1 / 44

Backflow Prevention

Backflow Prevention. Cross Connection Control. Cross Connection Control Charleston Mt. Pleasant Summerville. Polluted versus Contamination. Pollutant risk – color or odor Contaminant risk – health hazard. Polluted versus Contamination. Irrigation considered contamination risk

Télécharger la présentation

Backflow Prevention

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Backflow Prevention

  2. Cross Connection Control Cross Connection Control Charleston Mt. Pleasant Summerville

  3. Polluted versus Contamination • Pollutant risk – color or odor • Contaminant risk – health hazard

  4. Polluted versus Contamination • Irrigation considered contamination risk • Pesticides and fertilizers

  5. Cross Connection • Cross connection is any connection between potable and non-potable water

  6. Backsiphonage • Backsiphonage is the reverse flow of water

  7. Backsiphonage

  8. Cross Connection

  9. Back pressure • Back pressure is continuous pressure back toward potable water • Elevation example

  10. BACKFLOW PREVENTERS(Can be TESTED) Reduced pressure(RP) • Most pressure loss • $180 • Backpressure, pressure relief valve • Avoid water submersion of relief valve • 12 psi loss

  11. Reduced pressure(RP)

  12. BACKFLOW PREVENTERS(Can be TESTED) Reduced pressure(RP) • 12” above ground installation

  13. Reduced pressure(RP)

  14. BACKFLOW PREVENTERS(Can be TESTED) Pressure Vacuum Breaker (PVB) • Spring-loaded check valves and air-inlet prevent backsiphonageonly • Not intended for backpressure • $70 cost • 5 psi loss

  15. Pressure Vacuum Breaker (PVB)

  16. BACKFLOW PREVENTERS(Can be TESTED) Pressure Vacuum Breaker (PVB) • 12” above highest head installation

  17. BACKFLOW PREVENTERS(Can be TESTED) Double Check Valve • Spring loaded check valves only • No relief valve • 5 psi loss

  18. Double Check Valve

  19. BACKFLOW PREVENTERS(CANNOT be TESTED) Dual check valve • Spring loaded check valves only

  20. BACKFLOW PREVENTERS(CANNOT be TESTED) Atmospheric Vacuum Breaker (AVB) • Float inlet • Not intended for continuous pressure • One for every valve, 6” above highest head • Cheapest • 2 psi loss

  21. Atmospheric Vacuum Breaker (AVB)

  22. BACKFLOW PREVENTERS(CanNOT be TESTED) Anti-Siphon Valve • Control valve with built-in AVB

  23. OTHER BACKFLOW PREVENTION AIR GAP • Breaks vacuum of backsiphonage

  24. OTHER BACKFLOW PREVENTION HOSE BIB • Vacuum breaker attachment

  25. INSTALLATION • Install after POC • A licensed plumber must tap into potable water system • Exception is homeowner that can tap into own water supply

  26. INSTALLATION COPPER PIPE Two feet of copper (type K) in ground, before and after backflow preventer • Rigidity • Exposure

  27. DHEC • South Carolina Department of Health and Environmental Control (DHEC) • http://www.scdhec.gov/environment/water/dwbflow.htm

  28. Copper Pipe Sweating copper pipe

  29. Copper Pipe • Sandpaper or emery cloth to clean pipe

  30. Copper Pipe • Flux surfaces • Helps draw in solder

  31. Copper Pipe • Dry-fit pipe and fitting

  32. Copper Pipe • Heat pipe connection

  33. Copper Pipe • Touch joint with solder • Melts and draws inside

  34. Copper Pipe

  35. TESTING • Tested annually by licensed tester • Certified BF inspector • DHEC, John Watkins 803-898-3567 • 3 day class ($225) • Equipment ($700) • http://www.scdhec.gov/environment/water/dwbflow.htm

More Related