1 / 11

Week 4 – NFPA 13: Area Design Calculations

Week 4 – NFPA 13: Area Design Calculations. 1. Area Protected by each sprinkler. A= S x L Where: A = area covered by the sprinkler, in square feet S = distance between sprinklers on the branch lines, in feet L = Distance between branch lines. 2.Determine the Number of Branch Lines.

jake
Télécharger la présentation

Week 4 – NFPA 13: Area Design Calculations

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Week 4 – NFPA 13: Area Design Calculations

  2. 1. Area Protected by each sprinkler • A= S x L Where: • A = area covered by the sprinkler, in square feet • S = distance between sprinklers on the branch lines, in feet • L = Distance between branch lines

  3. 2.Determine the Number of Branch Lines • Number of Branch Lines = (Width of Bay)/(Lmax) Where: • Lmax = max allowable distance between sprinklers • Smax=max allowable distance between sprinklers

  4. 3. Determine the Distance Between Branch Lines • L = (Total width of bay) / (Number of branch lines)

  5. 4. Determine the Maximum allowable distance between sprinklers • A = S x L • S = A/L

  6. 5. Determine the minimum number of sprinklers on each branch line • Sprinklers on branch line = (total length of bay) / (Max. distance between sprinklers)

  7. 6. Determine the Actual Distance between Sprinklers (Sactual) • Sactual = (total length of bay) / (number of sprinklers on line)

  8. 7. Verify Sprinkler Coverage • Verify at this time that the actual square foot limitation is in accordance with NFPA 13.

  9. Example • 75 foot by 50 foot warehouse with branch lines running parallel to the 75 ft side. • Ordinary Hazard

  10. Example (cont) • Area max (Amax)as per sprinkler per NFPA 13 (Table 8.6.2.2.1): Ordinary Hazard System = 130 ft2, Lmax=15 ft • # of branch lines=width/Lmax= 50 ft/15ft=3.33, rounded up to 4 • Distance between branch lines: L=total width/# branch lines=50 ft/4=12.5 ft • Distance to walls = 12.5/2 = 6.25 ft • S=A/L = 130 ft2 / 12.5 ft  S= 10.4 ft • Min # of sprinklers on each branch line = (total length of bay)/(max distance between sprinklers)= 75 ft/10.4ft=7.21 sprinklers = 8 sprinklers • Sactual=total length/#of sprinklers on line = 75 ft/8sprinklers = 9.375 feet • Total # of sprinklers = 4 x 8 = 32 sprinklers • Verify sprinkler coverage • A=S x L = 9.375 ft x 12.5 ft = 117.2 ft2

  11. Example - Final Layout • 32 sprinkler, 4 branch lines, 8 sprinklers/branch line