1 / 58

Safety operating

Safety operating. Electrical facilities have to be constructed due to the standards and have to stay in a proper condition . By changing of the operation conditions (e.g. kind of branch, humidity, dry, fire hazardous or explosive), the existing assets have to adapt to the valid standards.

vine
Télécharger la présentation

Safety operating

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Safety operating Electrical facilities have to be constructed due to the standards and have to stay in a proper condition. By changing of the operation conditions (e.g. kind of branch, humidity, dry, fire hazardous or explosive), the existing assets have to adapt to the valid standards. By monitoring dangerous defects for individuals, animals or real values actions for defect clearing have to be taken without any delay. If it is not possibe to eliminate the danger at once it is initially to be limited (e.g. by cordon off or caution labels). The responsible person for the switchgear ist to be called immediatly. Faulty electrical equipment may not be used, exept the further use is obviously safe.

  2. 1. Before first starting up and after every change, repair or maintenance the asset is to be tested by an electrical technician. 2. Equipment/assets have to be re-tested in certain intervals. Emerging fault have to be diagnosed early enough in a certain time limit. The rule books must be respected by testing . By request a test log book with certain records is to be kept.

  3. Common intervals for fixed electrical equipment

  4. Common intervals for mobile electrical equipment

  5. Air-insulated double busbar switchgear 10 kV Division into six compartments Switchgear with extractable switches (connect- and disconnect position) Switch truck out of panel for maintenance When circuit breaker ist solid buildt in, busbar and cable disconnectors are required

  6. Details of a truck type switchgear Circuit breaker in test position Backout of circuit breaker on switch truck

  7. Designs of switchgears in distribution substations Air insulated switchgears AIS • Insulation by air, • arcing control by air ore, sometimes, by vacuum Gas insulated switchgears GIS • sealed pressure system • Insulation by SF6, • Arcing control by SF6 oder vacuum • No refilling ofSF6 during lifetime • overpressure: 2 – 5 kPa (0,2 – 0,5 bar) • Quantity: approx. 2 kg SF6 in a ring-main-unit

  8. Air insulated switchgear for distribution substations • type-tested switchgear (IEC 62271-200) • metal enclosed • Factory assembled (field-by-field) • Single compartment partition • assembly on baseframe • mind torques for assembly Dimensions for 10 kV: Width: 600 mm Length: 730 mm (CB-feeder: 900 mm) Height: 1900 mm Weight: 170 kg (CB-panel: 250 kg metering panel: 270 kg)

  9. Gas-insulated switchgear for distribution substations • Compact transformer substations, • e. g. forwind power stations • Garage and vault substations • Underground and underfloor substations • Sidewalk substations • Damp, sandy or dusty areas Almost maintenance-free Welded switchgear vessel without seals, made of stainless Be carefull for drillings! Normally not expandable Dimensions: Scheme 10 up to 24 kV Width: 980 mm Length: 665 mm Height: 1400 mm Weight: 298 kg

  10. Details Siemens 8 DJ 20 (1) 1

  11. Details Siemens 8 DJ 20HRC-Fuse compartment 4

  12. Details Siemens 8 DJ 20 (2) 2

  13. Details Siemens 8 DJ 20cable compartment

  14. Details Siemens 8 DJ 20 (3) 3

  15. Details Siemens 8 DJ 20Ready-for-service indicator Messdose magnet.Kopplung

  16. Details Siemens 8 DJ 20 (4) 4

  17. Details Siemens 8 DJ 20short -circuit indicator

  18. Details Siemens 8 DJ 20 (5) 5

  19. Details Siemens 8 DJ 20voltage indicator energized faulty De-energized 3 4

  20. Details Siemens 8 DJ 20 (6) 6

  21. Details Siemens 8 DJ 20operating mechanism 1 6 3 5 4 2

  22. Overview of a distribution substation 4100 Safety guard Medium voltage switchgear AIS 2800 Substationaccessories A A LV and metering room meter Earthing terminal Duct bolt for earthing intrusion freer ventilation grille 4 cable entrances, Door with intrusion free ventilation grille Hauff HD 150

  23. Overview of a distribution substation 2350 profile A - A

  24. Overview of a distribution substation Scheme: 2 ring main feeder–1 transformer feeder

  25. Overview of a distribution substation Operating control line Property line metering

  26. Overview of a distribution customer substation Operation control line Metering panel Circuit breaker panel Customer disconnects Power utlity connects Property line

  27. Designs of distribution substations Pole substation enclosured transformer towerstation

  28. Designs of distribution substations Accessible substation with air insulated swichtgear Dimensions: 2,80 m x 3, 50 m

  29. Designs of distribution substations MV switchgear air insulated Transformer with safety guard LV-switchgear Accessories

  30. Maintenance of distribution substations Pre-condition: Station is disconnected, earthed and free for working Wartung: Switchgears: - clean contacts and lubricate with approved grease by manufacturer - de-lubricate breaker mechanism carefully and re-lubricate - Function check, check operating mechanism - check HRC-fuses (dirction of mounting, proper dimension, - check release with test fuse - check cable box - check position indication Transformer - clean, - check oil level NSpg.: - clean (Live working !), - Beschriftung kontrollieren Building: - clean ventilation grilles, - check roof, - clean indoor, - check outdoor, locks, - check signage - check earth resistance,

  31. Maintenance policies n n n j j j criterion: importance Action required? criterion: Diagnosis CorrectiveMaintenanceCM ConditionBased MaintenanceCBM Time Based MaintenanceTBM ReliabilityBased MaintenanceRBM

  32. Time Based Maintenance • maintenance in constant periods • exchange of assets after constant up-time • high availability • no use up to maximum expected life Most cost-intensive maintenance

  33. Corrective Maintenance • Repair or replacement after failure • asset availability depends on equipment availability • no influence on time between failures Most competitivemaintenance

  34. Condition Based Maintenance • Maintenance or repair depends on technical condition All identicalassetsaretreatedthe same way

  35. Reliability Based Maintenance • Maintenance or repair depends on technical condition • significance of asset importance for network Best maintenancepolicy

  36. Evaluation Process For a Significance Based Maintenance MV Switchgear LV Switchgear Transformer Building Terminal Box S Time SinceLast Visual Control Condition Of Substation

  37. Evaluation Process For a Significance Based Maintenance: Condition Transformer Criterion 1 e.g. Condition of Tank Total Evaluation Of Component e.g. Transformer: x Points S Criterion n e.g. Energized Time

  38. Evaluation Process For a Significance Based Maintenance: Condition 1. Asset Scaling: Score: 100: Bad Condition 0: Very Good Condition

  39. Evaluation Process For a Significance Based Maintenance: Condition 2. Substation Normalized Condition of Transformer Substation: 29 (quite good)

  40. Evaluation Process For a Significance Based Maintenance: Significance Total Index Normalized summation = 44,0

  41. Kinds Of Criteria • identification of condition is necessary on-site • (Inspection) • Data from asset-Information system • (no changes during life-cycle of equipment • Data from Asset-Information System • (no changes during life-cycle of equipment) • Periodical estimation for equipment-groups • (spare part supply) K.O. - Criteria: activity normaly necessary at once ! Leakages, partial discharges etc.)

  42. From Condition And Significance To Priority 100 Area 1 Condition Area 2 Area 3 Index g 100 Significance 36,5 Ranking of activity: The substation with the highest index is to be replaced first (area 1). The substation in the example above (area 3)gets an extended inspection period. In area 2 the substation will get a reduced inspectionperiod. By turning the angle of 45° you canchange the weighting between condition and significance

  43. Limiting Values K.O.- criterium: maintenance when possible instantly, but not later than a year Single component bad: more than 30 pts (normalized) rehabilitation required against significance Total index: more than 60 pts (normalized) rehabilitation or maintenance to be proofed External initiation: civil works, conclusions from calculation

  44. Inspections Periodical surveys: suggestion normalized period: 4 years if necessary (AIS with heavy contamination 2 years) Periodical maintenance: suggestion GIS: 10 years AIS with heavy contamination 4 years, depending on condition and special recommendations of manufacturer Special tools: thermography partial-discharge measures

  45. Inspections Initial survey

  46. Inspections Periodical survey

  47. Cable distribution cabinet Thermography Bad connection in a MV cable sealing end - High investment cost - Education an training needs + Diagnostics of weak spots at an early stage + cost savings by specific improved efficiency damaged Diazed-element in a LV-switchgear

  48. Measurement of partial discharge of a paper insulated MV-cable typ. max. PD-Values: paper insulated cable 10.000 pC XLPE cabele 7.000 pC

  49. Live Maintenance • + operation without disconnection possible • no switching risk, no emergency generator required • + economic for refill of cable-boxes • Especially trained staff needed • A lot of technical equipment needed • - Residual risk

  50. Inlet- and outlet-air h Pierce-proofed ventilation grille Increase of required area Ventilation grille for 10%Jalousie for 50% (free profile) Outlet-air ~ 1,1 x inlet-air PV = P0 + k x PK With k = 1,06 for oil filled tranformers and k = 1,2 für cast resin transformers

More Related