An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Developing a Simplified Heat Pump Sizing Procedure Or Don’t write specs you cant enforce

  2. Current Status • PTCS allows for a full Manual J sizing procedure or the PTCS spreadsheet • We don’t know how well this working • COTRs “look” at the file, there is no QA follow up • The printout for most Manual J runs don’t list the inputs making verification impossible if attempted • Capacity tables of heat pumps are not required

  3. Obstacles to Greater Sizing • PTCS does not have the resources to QA the existing sizing procedure • Training • QA • Pre screening of raw data for error checking purposes

  4. A possible approach that can be enforced • MUST BE SIMPLE! • Simple means a number two pencil and a sheet of paper. • Simple means it be error checked in I a minute • Simple means the QA person can verify input in 5 minutes

  5. Why Simple Might Work • We only care about keeping the balance point below 30F • Cooling load is complicated, heating is not • We live in a place with dry summers, over sizing the AC will not cause discomfort due to high RH. • R410 heat pumps seem to have about 68% of their rated capacity at 30F • Limited to insulated homes with sealed and insulated ducts (like the current calculator)

  6. What all this Means • All we care about is the heat loss at 30F • No more “oops I got the wrong city” • One size fits all • We match that heat loss against 68% of the rated output and this produces the minimum size heat pump PTCS will accept • The heat loss procedure can be really simple

  7. How It Works Three Ton Hp is the min. size OR the real simple method: 23,700/3= 660 sq ft per ton

  8. Next Step • Fine tune the capacity of heat pumps at 30F table • Test with contractors • Test with utility managers