An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. RHEEM COMMERCIAL WATER HEATING TRAINING

  2. TRAINING COURSE OBJECTIVES • Introduction to Rheem Commercial Booklet • Range appreciation • Familiarise key design / installation criteria • Introduction to manifolding • Introduction to sizing • Value added service

  3. Commercial Water Heating course contents • Chapter 1 - Range overview - Commercial Booklet • Chapter 2 - Heat Pump • Chapter 3 - Commercial Solar • Chapter 4 - Equaflow Manifolding • Chapter 5 - Commercial Continuous Flow • Chapter 6 - Commercial Storage Gas systems • Chapter 7 - Raypak Heating and Hot Water • Chapter 8 - Commercial Electric • Chapter 9 - Guardian Warm Water • Chapter 10 – Pump Sets • Chapter 11 - Sizing and Selecting • Chapter 12 - Commercial installation and design

  4. Chapter 1 Range Overview & Rheem Commercial Booklet

  5. Chapter 2 - Commercial Heat Pump

  6. COMMERCIAL HEAT PUMP LAYOUTS

  7. COMMERCIAL HEAT PUMP LAYOUTS

  8. Chapter 3 - Commercial Solar

  9. Commercial Solar • Terminology • Split / Pumped / Loline • Close Coupled / Thermosiphon / Hiline • Direct / Indirect (Premier Hiline)

  10. Commercial Solar Loline

  11. Commercial Solar Loline • Pumped system • Collectors and tank are split • Fluid is pumped between collectors and tanks • Can be on same level or different levels • Direct system • Consumed water passes through the collectors • Partial frost protection • In series boost

  12. Commercial Solar Loline • 325L and 410L vitreous enamel storage tanks • Manifold tanks as required • NPT200 collector • Painted aluminium selective surface • 7 riser tubes • Good performance in all regions

  13. Commercial Solar Loline • Frost • Limited frost protection • Frost sensor strategy • Electric or gas frost heater • Secondary Solar Recirculation • Maximum solar energy use • reduces energy use • BMS output • Run and fail status

  14. Commercial Solar Premier Hiline

  15. Commercial Solar Premier Hiline • Thermosiphon system • Collectors and tank are close coupled • Fluid rises through collectors naturally to tank • Tank is always above collectors • Indirect system • Transfer fluid passes through the collectors and transfers heat to tank via heat exchanger • Full frost protection • In series or in- tank electric boost

  16. Commercial Solar Premier Hiline • 300L stainless steel tank • Manifold systems as required • 8 systems per array, multiple arrays possible • S200 collector • Steel collector • Painted selective surface • Good performance in all regions

  17. Flat Plate vs Evacuated TubeCollectors

  18. Chapter 4 EQUA-FLOW MANIFOLDING

  19. EQUA-FLOW BASICS

  20. EQUA-FLOW BASICS • Header diameters for cold/hot to be equal • Branch diameters for cold/hot to be equal • Hydraulic water flow “In one side, out the opposite” • Balanced performance per unit. Full delivery capacity from system Flow direction Out In Line Flow direction In

  21. EQUA-FLOW BASICS Flow direction Out Back to Back Flow direction In

  22. EQUA-FLOW BASICS 1 1 B 0+1+1=2 A 0

  23. PATH of LEAST RESISTANCE 1 1 B A 1 1

  24. MORE EQUA-FLOW PRINCIPLES A B 1 2 1+2+2+1+0=6 1+2+1+2=6 0+2+1+1+2=6 1 2

  25. ANGLED MANIFOLD A 3 + bend 1 1 3 + bend B

  26. BACK TO BACK MANIFOLD 0.75 1 1 H4: 0.75+1+1 = 2.75 H6: 0.75+1+1 = 2.75 A B H2: 0.75+1+1 = 2.75 H5: 1+1+0.75 = 2.75 H1: 0+1+1+0.75 = 2.75 H3: 1+1+0.75 = 2.75 1 1 0.75

  27. EQUAFLOW PRINCIPLES IN PRACTICE

  28. COMPLICATED EQUAFLOW PRINCIPLES IN PRACTICE When designing/ inspecting complicated manifolds consideration must be given to primary loops as well as hot and cold headers

  29. EQUAFLOW PRINCIPLES IN PRACTICE

  30. COMPLICATED EQUAFLOW PRINCIPLES IN PRACTICE

  31. BRANCHES • NEVER use non-return valves or pressure limiting valves in the branch • These create imbalance in the branches • Non-return and pressure reducing valves must be in a train on the cold water inlet COLD WATER SUPPLY TO WATER HEATER MANIFOLD

  32. BRANCHES • Last branch should be a T piece, not an elbow, to maintain equal resistance in all branches T PIECE

  33. Chapter 5 - Commercial CFWH

  34. USE MM AND FF ADAPTERS IF HORIZONTAL LENGTH OF HORIZONTAL TERMINATING FLUE EXCEEDS 2.7M TRIM RING USE CONDENSATE DRAIN & TRAP IF VERTICAL SECTION OF HORIZONTAL TERMINATING FLUE EXCEEDS 2M RHEEM INDOOR CFWH – FLUE SYSTEMS

  35. Rheem Multipak, Tankpak, Commpak and Commpak PlusCommercial Continuous Flow Hot Water Solutions

  36. Chapter 6 - Commercial Gas Storage

  37. RHEEM Commercial Gas Storage • Work horse of the industry • 3 input sizes – 50, 110, 200MJ/hr • Indoor and outdoor models • Multi-fin flue technology • Flue damper • Hot Surface Ignition • Up to 82oC • Room sealed flue

  38. HD Gas Layout

  39. 631275 Room Sealed Flue • Converts outdoor model to indoor room sealed • Ideal where no ventilation, contaminated air supply or fluing to roof impractical • 3m and 3 x 90o bends • Re-use flue terminal • Kit P/No 299135

  40. Chapter 7 – Raypak Heating and Hot Water

  41. Raypak Layouts

  42. Chapter 8 - Commercial Electric Storage

  43. RHEEM Commercial Electric Storage • Work horse of the industry • 2 x 3 element models – 50 & 315L • 1 x 6 element model – 315L • Up to 36kW output • Indoor and outdoor installation • Heavy Duty enamel • Larger anode • Models up to 82oC

  44. HD Electric Layout

  45. Chapter 9 - Rheem Guardian Warm Water

  46. Chapter 10 - Pump Sets