1 / 17

SEPAM Communications Troubleshooting

SEPAM Communications Troubleshooting. Power. Communications module not powered. Power. Communications module not powered. Terminating Jumper. Protocol. Modbus Wiring . 2-Wire RS-485 + connects to + and – connects to - 4-Wire RS-485 +’s and –’s are swapped TX+ > RX+, TX- > RX-, etc.

skimball
Télécharger la présentation

SEPAM Communications Troubleshooting

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. SEPAM Communications Troubleshooting

  2. Power • Communications module not powered

  3. Power • Communications module not powered

  4. Terminating Jumper

  5. Protocol

  6. Modbus Wiring • 2-Wire RS-485 • + connects to + and – connects to - • 4-Wire RS-485 • +’s and –’s are swapped • TX+ > RX+, TX- > RX-, etc.

  7. Modbus Configuration • Modbus Address, Parity, Baud Rate

  8. Incorrect Sepam Port selection • Sepam 80 has dual comm and remote module ports

  9. ION Master Connections • To communicate to an ION meter there are two communication port settings that need to be made. • Comm port on the meter needs to be set to Modbus Master • Modbus Master Options Module must have the comm port assigned to ModbusGate Connection

  10. ION Master Connections (cont)

  11. ION Master Connections (cont)

  12. ION Master Connections (cont)

  13. Common Wrench Errors • Wrench 1 (most common) • Typically CCA63x (CT module) is absent • I/O module is absent • Wrench 2 • Typically caused by faulty wiring between remote module connection. • Wrench 3 • MET148-2 (Temp Module) module is not available • Wrench 4 • MSA141 (Analog Module) is not available • DSM303 (Remote Display) is not available • Wrench 5 • MCS025 (Sync-Check) is not available • Wrench 10 • CPU overload (Sepam 80 only) typically caused by excessively large Logipam program

  14. Wrench 1 (Most Common)

  15. Wrench 1 • Normally caused by: • CT module not attached to relay • I/O card is configured in the software but is not attached to relay • If you are unable to connect with SFT2841 it could indicate a major fault with the base unit • On Sepam 80 it could indicate a faulty memory cartridge

  16. Verifying Cause of Error • IF you are able to connect with the software…

  17. Questions?

More Related