This document outlines the steps to calculate the voltage regulation for a 220-volt three-phase generator. The generator has a synchronous impedance of Zsynch = 0.135 + j1.22 Ohms. Given a rated current of 82 amps and a lagging power factor of 0.8, we determine the voltage regulation. Key calculations include finding the resulting voltage and the final regulation percentage, which is computed to be 64%. This analysis is crucial for assessing generator performance in varying load conditions.

cody-duffy
Télécharger la présentation

Voltage Regulation Calculation for 220V Three-Phase Generator with Lagging Power Factor

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Three-Phase GeneratorRegulation Problem: For the 220 volt three-phase generator, having a Zsynch = 0.135+j1.22 Ohms Determine the voltage regulation for a rated current of 82 amps and 0.8 lagging power factor

  2. Calculations  = Cos-1(0.8) = -36.8 o VOC = I /  (Zsynch) + 127 VOC = 82 / -36.8 o (0.135 + j1.22) + 127 VOC =208 volts

  3. Final Calculations • VNL = 208.8)(√3) = 361 volts • VFL = 220 volts • Reg = (VNL-VFL)/VFL = 64 %