Air Flow Analysis in Pharmaceutical “Clean Rooms”. Patrick Phelps ( Flowsolve ) and Richard Rowe ( Clean Room Construction Ltd ). IPUC 8 - Luxembourg - May 2000. Air Flow Analysis in Pharmaceutical “Clean Rooms”. Industrial Context Health and Safety Issues

Télécharger la présentation

Air Flow Analysis in Pharmaceutical “Clean Rooms”

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Air Flow Analysis in Pharmaceutical “Clean Rooms” Patrick Phelps ( Flowsolve) and Richard Rowe ( Clean Room Construction Ltd ) IPUC 8 - Luxembourg - May 2000

  2. Air Flow Analysis in Pharmaceutical “Clean Rooms” • Industrial Context • Health and Safety Issues • Application to an Existing Room • Application to New Ventilation Designs • Conclusions • Experimental Verification

  3. Areas concerned with the preparation, processing and packaging of pharmaceutical products Strict codes of practice employed to eradicate risk of product contamination “Clean Rooms”

  4. “Clean Rooms” • Personnel access controlled • 2-layer sterile over-clothing • Equipment sterilised before entry • Strict cleansing procedures • Particular attention to ventilation

  5. Ventilation of “Clean Rooms” • Design and performance of air supply, filtration, and extraction arrangements must meet exacting standards • Positive pressure areas • Use of Laminar Flow Units (LFU’s)

  6. “ Laminar Flow Units ” Devices which deliver a controlled down-draught of re-filtered air over sensitive regions • preparation areas • processing areas • packaging areas • storage areas

  7. Air Flow Analysis in Pharmaceutical “Clean Rooms”

  8. CFD Application to Air Flow Analysis in “Clean Rooms” Context Upgrade of ventilation system in a suite of “ clean rooms” at a UK pharmaceutical company

  9. CFD Application to Air Flow Analysis in “Clean Rooms” Objective Use CFD to ensure exacting requirements can be met , following installation of a number of LFU’s .

  10. CFD Application to Air Flow Analysis in “Clean Rooms” Workscope 3 rooms selected as representative examples of areas being upgraded • Room 30 • Room 23 • Room 42

  11. Modelling Considerations - 1 • Irregular shaped domains • Internal Obstructions to flow • Cartesian grid employed • K-e (Chen) turbulence model used • Buoyancy important in transient • (otherwise assume isothermal)

  12. Modelling Considerations - 2 Dependent variables solved • pressure, p • lateral velocity component, U • vertical velocity component, V • Longitudinal velocity component, W • Turbulence kinetic energy, k • Turbulence energy dissipation rate, e • residence time parameter, tres • (temperature, T (for transient)

  13. Modelling Considerations - 3 Boundary Conditions • Air supply ducts • prescribed sources of mass, momentum, turbulence and residence time • Air Extract ducts • specified fixed-pressure outlet sinks • LFU’s • inlets and outlets specified as above

  14. Representation of LFU’s • Air flow in individual units not solved • treated as internal blockages in domain • air discharged from base at prescribed rate • matching intake from front face • interactive updating of discharge residence time • constant internal residence time assumed

  15. Room 30 • Small room - 4.94 x 5.94 x 2.92 m. • Used for processing, filling and packaging of products • Contains central plinth with filling-machine enclosure above • Conveyor-linked trays outboard of enclosure, for containers & finished goods

  16. Room 30 - “ Before ”

  17. Room 30 Simulations • Steady flow patterns “ before ” • LFU’s in enclosure only • Steady flow patterns “ after ” • following fitment of 10 new LFU’s • 75,000 node 3-D model • Distribution : 50 x 30 x 50

  18. Room 30 - “ After ”

  19. Room 30 Simulations Objectives • Check for “dead zones” • ensure ventilation criteria met Criteria • 25 Air changes per hour • (residence time 144 seconds)

  20. Room 30 - Sectional Planes

  21. Room 30 - “ Before ”

  22. Room 30 - “ After ”

  23. Room 30 - “ Before ”

  24. Room 30 - “ After ”

  25. Room 30 - “ Before ”

  26. Room 30 - “ After ”

  27. Room 30 - “ Before ”

  28. Room 30 - “ After ”

  29. Room 30 - “ Before ”

  30. Room 30 - “ After ”

  31. Room 30 - “ Before ”

  32. Room 30 - “ After ”

  33. Room 30 - “ Before ”

  34. Room 30 - “ After ”

  35. Room 30 - “ Before ”

  36. Room 30 - “ After ”

  37. Room 30 - “ Before ”

  38. Room 30 - “ After ”

  39. Room 30 - “ Before ”

  40. Room 30 - “ After ”

  41. Room 30 Ventilation Summary(after refurbishment) • Complex flow paths between inlet and outlet • Pattern complicated by LFU intake extraction flows • air has to pass around central plinth and filling-machine enclosure • air in near-side passage has to “run gauntlet” of LFU’s

  42. Room 30 Ventilation Summary(after refurbishment) • Outflow-weighted residence time of 121 seconds meets client criterion • “near” extract air considerably “older” than “far” extract air • some “dead zones” still apparent • evidence of entrainment into more than one unit

  43. “ Dead Zones ” - before

  44. “ Dead Zones ” - after

  45. LFU intake times - 1

  46. LFU Unit intake times - 2

  47. LFU Unit intake times - 3 • Units D1, D2, B2, C2, A1 receive considerably fresher air than their neighbours A2-A4, B2 and C1 • Air entering A4 is 2.2 times older than that entering D1 • Air leaving A4 exceeds air-change criterion en route to outlet

  48. Conclusions • “Residence time” analysis concept adds considerable value to vector and contour plots in assessment of complex ventilation flows.