1 / 18

ISENTROPIC EFFICIENCY CALCULATIONS for POSITIVE-DISPLACEMENT ROTARY-LOBE BLOWERS

ISENTROPIC EFFICIENCY CALCULATIONS for POSITIVE-DISPLACEMENT ROTARY-LOBE BLOWERS. Roger E. Blanton, P.E. District Sales Manager Kaeser Compressors, Inc. EFFICIENCY. All air and gas compressors are less than 100% efficient. P1 V1 T1. Position 1. P2 V2 T2. Position 2. EFFICIENCY.

rashad
Télécharger la présentation

ISENTROPIC EFFICIENCY CALCULATIONS for POSITIVE-DISPLACEMENT ROTARY-LOBE BLOWERS

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ISENTROPIC EFFICIENCY CALCULATIONS for POSITIVE-DISPLACEMENT ROTARY-LOBE BLOWERS Roger E. Blanton, P.E. District Sales Manager Kaeser Compressors, Inc.

  2. EFFICIENCY • All air and gas compressors are less than 100% efficient

  3. P1 V1 T1 Position 1 P2 V2 T2 Position 2 EFFICIENCY P2 > P1 V2 < V1 T2 > T1

  4. EFFICIENCY • Entropy is a measure of the energy loss

  5. COMPRESSION MODEL • Constant entropy (isentropic) process is ideal • No heat loss and perfectly reversible

  6. ISENTROPIC COMPRESSION • Follows this relationship, P2 /P1 = (v1/ v2)k » Pvk= a constant where: v = specific volume [ft3/lb] P1, P2 = initial and final pressure [Pabs] k = Cp/Cv = specific heat ratio = 1.4 for air

  7. COMPRESSOR WORK • For continuous isentropic compression of a gas obeying the previous relationship, work per unit mass (ft·lb/lb) is Wis = vdP = P1 * v1 * [k / (k-1)] * [(P2 / P1)((k-1) / k) – 1] BHF = Big Hairy Formula !!!

  8. POWER • hpis = Wis * m / 60 / 550 where m is mass flow rate in lb/min

  9. EFFICIENCY • Isentropic efficiency of a compressor is the ratio of the ideal isentropic work to the actual work required is = Wis / Wact = hpis / hpact

  10. EXAMPLE CALCULATION • Brand K model 42 @ 2000 rpm • P1 = 14.7 psia • P2 = 10 psig (24.7 psia) • T1 = 68° F • ρ1 (density) = 0.075 lb/ft3 • K = 1.4 (air) • BHP = 13.2 (from performance table) • CFM = 222 (from performance table) • m = 222 * 0.075 = 16.65 lb/min

  11. EXAMPLE CALCULATION (cont’d) • v1 = 1/ ρ1 = 1 / 0.075 = 13.33 ft3/lb • k / (k-1) = 1.4 / (1.4 – 1) = 1.4 / 0.4 = 3.5 • P2 / P1 = 24.7 / 14.7 = 1.68 • (k-1) / k) = (1.4 -1) / 1.4 = 0.4 / 1.4 = 0.286 • (P2 / P1)((k-1) / k) = 1.680.286 = 1.16

  12. EXAMPLE CALCULATION (cont’d) Back to the Big Hairy Formula Wis = P1 * v1 * [k / (k-1)] * [(P2 / P1)((k-1) / k) – 1] Wis = 14.7 * 13.33 * 3.5 * [1.16 -1] * 144 = 15,801 ft·lb/lb

  13. EXAMPLE CALCULATION (cont’d) • hpis = Wis * m / 60 / 550 • hpis = 15801 * 16.65 / 60 / 550 = 8 hp

  14. EXAMPLE CALCULATION (cont’d) • is = hpis / hpact • is = 8 / 13.2 = 61% efficient

  15. CONCLUSION • Repeat this procedure for different blowers at the same pressure

  16. CONCLUSION • Perform this calculation on blowers bid for a project to evaluate efficiency • Look at blower efficiency, not just price when making a decision

  17. CONCLUSION • Perform a Life Cycle Cost (LCC) analysis • Typically a 20 year project horizon is considered • Include installation, estimated maintenance, and operating costs • Discount the expenses to net present value (NPV) for comparison

  18. CONCLUSION • Operating cost greatly outweighs first cost • Blower efficiency is important for customer satisfaction