An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Understanding Micrologic

  2. Contents • Range • Protection against overloads • Protection against short-circuits • Protection against insulation faults • Hardware • Metering • Others functions • Monitoring and/or protection of loads • Load shedding and reconnection • Programmable controller • Harmonic • Asic and microprocessor self-protection

  3. MicrologicRange Micrologic 6. 0 P Measurement type version Current protection type Without Measurement type P A H Current protection type 5.0 H 6.0 H 7.0 H 5.0 P 6.0 P 7.0 P 2.0 A 5.0 A 6.0 A 7.0 A 2 : Distribution L, I 5 : Selective L, S, I 6: Selective and ground fault L, S, I, G 7 : Selective and earth leakage L, S, I, V 2.0 5.0 Return to contents

  4. Protection against overloadsphases LT setting • Long-time protection (i²t) of the phases and the neutral • Protect against premature ageing of cables • Adjustable setting range using rating plugs • standard : 0.4 - 1, low : 0.4 - 0.8, High : 0.8 - 1, plug OFF • Setting to within one Amp with keypad or via Communication é8 Protection against risk of fire

  5. Protection against overloadsneutral conductor • Neutral protection • Adjustment : • by three position dial on the 4th pole : 4P 3D, 3D+N/2, 4P 4D • by keypad : OFF, 1/2, Full, 1.6 (3 pole breaker only) • Settings : • N/2 : IrN = 1/2 IrP, IsdN = 1/2 IsdP, IiN = IiP, IgN = IgP • 1.6N : IrN = 1.6 IrP, IsdN = 1.6 IsdP, IiN = IiP, IgN = IgP • Oversized neutral protection • protection against 3rd-order harmonics summed up in the neutral conductor • 3Pole breaker only

  6. Protection against overloads3rd harmonic in neutral conductor

  7. Protection against overloadsIDMTL • Long-time protection of the phases IDMTL type (Inverse definite minimum time lag) • High voltage fuse • Extremely inverse time • Very inverse time • Standard inverse time • Definite time Improvement of discrimination with HV fuses Better protection of switchgears Return to contents

  8. Protection against short-circuits • Short-time protection • For low impedance short-circuits (80% of faults) • I²t ON to improve discrimination with downstream protection, inverse time protection up to 10Ir • Instantaneous protection • For solid short-circuits • N1 and H1 breaker : OFF position inhibits the instantaneous protection • H2, H3 and L1 breaker : OFF postion = DIN value (shown on screen) • RMS measurement with 20ms fixed time delay ST pick-up ST delay Inst. pick-up Protection against risk of damage

  9. Protection against short-circuits Zone selective interlocking (ZSI) • Principle : • ZSI enables the control units to communicate with each other. The system is able to locate the short circuit or ground fault and clear it. • Functionning : • ZSI allows the circuit breaker to ignore its preset delay when necessary. The fault is cleared by the nearest upstream circuit breaker with no intentional time delay. • Advantages : • Faster tripping time without sacrificing coordination • Limitation of system stress by reducing amount of let through energy. Maximum : 100 circuit breakers interconnected whatever the configuration Return to contents

  10. Protection against insulation faultsGround fault • Ground fault protection • Micrologic 6.0P • Made mandatory by NEC • Residual current Source Ground Return Ig Prevent risk of fire

  11. Protection against insulation faultsEarth leakage New • Earth-leakage protection • Micrologic 7.0P • Mandatory per standards NFC 15100 and IEC 364 • In a TT system, protects property against low level fault currents • In a TNS system, protects installations where long cables are installed Return to contents

  12. Opto Com Hardware Principle and power supply ZSI M2C/M6C COM Module ASIC Basic protection L S I G V Microprocessor Additional functions (monitoring, measurement, analyses...) Synchronous Exchange data Mitop Air CT Isolation Plugs : Calibre/ perform. Optical coupling Iron CT Power supply Trip unit power supply Surplus Optional external 24V DC power supply for : programmable contact power supply and when breaker is open : • Powers display, • Identification, adjustments through “Com” module Test kit Standard Internal voltage sensor <690v or optional external voltage sensor for µP power supply and measurement 24V DC BUS power supply Return to contents

  13. MeteringPrinciple Refresh Sampling 544µs 1 s 1s Integration Instant. data 15 s (sliding) 5..60 min (fixed) 5 to 60 min Integration Demand data Return to contents

  14. 10ms RMS measurement • Sampling frequency : • 1838Hz • One measurement point every 544µs • 36 points per cycle • RMS value calculation 20ms

  15. Others functionsPrinciple Meter Monitor Programmable Controller Logging: Data Logs Historical Data Maintenance Data Instant. data IRMS P Q S EP EQ Min / Max Max I1 : Min f17 Thresholds (pickup & dropout) Demand Iavg Pavg Relay Activation M2C/M6C Breaker trip Mitop Return to contents

  16. Demand measurementsfixed or sliding window • fixed window • Measurement of active reactive and apparent power • time intervals programmable between 5mn and 1h • values are refreshed at the end of the time interval • Sliding window • Measurement of current and active reactive and apparent power • time intervals programmable between 5mn and 1h • values are refreshed every 15 sec sliding fixed 5mn to 1h t 15s

  17. Power factor PF • Power factor • PF = P/S P: active powerS: apparent powerNota : cos ф= P1/S1P1 : Fundamental active powerS1 : Fundamental apparent power apparent power S kVA reactive power Q kvar active power P kW

  18. Reactive Power Reactive Power Watts - VArs + P.F + Watts + VArs + P.F - Watts - VArs + P.F + Watts + VArs + P.F + Watts - VArs - P.F - Watts + VArs - P.F + Watts - VArs - P.F + Watts + VArs - P.F - Power factor PFSign convention Reactive Power Watts - VArs + P.F - Watts + VArs + P.F + Active Power Active Power Active Power Watts - VArs - P.F - Watts + VArs - P.F + IEEE : PF sign = - Q sign(P/S) IEEE altenate : PF sign = Q sign(P/S) IEC : PF sign = sign(P/S)

  19. Monitoring and/or protection of loadsbased on current, voltage, power, frequency • Current and voltage unbalance • Maximum current (per phases & neutral) • Minimum / maximum voltage • Minimum / maximum frequency • Reverse power • Phases rotation

  20. Monitoring and/or protection of loads Principle of operation variable T1 Activation threshold Deactivation threshold T2 t Alarm generated by Micrologic

  21. E max Monitoring and/or protection of loads Current unbalance ANSI 46 • Application • Protect rotating machines (motors, generators) operating on balanced three-phase supplies against ageing and slowing • Balance single-phase loads on three-phase distribution systems • Detect phase loss • Principle • the function compares the current unbalance to the threshold previously set by the user, for a time greater than the time delay • Example • I1 = 2500A I2 = 4000A I 3 = 3400A • Iaverage. = 3300A • Emax = I1 - Iave. = 800A • DI = Emax /Iaverage = 24% I average I1 I2 I3

  22. Monitoring and/or protection of loads Maximum current per phase and N • Application • Obtain the maximum current demand in the presence of major load fluctuations (welding machines, crushers, hoists) • Principle • This function calculates the maximum demand value of the current in each Ph and Neutral over a sliding time interval. • The interval can be adjusted between five minutes and one hour. • The value is refreshed every 15s I max demand t1 t2

  23. Monitoring and/or protection of loads Voltage unbalance ANSI 47 • Application • Protect loads against vibrations, temperature rise and premature ageing • Principle • The function compares the voltage unbalance to the threshold previously set by the user, for a time greater than the time delay. • Example • U12 = 330v • U23 = 390v • U31 = 10V • U average. = 243v • Emax = U31 - U average. =233v • DU = Emax /U average. = 96% U average E max U12 U23 U31

  24. U12 U23 U31 Monitoring and/or protection of loads Minimum voltage ANSI 27 • Application • Protect motors against voltage drops resulting in loss of torque and a major increase in the current drawn by the motor • Check the output voltage of a generator… • Principle • The function is activated when one of the phase to phase voltages is below the threshold set by the user, for a time greater than the time delay. • The function is desactivated when all 3 phase are above the threshold. U12 U23 U31 Activation threshold U min dectivation threshold U min

  25. Monitoring and/or protection of loads Minimum voltage ANSI 27 U U max activation threshold (maxi 1200V) U min deactivation threshold T2 T1 U min activation threshold(mini 100V) 100V Alarm t

  26. U12 U23 U31 U12 U23 U31 Monitoring and/or protection of loads Maximun voltage ANSI 59 • Application • Protect loads (motor and transformer) against abnormally high voltages that can result in irreversible damage • Avoid saturation of transformers • Principle • The function is activated when one of the phase to phase voltages is above the threshold set by the user, for a time greater than the time delay • The function is desactivated when all 3 phases are under the threshold Activation threshold U max deativation threshold U max

  27. Monitoring and/or protection of loads Maximum voltage ANSI 27 U 1200V T1 U max activation threshold(maxi 1200V) T2 Deactivation threshold U min activation threshold (mini 100V) Alarm t

  28. Monitoring and/or protection of loads Reverse power ANSI 32P t • Application • Protect diesel engines from generators operating as motors • marine applications, generator sets… • Avoid power transfers between two parallel-connected sources • Principle • The function is activated when the active power flowing in the direction opposite set by the user is greater than the activation threshold for a time greater than the time delay. Activation Reconnection Deactivation Load shedding Reverse power P kW

  29. Monitoring and/or protection of loads Minimum frequency ANSI 81 • Application • Check the frequency of a generator • Check the frequency across the terminals of a motor • Avoid saturation of transformers following a drop in frequency • Principle • The function is activated when the frequency exceeds the set threshold for a time greater than the time delay

  30. Monitoring and/or protection of loads Minimum frequency ANSI 81 F F max activation threshold (maxi 540Hz) T2 F min deactivation threshold T1 F min activation threshold(mini 45Hz) 45Hz Alarm t

  31. Monitoring and/or protection of loads Maximum frequency ANSI 81 • Application • Check the frequency of a generator • Check the frequency across the terminals of a motor • Principle • The function is activated when the frequency exceeds the set threshold for a time greater than the time delay

  32. Monitoring and/or protection of loads Maximum frequency ANSI 81 F 540Hz T1 F max activation threshold(maxi 540Hz) T2 F max deactivation threshold F min activation threshold (mini 45Hz) Alarm

  33. Monitoring and/or protection of loads Phase rotation F2 • Application • Avoid reversed rotation of motors • Check on coupling between generator and distribution system (phase sequence) • Principle • The function compares the actual phase sequence with the selected sequence • Alarm only • Not available if the 400 Hz frequency is set F1 F3

  34. Load shedding and reconnectionbased on current t • Application • Ensure the continuity of service of priority circuits by disconnecting non-priority loads • Principle • The function is activated when the current exceeds the set threshold for a time greater than the time delay reconnection shedding I

  35. Load shedding and reconnectionbased on power P kW • Application • Ensure the continuity of service of priority circuits by disconnecting non-priority loads • Principle • The function is activated when the power exceeds the set threshold for a time greater than the time delay 10MW Activation Deactivation 100 kW t Alarm shedding reconnection

  36. Programmable controllerAlarms and relay outputs with distinct thresholds Activation T1 • Alarm • on supervisor via Com module • activation and desactivation after a programmable time delay • M2C or M6C relay outputs • without latching ==> follows the state of the alarm • with temporary latching • programmable from 1s to 6mn • with permanent latching ==> needs a resetting Deactivation T2 t Alarm Relays without latching Relays with temporary latching from 1s to 360s possible Resetting Relays with permanent latching Reset

  37. T1 Programmable controller Alarms and relay outputs with identical thresholds • Alarm • on supervisor via Com module • activation and desactivation after a programmable time delay • M2C or M6C relay outputs • without latching ==> follows the state of the alarm • with temporary latching • programmable from 1s to 6mn • with permanent latching ==> needs to be reset Activation/ T2 Deactivation Alarm Relays without latching from 1s to 360s Relays with temporary latching possible resetting Relays with permanent latching Reset

  38. HarmonicDefinition A periodic signal is a combination of : • The original sinusoidal signal at the fundamental frequency • Other sinusoidal signals (the harmonics) with frequencies that are whole-number multiples of the fundamental frequency • A DC component, where applicable Return to contents

  39. HarmonicOrigin and effects • OriginHarmonics are caused by non linear loads such as : • Welding machines • arc/induction furnaces • Variable speed drive • office equipment (computer, copy machine, neon lighting…) • EffectsThe flow of harmonics in distribution systems can cause serious problems such as : • Increased currents (oversized neutral) • Additional losses and premature aging • Disturbances to loads due to voltage harmonics • Disturbances in communication networks Return to contents

  40. HarmonicQuality indicators • These indicators are the indispensable tools used to determine any required corrective action : • Measurement of the fundamental • Phase displacement of the fundamental • Harmonic distorsion THD • cos ф, power factor • K factor, crest factor • Distorsion power, distorsion factor • Amplitude spectrum up to order 31 st • Displacement spectrum Return to contents

  41. Harmonic Total Harmonic Distortion • Current THD% • Current per phase • Neutral current • Voltage THD% • Phase to phase voltage • Phase - Neutral voltage

  42. Harmonic Fast Fourier Transfert • Current harmonics • each phase plus neutral • up to 31st order • Voltage harmonics • phase to phase • phase to Neutral • up to 31st order Return to contents

  43. Harmonic Waveform capture (WFC) • Triggered manually • 4 cycles • magnitude I : [ 0- 1.5 In] • magnitude V: [0- 690V] • 64 points /cycle • Triggered on event (alarm > 1s) • 4 cycles (on supervisor) • magnitude I : [ 0- 1.5 In] • magnitude V: [0- 690V] • 64 points /cycle • triggered by a fault • 11/13 cycles (50/60 Hz) • magnitude I : [ 0- 20 In] • magnitude V: [0- 690V] • 18/15 points /cycle (50/60 Hz) WFC available through the COM option only

  44. µPro Auto-test µPro & automatic reset Asicwatchdog Maintenance log time recording : Asic maxi temperature ASIC error code Asic and microprocessor self-protection ASIC Self protection : - temperature - power supply deficiency Data exchange reading

  45. Asic and microprocessor self-protection • ASIC self protection • resulting in a circuit breaker tripping : • excessive temperature >120° • ASIC power supply deficiency (overvoltage) • Indication : • LED Ap « ON » • display of error code on LCD screen • Events log recording ===>supervisor • µP self protection • never trip the circuit-breaker • Memory check sum • Time-out • Detection by the µPro of a serial link failure between µP and the ASIC • Indication : • Events log recording ===>supervisor (if communication still healthy)

  46. That ‘s all for today ! Isn ’t it simple and nice ?