E N D
1. Rapidzone Operation: Network Data Sharing Discharge air temp information is broadcast to zone controllers via E-Bus
2. Zone Controller Operation: DAT Control
3. Setpoint Knob Operation Setpoint knob determines centre of deadband between heating and cooling
Example:
deadband is set for 6
knob set for 73
heat setpoint becomes 70
cool setpoint becomes 76
deadband exists between 70 - 76
4. Rapidzone Operation: Terminal Loads Terminal Load: zone deviation from setpoint
Terminal Load is broadcast from each zone to RTU via E-Bus
< 20 % zone is satisfied
> 20 % zone requires heating or cooling
Zones can be configured as priority, terminal load multiplied by 1.5
5. Terminal Load RTU will run in cooling mode until Zone 3 is satisfied (TL drops below 20%)
Zones 1 and 2 remain closed or in minimum position