1 / 25

Chapter 3 (cont) Solid and Liquid Insulating Materials

Chapter 3 (cont) Solid and Liquid Insulating Materials. Solid and Liquid Insulating Materials. Liquids and solids have higher molecular densities than gases – in terms of Paschen’s Law a better insulating performance is expected

ciara
Télécharger la présentation

Chapter 3 (cont) Solid and Liquid Insulating Materials

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Chapter 3 (cont) Solid and Liquid Insulating Materials

  2. Solid and Liquid Insulating Materials • Liquids and solids have higher molecular densities than gases – in terms of Paschen’s Law a better insulating performance is expected • Practical factors, such as impurities and non- homogeneity cause a worse than expected performance.

  3. Dielectric constant/Polarization • Dielectrics have the property of polarization, i.e. the molecules are dipoles. • If the applied field is zero, the dipoles are randomly arranged. • When a field isestablished, thedipoles are alignedin the direction ofthe field.

  4. Losses in dielectrics: tan  • Dielectric losses. • AC: molecules try to follow field • Polarization of dielectric • Inter-molecular friction due to applied ac field • Heat generation • Proportional to tan , V2: • P = VIR = VICtan  = V(V 2f C) tan  = 2 f C V2 tan 

  5. Solid Insulating MaterialsTypical materials

  6. Solid Insulating MaterialsThermal breakdown • Thermal runaway • When heat generation > Heatloss- thus thermal instability • Two cases • overvoltage and • increase in thermalresistance due to drying outof surrounding soil –overloadingof cables. Overvoltage condition: Soil drying out:

  7. Solid Insulating Materials FailureInternal Partial Discharges • Electric Field higher in gas-filled voids (2.2.4). (1E1=2E2) • Discharges in the voids causedamage to the solid material: • electron bombardment • UV • ozone

  8. Solid Insulating Materials FailureTracking and Erosion • Surface discharges caused by poor design (3.3.2c) • Conducting carbonaceous tracks form (tracking) or • Loss of material(erosion) • Aggravated by dustand pollution.

  9. Insulating Liquids • Mineral oil used in transformers for cooling and insulation, together with paper. • Molecules more closely packed - higherflashover voltage expected. • Causes of failure: • Water (50 ppm: 50 => 23 kV/mm) • Fibre bridges • Gas bubbles • Standard oil test: 2.5 mm gap withstands 60 kV

  10. InsulatingLiquids (cont.) • Flashover mechanisms: • Fibre bridge formation: cellulose fibre dipole (+absorbed water) are arranged head-on-tail (dipoles move to the highest field) • Air bubbles, Water drops(partial discharges) • Oil test: 60 kV across a2.5 mm gap.

  11. InsulatingLiquids (cont.) • Practical aspects: • Conservator (expansion tank) + silica gel breathers. • Barriers (hard paper insulation) between windings prevent fibre bridge formation. • Regular oil purification toremove fibres andmoisture. • Chemical oil tests andgas analysis.

  12. Gas Analysis of Oil • Oil analysis (gas in oil) nowadays plays an important part in transformer diagnostics. • Transformer insulation basically consists of oil and cellulose (paper). • The main degradation processes of these materials are: • Corona • Pyrolysis (decomposition due to heating in the absence of oxygen) • Arcing.

  13. Gas Analysis of Oil (cont.) • Typical gases that are formed are: • methane (CH4) • ethane (C2H6) • ethylene (C2H4) • acetylene (C2H2) • hydrogen (H2) • Carbon monoxide (CO) • and carbondioxide (CO2).

  14. Combinations of insulation systemsParallel systems • Electric field in both parts the same: • E=V/d • Example: • The two electrodes are d = 5 cm apart. Material A is a solid material with a relativepermittivity of 6 and a dielectric strength of600 kV/cm, while materialB is an insulating oil witha 2.3 permittivity and adielectric strength of120 kV/cm. At whatvoltage will the systemfail? Ignore end effects.

  15. Combinations of insulation systemsSeries systems • Example (1E1=2E2) • In Fig. (a), a uniform air gap of 10 cm is shown with a voltage of V = 200 kV across the gap. It follows that E = 200/ 10 = 20 kV/cm.The gap will not flash over at this voltage. • In order to "improve" the reliability, a 9 cm thick sheet of epoxy with a relativepermittivity r = 3 wasintroduced in the gap asshown in Fig.(b). Did itwork?

  16. Combinations of insulation systemsSeries systems (cont.) • Void in dielectric(1E1=2E2)

  17. Practical Design: Insulator • Note that the field is higher in the air sections of the series path between the electrodes. • Further the field strength is high near the electrodes.

  18. Surface Discharges • Field lines cross boundarybetween solid and air. • Field strength in air highest(1E1=2E2) • Air has a lower breakdownstrength than glass andbreaks down first. • Air on the surface of theglass breaks down – theglass remains intact.

  19. InsulatorPollution • A salty layer forms on the insulator surface. • Near the coast or in industrial areas. • Moisture (fog, humidity)is absorbed into the layerand forms a conductinglayer on the insulator.

  20. Insulator Pollution (cont.) • The layer dries out at thenarrowest parts. • Highestcurrent density/powerdissipation. • Arcs develop over the drybands – until completeflashover occurs.

  21. Polymeric Materials • EPDM Rubber (Ethylene Polythene Diene Rubber): • Not hydrophobic – has been shown to age in severely polluted regions. • Silicone rubber: • Hydrophobic, even when polluted.

  22. Hydrophobic polymeric materials

  23. Hydrophobicity

  24. Summary of Insulating Materials

  25. Summary • In this chapter the properties of gaseous, liquid and solid insulating materials and combinations thereof were explored. • In the next chapter laboratory methods to be used to evaluate the strength of insulation systems will be discussed.