs et auto transformateurs sera réalisée tous les 3 ans par le DPTG. Pour les transfos neufs, une analyse complète est effectué avant la fin de la première année pour la réception définitive. La périodicité d’entretien des régleurs en charge, est définie comme suit: Les régleurs de marque MR type (M, MS, D), ACEC type RR et CGE type CLR 100 ,ont comme périodicité: Chaque 6 ans ou 70000 manoeuvres Le régleur de marque MR type H aura comme périodicité: chaque 6 ans ou 50000 manœuvres

  6. Date: …../…../……... DPTE / DGMTE Fiche d’entretien TR, ATR et BPN Code BDM: Marque TR/ATR:…….…….. OT :……………… Marque BPN :…………………… Observations:……………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………….… Chargé de Travaux Chef de l’unité

  7. Date: …../…../……... DPTE / DGMTE Fiche d’inspection régleur Observations:……………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………….. Chargé de Travaux Chef de l’unité

  8. PÉRIODICITÉ D’ENTRETIEN DES DISJONCTEURS

  9. Date: …../…../……... DPTE / DGMTE Fiche d’entretien disjoncteur à SF6 à commande Mécanique Code BDM: Marque/Type Disj: …….…….… OT :……………………………… (*)Cette opération sera effectuée tous les 5 ans Observations:………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………….. Chargé de Travaux Chef de l’unité

  10. Date: …../…../……... DPTE / DGMTE Fiche d’entretien disjoncteur à SF6 à commande hydraulique Code BDM: Marque/Type Disj: …….…….… OT :……………………………… (*)Cette opération sera effectuée tous les 5 ans Observations:………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………….. Chargé de Travaux Chef de l’unité

  11. Date: …../…../……... DPTE / DGMTE Fiche d’entretien disjoncteur à SF6 à commande hydraulique Code BDM: Marque/Type Disj: …….…….… OT :……………………………… (*)Cette opération sera effectuée tous les 5 ans Observations:………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………….. Chargé de Travaux Chef de l’unité

  12. POLITIQUE DE LA MAINTENANCE DES LIGNES AERIENNES La visite au sol est réalisée au moins une fois par an pour les lignes qui traversent des zones d’agglomération ou zones polluées. Pour le reste des lignes les visites sont programmées tous les deux ans. La visite montée sous tension est programmée tous les cinq ans pour les lignes qui ont plus que dix ans ou sur un tronçon de ligne qui a subi des déclenchements fugitifs. Le lavage sous tension et hors tension est programmé sur des tronçons de lignes choisis suite aux rapports de visites qui décèlent le degré de pollution des lignes. Visite suite incident est déclenchée en cas d’ un défaut persistant sur la ligne ou un défaut fugitif et qui se répète sur le même pylône

  13. Date: …../…../……... DPTE / DGMTE RAPPORT DE VISITE Code BDM ligne Type Visite OT : …… Observations:……………………………………………………………………………………………………………………………………………………………………………………………………………………………………………….. Chargé de Travaux Chef de l’unité

  14. PYLONE N° 11 RD-GR1&2

  15. LES INDICATEURS

  16. MAINTENANCE DES POSTES GIS • Visite visuelle du poste blindé une fois par mois • Entretien périodique des commandes des disjoncteurs selon le type de commande et l’exigence du constructeur. • Entretien systématique de tous les compartiments du poste blindé tous les cinq ans

  17. MERCI POUR VOTRE ATTENTION