1 / 8

Mechanical for Oil Heat

Mechanical for Oil Heat. Mechanical codes. Every state has codes. They may be the same in some states, but different in other states. Always have a copy of the mechanical code book of the state you are working in. Since we live in connecticut, here are some mechanical codes that apply to us.

lilika
Télécharger la présentation

Mechanical for Oil Heat

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Mechanical for Oil Heat Mechanical codes

  2. Every state has codes. They may be the same in some states, but different in other states. • Always have a copy of the mechanical code book of the state you are working in.

  3. Since we live in connecticut, here are some mechanical codes that apply to us. • They were taken right out of the international mechanical code book.

  4. Section 303:equipment and appliance location • Sec.303.3 Prohibited locations. Fuel fired appliances shall not be located in, or obtain combustion air from, any of the following rooms or spaces: • Sleeping rooms • Bathrooms • Toilet rooms • Storage closets • Surgical rooms

  5. 303.7 pit locations • Appliances installed in pits or excavations shall not come in direct contact with the surrounding soil. The sides of the pit or excavation shall be held back a minimum of 12 inches from the appliance. Where the depth exceeds 12 inches below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry. Such concrete or masonry shall extend a minimum of 4 inches above adjoining grade and shall have sufficient lateral load-bearing capacity to resist collapse.

  6. 303.8 elevator shafts • Mechanical systems shall not be located in an elevator shaft.

  7. Section 305: piping supports • 305.4: interval of support- piping shall be supported at distances not exceeding the spacing specified in table 305.4.

  8. Table 305.4 piping support spacing • Piping material Horizontal spacing Vertical spacing • ABS pipe 4 ft 10 ft • Aluminum pipe 10 ft 15ft • Brass pipe 10 ft 10 ft • Bass tubing 1 ¼” or smaller 6 ft 10 ft • Brass tubing 1 ½” or larger 10 ft 10 ft • Cast iron pipe 5 ft 15 ft • Copper pipe 12 ft 10 ft • Copper tubing 1 ¼ “ or smaller 6 ft 10 ft • Copper tubing 1 ½ “ or larger 10 ft 10 ft • CPVC pipe 1” or smaller 3 ft 10 ft • CPVC pipe 1” or larger 4 ft 10 ft • Steel pipe 12 ft 15 ft • PVC pipe 4 ft 10 ft

More Related