1 / 23

Natural Gas Pipe Sizing

Natural Gas Pipe Sizing. Procedure:. Find the longest run from the gas meter to the farthest appliance. Use linear feet. Add up the Btuh input of all appliances connected to this gas line. Enter the table at the longest run column and don’t get out of it again.

Télécharger la présentation

Natural Gas Pipe Sizing

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Natural Gas Pipe Sizing

  2. Procedure: Find the longest run from the gas meter to the farthest appliance. Use linear feet. Add up the Btuh input of all appliances connected to this gas line. Enter the table at the longest run column and don’t get out of it again. Size all piping using this column (mains, branches, etc.).

  3. Longest run = 15 + 10 + 3 + 3 + 46 + 2 = 87 Linear Feet 8 +

  4. Total Btuh input of all appliances = 45 + 60 = 290,000 Btuh 100 + 50 + 35 +

  5. Longest run = 87’ Pipe size = 1 ¼” Total input = 290 MBH

  6. 1 ¼” 290 – 150 = 140,000 Btuh

  7. Pipe size = 1” 140 MBH

  8. 1 ¼” 1” 140 – 35 = 105,000 Btuh input

  9. 105 MBH Pipe size = 1”

  10. 1 ¼” 1” 105 – 45 = 60,000 Btuh input

  11. 60 MBH Pipe size = ¾”

  12. ¾” 1 ¼” 1” Boiler and Hot Water Heater branch line = 150,000 Btuh

  13. 150 MBH Pipe size = 1”

  14. 1” ¾” 1 ¼” 1” Hot Water Boiler branch line = 100,000 Btuh

  15. 100 MBH Pipe size = 1”

  16. 1” 1” ¾” 1 ¼” 1” Hot Water Heater branch line = 50,000 Btuh

  17. 50 MBH Pipe size = ¾”

  18. 1” ¾” 1” ¾” 1 ¼” 1” Clothes drier branch line = 35,000 Btuh

  19. 35 MBH Pipe size = ½”

  20. 1” ¾” 1” ½” ¾” 1 ¼” 1” Range/Oven branch line = 45,000 Btuh

  21. 45 MBH Pipe size = ¾”

  22. ¾” 1” 1” ½” ¾” ¾” 1 ¼” 1” Finished. Make-up your pipe and fitting list.

  23. Any questions? Thank you for your time and attention.

More Related