1 / 8

Accident/Incident: Mossel Bay Municipality. Accident occurred during July 2006

Accident/Incident: Mossel Bay Municipality. Accident occurred during July 2006.

maida
Télécharger la présentation

Accident/Incident: Mossel Bay Municipality. Accident occurred during July 2006

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Accident/Incident: Mossel Bay Municipality. Accident occurred during July 2006

  2. A Senior Electrician from the Mossel Bay Municipality, Eastern Region sustained serious injury (broken leg, ribs and punctured bowel) when he fell to the ground whilst replacing a low voltage distribution box on a wooden pole, which broke at the base. The wooden pole, which forms part of an ABC strain assembly was also supported by a stay wire which sheared at a weak point. The electrician worked on the same pole a week prior to the incident and therefore misjudged the integrity of the wooden pole and stay wire which are erected on an island where the water table is high. Description of events

  3. Great Brak River- Mossel Bay

  4. An investigation has revealed as follows: • A week prior to the incident the electrician worked on the same pole and tapped the pole with a mallet to ascertain whether the inner core of the pole had decayed. As he did not hear a hollow sound from the pole, he assumed that the pole was healthy. • The electrician neglected to examine the condition of the stay wire as it was covered with creepers. It was discovered that the stay wire had deteriorated extensively and was on the brink of failure.

  5. Corroded Stay Wire

  6. Decayed Wooden Pole

  7. Lessons from this incident • A decayed pole in a water logged environment may not give off a hollow sound when tapped with a mallet. • Employees should be constantly alert of hidden defects. A corroded stay wire amongst vegetation is a potentially dangerous condition.

  8. Thank You!