This thesis presentation by Graham Finch from the University of Waterloo delves into the performance monitoring of rainscreen wall assemblies in Vancouver, BC. It highlights essential research on exterior gypsum, monitoring techniques, and hygrothermal modeling. Key findings include moisture content correlations, seasonal performance evaluations, and recommendations for design improvements to enhance wall performance. Additionally, it discusses the implications of moisture on structural integrity and the challenges of accurate modeling in ventilated wall systems.
01 / 58Rainscreen Performance Monitoring: Insights and Advances from Current Research
1 / 17
Télécharger la présentation
Rainscreen Performance Monitoring: Insights and Advances from Current Research
Une image / un lien ci-dessous est fourni (tel quel) pour télécharger la présentation
Politique de téléchargement : le contenu du site vous est fourni TEL QUEL pour votre information et votre usage personnel ; il ne peut être vendu, concédé sous licence ni partagé sur d’autres sites sans l’accord de son auteur.Le contenu vous est fourni TEL QUEL, pour votre information et votre usage personnel uniquement.Téléchargez la présentation en cliquant sur ce lien.Lors du téléchargement, si vous ne parvenez pas à télécharger une présentation, l’éditeur a peut-être supprimé le fichier de son serveur.Pendant le téléchargement, si vous ne parvenez pas à obtenir une présentation, le fichier a peut-être été supprimé par l’éditeur.
Introduction • Background • Current Research Highlights • Exterior Gypsum • Hygrothermal Modeling • Building 3 – A Case Study • Monitoring Program Improvements • Still to Come May 2006 - BCBEC Symposium
Background • Building Monitoring Program • RDH Building Engineering (RDH) • Canadian Mortgage and Housing Corporation (CMHC) • Homeowner Protection Office • British Columbia Housing Management Commission • Designed and installed on five buildings in Vancouver, BC being constructed or rehabilitated using a rainscreen wall assembly. • Data collected includes temperature, relative humidity, moisture content, wetness, pressure, wind, rain, and driving rain. May 2006 - BCBEC Symposium
Background • University of Waterloo MASc Student • Rainscreen Performance Monitoring Study part of Graduate Thesis work • Build on initial RDH work • Further work as part of thesis • Further data analysis • Trends, Normals, Abnormalities • Wetting and Drying Rates • Hygrothermal Modeling • Validation • Material Testing May 2006 - BCBEC Symposium
Presentation Outline – Research Highlights • Measuring moisture content of exterior gypsum using electrical resistance • Hygrothermal modeling of ventilated rainscreen walls • Seasonal performance of Building 1 • Improving performance by design • Building 3: A case study • Field validation of monitored results May 2006 - BCBEC Symposium
Exterior Gypsum Sheathing Properties • Purpose • Measure performance of exterior fiberglass faced gypsum exposed to humid conditions • Correlate electrical resistance of gypsum with gravimetric moisture content • Well established correlation for wood • More difficult with gypsum • Provide approximate sheathing moisture contents for Buildings 3 and 5 to assess performance May 2006 - BCBEC Symposium
Exterior Gypsum Sheathing Properties • Physical Properties • Strength loss with elevated moisture content • As a result of high relative humidity or liquid water exposure • Levelton study results (Later today) • Other Issues • Mould Growth • Corrosion when in contact with metals ie. Steel studs May 2006 - BCBEC Symposium
Why does it matter? • Significant strength loss with as little as 1 - 2% moisture content • Saturated = Destroyed Exposed to 100% RH for 1 year May 2006 - BCBEC Symposium
Mould Growth • Possible under humid conditions and prolonged periods of time 4 months 4 years May 2006 - BCBEC Symposium
How Long does it take? • Gypsum boards relatively permeable to water vapour • 1000-2000 metric perms • Fast response to moisture • Wetting - 2% moisture content increase (from dry) in 2 days exposed to 100% RH • Even faster drying rates • Likely prevent very high MC levels from being achieved in the field May 2006 - BCBEC Symposium
Moisture Content and Electrical Resistance • Used to correlate measured electrical resistance (ohms) with an approximate gravimetric moisture content for field monitoring studies • Determine “how wet” the gypsum is without destructive testing • Handheld moisture meters give only relative idea of moisture content • Different meters, different scales May 2006 - BCBEC Symposium
Hygrothermal Modeling • Purpose: To correlate field results with those predicted by hygrothermal simulation • Can we accurately model walls with ventilated claddings? ie Rainscreen Walls • Can you accurately model a 2D problem with 1D software? • Ventilation cannot be neglected • Current software has limitations May 2006 - BCBEC Symposium
Modeling Requirements • Modeling ventilated wall assemblies with 1D software • Cladding input into model with an “effective permeance” which accounts for an assumed ventilated rate through cladding vent openings • Literature available for equivalent permeance values typically in range of 1000 + perms depending on flow rate May 2006 - BCBEC Symposium
Modeling Requirements • Modeling correlation with field results • Effective permeance method works on average however: • Ventilation is a dynamic variable - Wind and temperature differences drive pressures which change on a daily basis • Better correlation achieved by using actual temperature/relative humidity values from ventilated cavity/drainage space May 2006 - BCBEC Symposium
Discussion of Results • Stucco, Vinyl, and Cement board clad buildings all had similar annual trends and similar moisture levels of the sheathing • High RH (80-100%) and cool temperatures in the ventilated cavity space result in sheathing moisture contents between 20-25% during winter months May 2006 - BCBEC Symposium
Discussion of Results • Correlation of hygrothermal simulation with field data is good • Material properties are important to correlation • Moisture Isotherm for plywood/OSB have direct impact on results May 2006 - BCBEC Symposium
Uses for Hygrothermal Modeling • How can we improve the performance of ventilated rainscreen walls? • Insulated Sheathing • Is a polyethylene vapour barrier required? Would painted drywall work instead? • What is the impact of the indoor relative humidity and temperature? May 2006 - BCBEC Symposium
Can Insulated Sheathing Improve Performance? • Base case R-19 (2x6 wall) • Compare to R-12 (2x4 wall) • R-19 stud insulation plus vapour permeable R-8 insulation on exterior (no poly) • R-12 stud insulation plus vapour permeable R-8 insulation on exterior (no poly) • Vapour permeable R-12 on exterior only (no stud space insulation, no poly) May 2006 - BCBEC Symposium
Other Simulated Cases • OSB vs. Plywood, negligible difference in RH or MC results • Using standard OSB and Plywood properties from WUFI 3.3 database May 2006 - BCBEC Symposium
Results • Insulated sheathing improves the performance of ventilated rainscreen walls • A paint vapour retarder can be used as a replacement for poly, however exterior insulation and designed ventilation are both required May 2006 - BCBEC Symposium
Problems • High relative humidity within stud space 80-100% during winter months (All 8 monitored locations) • Corresponding high moisture content of fiberglass faced exterior gypsum • Interior suites – High relative humidity during winter (50-70%) May 2006 - BCBEC Symposium
Field Openings • Interior openings made in January 2006 • During seasonal period of elevated moisture levels within wall assembly • Confirm presence of moisture within stud cavity • Observe interstitial wall conditions after 4 years of service May 2006 - BCBEC Symposium
Suite Observations • Interior of all suites had high interior relative humidity • Condensation on window frame and glazing surfaces • Mould growth on interior drywall surfaces at corners May 2006 - BCBEC Symposium
Wall Opening Observations • Openings confirmed fiberglass faced exterior gypsum is getting wet • 80-100 relative moisture level (Delmhorst BD-10) • Calculated 1-2% moisture content (up to 6% in some locations) • Surface corrosion on steel studs • Sensors are returning valid data • Problematic details also contributing to moisture problems (thermal bridging) May 2006 - BCBEC Symposium