Instead of the "real type 2 characteristic" we use a resistance characteristic

Instead of the "real type 2 characteristic" we use a resistance characteristic. Relates only to 2-wire BEROs. Decisive for the operation of 2-wire BEROs is the module‘s input current at signal state "0" . This must be rated as per the BERO requirements.

odin
Télécharger la présentation

Instead of the "real type 2 characteristic" we use a resistance characteristic

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Instead of the "real type 2 characteristic" we use a resistance characteristic • Relates only to 2-wire BEROs. • Decisive for the operation of 2-wire BEROs is the module‘s input current at signal state "0". This must be rated as per the BERO requirements. • BERO standard EN 60947-5-2 specifies that a current of  1.5mA may flow when a BERO has signal state "0". • As long as the current flowing into the input of our module remains at 1.5mA, the module recognizes this as "0" signal. • The IEC 1131 Type 2 standard calls for an input current of  2mA at +5V. This requires a constant-current sink in the input. • On S5 modules and some S7 modules, this is implemented by a resistance characteristic (passive components) which lets the input current increase in dependence on the input voltage. • The input current of 1.5mA is attained somewhere above +5V, but below the module‘s operating point (typically 9.5V). For this reason, only the IEC 1131 Type 1 standard may be specified (I  0.5mA at +5V). Resistance characteristic IE [mA] Typ. operating point (9.5V) Imin to IEC 1131 Type 2 7 6 BERO- Norm I  1.5mA Imin to IEC 1131 Type 1 2 1.5 0.5 0 5 -30V 30 11 13 15 24 L+[V] “0“ “1“ 2- wire BERO L+ I ==> "0" signal I  1.5mA PLC input resistance M For internal use only

More Related