Passive Schools Air Temperature. Passive Schools provide excellent comfort levels with low running costs and less equipment to be maintained or replaced. The extra build costs are easily offset by the smaller heating system.

teagan
Télécharger la présentation

Passive Schools Air Temperature

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Passive SchoolsAir Temperature • Passive Schools provide excellent comfort levels with low running costs and less equipment to be maintained or replaced. The extra build costs are easily offset by the smaller heating system. • A Passive School maintains a stable year round temperature using extra insulation, higher air tightness levels, HRV and better windows, so the temperature rarely falls below 17 degrees. • The classroom is heated by the pupils who produce 2kw (25 kids x 80w = 2kw) plus 2kw Solar Gain plus 1kw from a radiator used for 1 hour in the morning before the kids arrive. This radiator will use less than €100 worth of energy per year, so when the heating system doesn’t work for 2 weeks in winter nobody notices. The classroom in a Passive School loses 1 degree overnight and heating costs are reduced to 10%. www.viking-house.ie

  2. Riedberg school, Frankfurtbasic facts • Opened in 2004 • Area 8,000 m² (6,300 m² + gym) • Occupants 650 – 675 • Construction type Concrete externally • insulated • Ventilation HRV • Heating Wood pellet boiler • Air tightness n50=0.46/h • Extras 30 kW photovoltaics www.viking-house.ie

  3. Riedberg school, Frankfurtenergetic performance • Calculated heat demand 15 kWh/(m²a) • U-value walls 0,17 W/(m²K) • U-value window frames 0,8 W/(m²K) • U-value glazing 0,6 W/(m²K) • U-value roof 0,11 W/(m²K) • U-value ground slab 0,21 W/(m²K) • Temperatures during the winterbetween 19.5 and 20.6 °C • Almost no overheating during the summerAverage in 2006 (warm summer) was 22.9 °C • CO2 concentration is constantly below the recommended threshold of 1,500 ppm • Heat consumption during the winter of 2005/2006 was 90 % below German standard www.viking-house.ie

  4. Overheating ControlDraught free building • Summer overheating is easily controlled by cooling the Thermal Mass using automatic actuator controlled vents at night and closing blinds within the windows by day. If the classroom gets too hot, just open a window~even in winter! • The heat generating kitchen is kept to the North side of the building. • Earth heat exchangers deliver 15-16 degree air when its 25 degrees outside and 7 degree air when its minus 10 degrees outside. This simple technology cuts the size of your heating or cooling system in half. • Cold surfaces and leaky buildings cause draughts. The 17 degree surface temperature of Passive School windows stops convection and the high level of air tightness ensures the building is draught free, so the child near the windows isn’t cold. www.viking-house.ie

  5. Riedberg school, Frankfurtcosts • Total 16.7 mio € • Additional costs ~ 3 % • Construction costs 1,110 €/m² • Est. payback period in 2003 30 years • Est. payback period in 2005 12 years • With oil prices hitting 130 $ / barrel payback period is even shorter today • After payback period energy savings of several thousand euros per year www.viking-house.ie

  6. Cold Bridge free ConstructionWarmer Walls • Cold Bridging is eliminated at design and construction stages, delivering walls without cold spots. • With a 15 degree wall, the thermostat is set to 25 degrees for comfort, with a 19 degree wall, the stat is lowered to 20 degrees. • Warmer surfaces reduce condensation eliminating fungus/mould growth. www.viking-house.ie

  7. Heinrich v. Kleist school, Frankfurtbasic facts • Opened in 2007 • Area 1,338 m² • Construction type extension, concrete • Ventilation Wolf KG 160 Gigant • Heating shares heating with existing building • Air tightness n50=0.24/h • Extras green roof insulation is CFC-free www.viking-house.ie

  8. LightingBiomass-PV • Lighting is the single biggest energy guzzler in British Schools and its excessive use can be easily reduced by adopting Passive School principles. Lights in UK schools often default to on because the controls are too complicated. Passive Schools usually have 3-3.5m high ceilings and windows are high in the walls to deliver natural light across the whole classroom. Up lighters that light the ceiling are a no-no, all lights should automatically switch off at break time and be manually switched back on. Night time security lights are operated by motion sensors that only work after dark. • Biomass boilers can be a maintenance nightmare if you pick the wrong model and PV often doesn’t do what it says on the tin, but they both need replacing every 15 years. • If the only difference between a Code 4 and a Code 6 school is the size of the PV array? then It makes more economical sense to build a Passive-Code 4 school and buy in Green Zero Carbon electricity. www.viking-house.ie

  9. Heinrich v. Kleist school, Frankfurtenergetic performance / costs • Calculated heat demand 14 kWh/(m²a) = 1.4 liters of oil per square meter per year • U-value walls 0.126 W/(m²K), Rockwool • U-value window frames 0.81 W/(m²K) • U-value glazing 0.6 W/(m²K) • U-value roof 0.095 W/(m²K) EPS insulation • U-value ground slab 0.144 W/(m²K) EPS and foam glass • Total costs: 2,692 €/m² • Construction costs: 2,053 €/m² www.viking-house.ie

  10. HumidityAir Quality • Humidity is controlled using HRV during the heating season and natural ventilation for the rest of the year. The ventilation rate for a Passive School is based on the occupancy levels, not on the volume of the building as per the UK building regs. • The Passive Schools with the lowest Co2 levels use HRV, and the performance of the pupils is 20% above average, so they can spend 2-3 years less in school (joke). • Without HRV the ventilated energy losses are massive and air quality is low, 500 pupils require 20m3/hr = 10,000m3/hr + 10% ~ 11,000m3/hr regardless of how voluminous the building is. • HRV for a 300 pupil school costs €150,000 which is cheap when you consider the benefits achieved from higher air quality and energy efficiency. • Children need more air than adults and are more sensitive to low air quality. • The Co2 level was below 1000ppm for 99.9% of the time in the 1st Belgian Passive School. Low air resistance ductwork is beneficial to avoid draughts. www.viking-house.ie

  11. Preungesheim primary school, Frankfurtenergy performance • Calculated heat demand 15 kWh/(m²a) = 1.5 liters of oil per square meter per year • U-value walls 0.13 W/(m²K) • U-value window frames 0.8 W/(m²K) • U-value glazing 0.6 W/(m²K) • U-value roof 0.092 W/(m²K), • U-values floor/ground slab 0.133 – 0.164 W/(m²K) • Total costs 21,85 mio € • Construction costs 1.41 mio € / 1,538 €/m² • Calc. payback period (2008) 9.3 years • Construction time 05/2006 – 08/2007 • Area 5,152 m² • Occupants 530 www.viking-house.ie

  12. ConsultancyQuality Control We can guide clients through the Passive Schools labyrinth by offering the following services: • Get involved in your project at the design stage to optimise building orientation and shape to reduce its energy demand • Cost benefit analysis calculating the payback period for any extra costs incurred building your Passive School • (PHPP) Passive House Planning Package calculations • Cold Bridge (CB) calculation and elimination using Therm • Condensation risk analysis and drying ability of your wall build up using WUFI • Supply and fit of our CB free PassivHaus certified foundation system delivering U-values as low as 0.08 • Guaranteed Airtightness result of n50=0.60/h from our Airtightness SWAT team • Passive House certification on completion www.viking-house.ie