230 likes | 241 Vues
This report provides an overview of the solar eclipse event on Aug. 21, 2017, including the eclipse path and preparation, coordination efforts, projected and actual solar generation reduction, and other observations. It also discusses the challenges in calculating the impact of distributed PV installations and the effects on system load. The report concludes with observations of system loading, generation output changes, and future eclipse events.
E N D
Solar Eclipse Post-Event Observations Oct 24, 2017 Jason AusmusManager Operations Planning
Overview • Eclipse Path and Preparation • BA/TOP Coordination Efforts • Projected Solar Gen Reduction • Actual Solar Gen Reduction • Other Eclipse Event Observations • Post-Eclipse Analysis Efforts
Peak/BA Eclipse Preparation Efforts • Requested event information and Operating Plans from all BA’s in the Peak footprint (plus AESO) • Summarized into Operating Memo for footprint • Held readiness webinar on Aug 17th to present study results and expected impact • Excellent response from BAs in providing data, operating plans and webinar participation!
Other Preparations by Peak • Real-time Ops Engineers (ROEs) also performed studies the night before utilizing the latest inputs • Created additional displays for situational awareness purposes
Estimated Impacts to Peak Footprint 1Utility Scale number accounts for both Solar PV and Solar Thermal • Utility Scale PV (uPV) estimates made assuming obscuration impact was 1 to 1, i.e. for every 1% obscuration a 1% MW output reduction will occur • Distribution Scale PV (dPV) estimates came from survey results
Actual uPV Impact due to the Eclipse ∆ ≈ + 115 MW/min ∆ ≈ + 80 MW/min ∆ ≈ -55 MW/min
Actual Impacts to Peak Footprint 1Utility Scale number accounts for both Solar PV and Solar Thermal • Actual Utility Scale PV (uPV) reduction confirmed the 1 to 1 relationship between % obscuration and % MW output, i.e. for every 1% obscuration a 1% MW output reduction will occur
Challenge of calculating exact dPV Impact • One of the challenges going into the eclipse was knowing the exact dPV installations • Not a lot of visibility behind-the-meter (BTM) • Difficulty separating changes in system load from changes in BTM generation • Peak collaborating with the National Renewable Energy Laboratory (NREL) • One objective is to determine actual BTM impact of dPV installations of the eclipse by BA
Effect of Distributed PV on System Load • Comparison of load ramp before eclipse (yellow arrow) vs during eclipse (blue arrow) • Load ramp increase due to reduction of distributed PV output resulting in increase in load on system • CAISO Solar Gen • CAISO System Load Eclipse Start Eclipse Max Eclipse Start Eclipse Max
System Loading Observations • During the eclipse, system load decreased • Some load drop was expected • 5% load drop in March 2015 Europe Eclipse • Likely causes were attributed to drop in temperature during the eclipse, human factors (curiosity of the event), etc. • Temperature drops were observed to be anywhere from 4 – 11 degrees in a 1 hour period
BA Area Generation Output – Most Significant Changes *NREL's work was funded by the DOE SunShot Initiative
BA Area Generation Output – Most Significant Changes *NREL's work was funded by the DOE SunShot Initiative
Generation Output by Fuel Type *NREL's work was funded by the DOE SunShot Initiative
Generation Output by Fuel Type *NREL's work was funded by the DOE SunShot Initiative
Select Path Flow Changes *NREL's work was funded by the DOE SunShot Initiative
Select Path Flow Changes *NREL's work was funded by the DOE SunShot Initiative
Other System Event Observations • No reliability issues observed during event • Sufficient reserves were maintained for the duration of the event • Peak and NREL currently collaborating on a final report of the event