The JC solution for small buildings and flat LON systems

The JC solution for small buildings and flat LON systems. Positioning. Demand on Small Systems Solutions is increasing HVAC, Electrical, Fire, CCTV Integration, Standard Protocols Support Security or Alarm Monitoring or Fire Station Some competitors offer simple solutions:

omana
Télécharger la présentation

The JC solution for small buildings and flat LON systems

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. The JC solution for small buildings and flat LON systems

  2. Positioning • Demand on Small Systems Solutions is increasing • HVAC, Electrical, Fire, CCTV • Integration, Standard Protocols Support • Security or Alarm Monitoring or Fire Station • Some competitors offer simple solutions: • without network controllers • no need for web servers and applications • less performances versus a full BMS

  3. A solution for small buildings • Competitive, flexible and scalable solution to be proposed where no web access, demand limiting and interactions are requested • Simple solution when specifications or Customers are only considering SCADA oriented systems, including Fire&Security Supervision. • Based on M-Series graphic style • Serial connectivity N2 and MODBUS, BACnet MSTP via router to IP, LON, EIBus, M-Bus using gateways or direct link to PC • Available TCP/IP like MODBUS IP and BACnet over IP; others on request • IP tunnelling available on N2 and MODBUS

  4. Features • Visualization and management for BMS and F&S • Graphic, Alarm, Trend • Read and write single and multiple points • Time stamp and report • Time Scheduler • Enhanced Notification (ESPA,SMS, SNMP) NO WEB, NO interaction, NO demand limiting!

  5. Graphics M-Graphics • Base on M-Series • Graphic with animation • Status and command • Multiple commands • i.e. Zone Set point • Function Mode Command

  6. Data Automation and Integration EDE (Extended Data Engine) • Core of M3i solution • N2 and MODBUS devices integration • OPC connection with data exchange (bridging) • Capability of simple processes

  7. Extended Scheduler ESX • Enhanced Schedule Extension • Easy Scheduler tool creation • Send commands to JC and 3rd party devices • Multiple Command features

  8. Alarms Handling M-Alarm • Alarm visualization for (HVAC, Electric, Fire, CCTV ACS and Intrusion) • Alarm tracking • Alarm acknowledgement

  9. Collecting Trends M-Trend • Graphic and table Trend visualization • Multiple trend points • Zoom function for details

  10. Option: The Reports Generator Metastore • Historical data report (temperature, humidity, pressure etc) energy consumption for energy management • Report on Quick-Report and Excel file (custom template); direct on printer local/network • Set up for report generation (daily, weekly, monthly);

  11. Option: Advanced Notification SMS ANX • Message Management for Alarms to Analog & GSM modems • ESPA Protocol (es. PABX) • Messages tracking • Alarm Query

  12. Option: Supervisioning simultaneous Screens Multiple screen • multiple SVGA video card • multiple screen : alarms, TVCC (Site Manager), topography and site maps

  13. IU9100 N2 bus N2 bus XT/XP DX9100 MIG TC910x Other Vendors Variable Speed Drivers Meter 3-party Emergency Remote I/O Operation Extension Modules: Connectivity to other field buses, applicable when few devices or datapoints have to be reported on M3i Available for LONworks, Eibus, WILO, GRUNFOSS, KSB and M-bus N2 bus connectivity,System 9100, N2OPEN, MIG,VND and 3-party devices • DX9100, DC9100 • TC91xx, SC9100, XT9100, XTM105 • Facility Explorer line • MIG300 Integrator with all available drivers • 3rd party Devices using N2 (VND) protocols • Configuration: • Expandable to 4 serial bus trunks

  14. IU9100 N2 bus FX15 Master Display Master Controller FX15 FX15 FX05 FX15 FX14 FX06 MIG FX05 FX14 Meter FX06 MIG Other Vendors Meter Other Vendors Extension Modules: Connectivity to other field buses, applicable when few devices or datapoints have to be reported on M3i Available for LONworks, Eibus, WILO, GRUNFOSS, KSB and M-bus N2 bus connectivity: FX devices • FX Line devices • System 9100 devices • 3rd party Devices using N2 VND • MIG300 Integrator • Configuration: Expandable to 4 serial bus trunks

  15. IU9100 IU9100 N2 bus Modbus XT/XP 3-party Emergency Remote I/O Operation MIG Multimeter FX06 Other Vendors Multimeter PLC Variable Speed Drivers Variable Speed Drivers 3-party Emergency Remote I/O Extension Modules: Connectivity to other field buses, applicable when few devices or datapoints have to be reported on M3i Available for LONworks, Eibus, WILO, GRUNFOSS, KSB and M-bus DX9100 N2 and MODBUS connectivity • All N2 devices • MODBUS 3rd party devices (Chillers & Rooftop, PLC, Meters, Others) having same bus protocol (RTU or ASCII), same speed and unique addresses • N2 and MODBUS on separate buses

  16. IU9100 N2 bus XT/XP INT-DX-LON01 DX9100 DX9121 3-party Emergency Remote I/O Operation MIG DX9121 FX06 N2E FTT10; PeerToPeer Other Vendors DX9121 Multimeter 3-party Emergency Remote I/O Operation Variable Speed Drivers N2E (DX9121) connectivity • N2 devices • N2E devices: max 20 DX 9121 per INT-DX-LON01

  17. FTT10 LonWorks Fan Split Systems LON Meter IRC Solution PLC LN product line The appropriate SCADA-like Workstation for LonWorks (A simple network using MIP interface, 5000 SNVTs) This version allows connection to devices having MIP interface (up to 4096 variables SNVTs) like VRV systems, PLC, LON gateways FTT10 network with repeaters and FTT/FTT routers are supported. LNS Binding Tool is needed (it has not to be a LNS Turbo Edition Version) LOnworks devices plug-ins can be used at OWS level

  18. Zone Display FTT10 LonWorks (*) Router Fan Split Systems LON Meter IRC Solution LN product line Variable Speed Drivers Zone Display FTT10 LonWorks (*) Router Other LONWORKS Compatible devices FX06 IRC Solution PLC FX15 The appropriate SCADA-like Workstation for LonWorks (VNI interface, LNS Turbo Edition, 5000 or 32000 SNVTs) It allows connection to devices having MIP interface (up to 4096 variables SNVTs) like VRV systems, PLC, LON gateways (*) TCP-IP/FTT10 Routing is supported. A LNS TE server and binding tool is required LOnworks devices plug-ins can be used at OWS level

  19. Zone Display FTT10 LonWorks Router Zone Display FTT10 LonWorks Router The appropriate SCADA-like Workstation for LonWorksM3i LN the appropriate SCADA-like OWS for LN series (*) (*) (*) TCP-IP/FTT10 Routing is supported. A LNS TE server and binding tool is required LOnworks devices plug-ins can be used at OWS level

  20. Facility Explorer FX devices equipped with LON card Zone Display FTT10 LonWorks Router FX06 FX14 FX15 FX15 LON Meter Zone Display FTT10 LonWorks Router FX06 FX14 FX15 FX15 LON Meter M3i LN Workstation and FX devices using LON

  21. Up to 8 M-Bus Meter any M-Bus Meter M-bus connectivity – Energy metering • RS232- M-bus converters to link large amount of M-bus devices (max 255 per bus) • N2 M-Bus modules connecting up to 8 meters • MIG to have a share distributed devices • Metastore can be used to generate Custom reports • Expandable to 4 serial bus for N2 and /or MODBUS • Heat meters as N2 devices are available and covering the billing needs RS232 RS232 M-Bus converter N2 bus MIG N2 to M-bus RS232 to M-bus any M-Bus Meter

  22. EIB/KNX connectivity – Electrical points & Lighting • RS232/EIB interface or IP/EIB interface. • N2-EIB modules are usable in case of need with particular reference to small points or distributed EIBus networks • Various EIB solutions for lightings may be applicable using JC IRC devices N2 RS485 IU9100 Ethernet TCP/IP EIB EIB EIB devices properly configured in the EIB network EIB devices properly configured in the EIB network

  23. Serial or Ethernet Integrations N2 + MODBUS FIRE Panel FIRE Panel Fire connectivity • Fire: • Esser IFC-8000 • Notifier AM-6000 • Data point automatically configured from Fire Panel database files to optimize commissioning time. • Other connections on request, the next are • Notifier Other Panels • Schrack • Any other available on SIS Europe list

  24. Integrations N2 + MODBUS Serial or Ethernet Intrusion Intrusion Intrusion connectivity • Intrusion: • Aritech MASTER ATS • Ademco Galaxy • CCTV : • Pelco MATRIX CM6800 • Data point automatically configured from Intrusion Panel database files to optimize commissioning time. • Other connections on request, • Any other available on SIS Europe list • Planned DVN connection

  25. Over IP MSTP P2000 Fan Split Systems BACnet IP Thick Client Field Bus connectivity Fan Coils,HVAC Meters Variable Speed Drivers Other 3-party controllers BACnet connectivity • System integration as: • P2000 ACS • Split Systems (VRV, VRF,..) • Equipment (chillers, meters,.) • PLCs • Fire panels • Competitors • Others… • BACnet connectivity must be validated by SIS Europe • BACnet validated routers planned in FY06 Q3.

  26. P2000 connectivity details using BACnet IP • P2000 Alarms and Events -M3i OWS can receive P2000 alarms and events, allowing the workstation operator to acknowledge them. During an alarm, the Metasys system can perform a pre-defined action (e.g. the system turns on the lights to a room if a door open alarm has been reported for that area). • Access Hardware and Status Information - P2000 hardware configuration and status information can be accessed from an M3i. • Create Action Interlocks - The P2000 software can be configured to cause actions to occur within the Metasys system when access is granted. • Door Commands and Output Points - The Metasys M3i workstation operator has the ability to initiate a door-open command or trigger a security output point, all managed from a single seat operation.

  27. TCP/IP Network Ethernet Modbus TCP/IP PLC XT/XP DX9100 MIG Serial Integration Fire Intrusion CCTV TC910x Multimeter Tunneling Connectivity • JC N2 Ethernet devices • MODBUS TCP/IP 3rd party devices connection • Needs a converter RS485/Ethernet for the BUS • (LANTRONIX UDS-10, JCI SECVT,...) • MS-SECVT-0 • LANTRONIX UDS-10

  28. PABX ESPA Ethernet SNMP SMS TRAP SNMP Serial Integration UPS IT management connectivity • Using ANX • SMS to mobile, • ESPA to PABX • SNMP to NMS “trap” from UPS SMS=Short Messages ESPA=European Selective Paging Association PABX=Private Automatic Branch Exchange SNMP=Simple Network Management Protocol

  29. Future connectivity Future Connections or Special Applications • According with Release to Sales Note • Contact SIS Europe which can provide several solutions • Available MIG integrations can be moved to M3i platform, contact SIS Europe ?

  30. System Capability (standard configuration limits to be applied,for projects with different needs, please contact SIS Europe) BUS N2 • Up to 100 N2 Devices • Example: • Max 80 TC91xx/FX06 • Max 20 others • DX91xx/FX15 • MIG300 • VND (ex. IME) BUS MODBUS • Up to 100 MODBUS Devices • Example : • 10 Circuit Breaker • 2 PLC • 78 Multimeters • 10 CDZ Liebert Hiross BUS Intrusion • More devices with the same protocol. • Example : • MAX 8 Aritech ATS MASTER or 8 ADEMCO Galaxy MAX 4 connections, MAX 5000 mappable items points BUS Fire • More devices with the same protocol • Example : • Max 8 Fire Centrals • Up to 5000 detectors Ethernet TCP/IP • More devices with different protocol(Tunnelling) • Example : • 5 plc MODBUS TCP/IP • 1 Aritech ATS Master Central • 1 PELCO CCTV LON • Up to 100 device Lonworks devices, 5000 TAGs (SNVT’s) • Flat LON, 32000 Tags, LON network design skills are required. BACNet IP • Up to 4000 objects

  31. Ethernet TCP-IP IU9100 IU9100 N2 bus INT-DX-LON01 DX9100 DX9121 XT/XP MIG DX9121 FX06 N2E FTT10; PeerToPeer meter DX9121 Other Vendors 3-party Emergency Remote I/O Operation 3-party Emergency Remote I/O Operation Networked Workstations • Up to 4 Workstations • Field busses can be connected to each OWS, having access from each Workstation to each bus trunk

  32. 3-party Emergency Remote I/O Operation Touch Screen as Workstation Ethernet TCP/IP M3i running on PC Panel Touch Screen Display having various sizes and fully localizable. All connectivity's available as per standard M3i on PC Touch screens are in evaluation and test. Availability planned end FY06 Q4. SSC Europe to announce the Touch Panel products range in separate deployment, support and coordination activity. RS485 N2 bus XT/XP DX9100 MIG TC910x Meter Other Vendors

  33. Touch Screen as HMI (Human Machine Interface) M3i connecting Local HMI Touch Screens having N2, Eibus and/or Modbus (various sizes, display types and fully localizable). Touchscreen are under evaluation and test, availability planned end FY06 Q4. SSC Europe to announce the Touch Panel products range in separate deployment, support and coordination activity. Ethernet TCP-IP RS485 N2bus RS485 Modbus KNX EIbus RS485 RS485 N2bus” N2 bus XT/XP XT/XP DX9100 3-party Emergency Remote I/O Operation FX15 EIB Multimeter Meter MIG MIG TC910x FX06 Eibus Lighting or I/O system Other Vendors PLC Meter Other Vendors Meter 3-party Emergency Remote I/O Operation Extension Modules Connectivity to other field buses, applicable when few devices or datapoints have to be reported to M3i. Available for LONworks, Eibus, WILO, GRUNFOSS, KSB and M-bus

  34. Interaction with other systems • Links to documents as PDF, excel,…..) • P2000 • Via BACnet,reading status and doors alarm and send command of manual open doors • Using Internet Explorer (P2000 V.3.4) it’s possible manage and insert new account (Web Based) • Fire IFC-8000 • Alarm and trouble sensors, • Get the status of the central

  35. Interaction with other systems • ARITECH ATS MASTER or ADEMCO GALAXY • Alarm receiving and sensor trouble detection • Area and central status • It’s allows the partial &/or total insertion of the protection and the alarm reset • PELCO MATRIX CM6800 • Visualization on TVC or monitor • Different sequence selection • To do the camera Preset on Dome devices • Interaction between Intrusion and TVCC using PC

  36. Interaction with other systems • JC DVN Series • Ethernet connection • From Graphics map clicking on TV Camera: a pop-up with the image will appear • To alarm the DVN is needed an direct interaction with the antintrusion central

  37. Interaction with other systems • In case : • No HW (hardwired) interaction • No field device interactions • No PC h24 controlled • When interaction is a critical M3i mission, UPS is strongly suggested. • Peer to peer communication at field level could be an alternative solution (LON, EIB, Modbus over IP, BACnet,....)

  38. MIG TC-9102 PLC Integration with VCT EDE Sharing value + calculation

  39. Sources calculation EDE Calculation Engine: EDE operators EDE Function EDE can combine multiple sources in a single equation using mathematical operators and functions. Available sources are, OPC/DDE Tags and field Network variables/Items. Equations does not allow managing runtime calculations, load shedding or load rolling. All these applications should be managed by field devices like DX9100 for runtime calculation.

  40. EDE calculation Engine EDE is able to send calculation value to multiple destinations and assign each destination a different value using equations with mathematical operators and functions. Available sources are, OPC/DDE Tags and field Network variables/Items. Equations does not allow managing runtime calculations, load shedding or load rolling. All these applications should be managed by field devices like DX9100 for runtime calculation. @ = Source Equation result.

  41. Considerations Questions & Answers THANKS !