Exercise Ducting Design

Exercise Ducting Design. Determine type and number of resisters Decide on the air distribution Decide on velocity and noise criteria Find worst case scenario Duct Sizing method selected: equal Friction. Data. 10m. 7m. Airflow = 3214 m³/h = 896 l/s. H = 3,5 m. Trox Air Distribution.

jonah-hill
Télécharger la présentation

Exercise Ducting Design

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Exercise Ducting Design • Determine type and number of resisters • Decide on the air distribution • Decide on velocity and noise criteria • Find worst case scenario • Duct Sizing method selected: equal Friction Daikin Europe, Consulting Sales Section

  2. Data 10m 7m Airflow = 3214 m³/h = 896 l/s H = 3,5 m Daikin Europe, Consulting Sales Section

  3. Trox Air Distribution Daikin Europe, Consulting Sales Section

  4. Trox Air Distribution Daikin Europe, Consulting Sales Section

  5. Trox Quick Selection Daikin Europe, Consulting Sales Section

  6. Position and type of resisters 10m How many resisters? L < 1,5 * W 10 < (1,5 * 7 = 10,5) L < 3 * H 10 < 3 * 3,5 = 10,5 in theory, 1 resister could do but the airflow = 896 l/s is TOO BIG for 1 resister 7m For a better air distribution, to avoid draft and noise, we select 8 diffusers H = 3,5 m Airflow= 896l/s Daikin Europe, Consulting Sales Section

  7. A C B C Air Distribution 10m 8-off TDF500’s For 112l/s 7m Airflow= 896l/s Daikin Europe, Consulting Sales Section

  8. Duct Layout Daikin Europe, Consulting Sales Section

  9. Duct Layout Daikin Europe, Consulting Sales Section

  10. Duct Layout - results Daikin Europe, Consulting Sales Section