1 / 10

Survey of water main failures in the United States and Canada

During 2011, Utah State University conducted a basic survey of utilities across the United States and Canada to obtain data on water main failures of municipal and private water supply systems. Surveys were mailed to a total of 1,051 US and Canadian water utilities in May and June of 2011.

unibell
Télécharger la présentation

Survey of water main failures in the United States and Canada

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ? ?utility operations Steven Folkman, John Rice, ammon SoRenSon, and nathan BRaithwaite Survey of water main failures in the United States and canada D responded to the basic survey were also invited to participate in a more detailed survey. A total of 188 utilities responded and completed the basic survey, with 47 also responding to a detailed survey. A total of 117,603 mi of pipe were represented in the basic survey and 32,130 mi in the detailed survey. This article documents some of the results from both surveys. One of the primary goals of this survey was to obtain data on current pipe inventories and failure rates of different pipe materials during a previous 12-month period. Most of the responses to the survey were received in the middle of 2011; thus, the survey estimates behavior during the 2010 and 2011 calendar years. The detailed survey allowed collection of a wider variety of data relating to operating parameters, installation practices, and pipe material preferences. uring 2011, Utah State University conducted a basic survey of utilities across the United States and Canada to obtain data on water main failures of municipal and private water supply systems. Surveys were mailed to a total of 1,051 US and Canadian water utilities in May and June of 2011. Those that ReSUltS oF a 2011 SURveY oF UtilitieS in the United StateS and canada PRovideS inFoRmation on wateR main FailUReS in mUniciPal and PRivate wateR SUPPlY SYStemS. 70OCTOBER 2012 | JOURNAL AWWA • 104:10 | FOLKMAN ET AL 2012 © American Water Works Association

  2. SURVEY REGIONS To show participation as a func- tion of geography, the areas covered by the basic survey were broken down into nine regions as shown in the map on page 71. The number of respondents to the basic survey are listed, followed by the number of respondents to the detailed survey in parentheses. •  Region 1—19 (7) •  Region 2—20 (4) •  Region 3—26 (5) •  Region 4—22 (6) •  Region 5—18 (3) •  Region 6—28 (11) •  Region 7—23 (2) •  Region 8—20 (4) •  Region 9—12 (5) No responses were obtained from the Canadian provinces of New Brunswick, Newfoundland, Nova Scotia, Prince Edward Island, or Quebec. Figure 1 shows the miles of water main pipe that were reported in the basic and detailed surveys according to region. water main pipe represented by those utilities. The trend line and equation are a best fit to the data with a zero intercept. The slope of this line indicates that on average there are 264 people served for each mile of water main installed. SURVEY SAMPLE SIZE The total length of water main pipe reported by the 188 survey par- ticipants was 117,603 mi (the survey  did not include sewer or force mains). In 2007 the US Environmen- tal  Protection  Agency  (USEPA)  reported that there are approxi- mately 880,000 mi of distribution MILES OF PIPE VERSUS POPULATION Figure 2 shows the relationship between the population served by the utilities participating in the basic survey and the number of miles of BC AB MB SK QC NL Region 9 AK PEI ON NB WA NS MT ME Region 1 ND VT OR NH MA MN ID WI SD NY WY MI RI PA IA NE Region 6 Region 3 CT NV OH Region 8 Region 2 Region 4 IN IL UT NJ WV CO HI VA KS DE CA MO KY NC MD TN OK AZ NM AR SC DC Region 5 AL GA MS LA Region 7 TX FL This map illustrates the regions as they were defined to report the basic and detailed survey results. FOLKMAN ET AL | 104:10 • JOURNAL AWWA | OCTOBER 201271 2012 © American Water Works Association

  3. survey would then represent approx- imately 10% of the installed water main pipe in the United States. Thus pipe in the United States (USEPA,  2007). The following year, a second  report (Royer, 2008) estimated the  quantified the size of a utility based on the number of miles of water main pipe installed. Four categories were established according to miles of  pipe:  small  (up  to  500  mi),  medium  (500–1,000  mi),  large  (1,000–3,000 mi), and very large  (more than 3,000 mi). Each survey  participant was allocated to one of the categories. Figure 3 shows the distribution of total miles according to these categories. a primary goal of this survey was to obtain data on current pipe inventories and failure rates of different pipe materials during a previous 12-month period. PIPE MATERIALS Many pipe products have evolved over time, and most of these could be broken down into subcategories on the basis of processing and sur- face treatments. These changes, along with new installation tech- niques, should affect the life expec- tancy of the pipe. The basic survey was intended to be relatively simple to complete in order to encourage wide participation. Most utilities have limited records as to which spe- cific pipe materials were installed decades ago. Therefore, subcatego- ries of material types were not tracked in the survey. The results reported in this article represent generic pipe material performance, but may not represent a specific product on the market today. The distribution of pipe materials based on miles of pipe is shown in Figure 4. Pipe material distribution as a percentage of the total length for both the basic and detailed sur- veys is shown in Figure 5. The detailed survey had a smaller num- ber of respondents but still gave a similar material distribution. The “other” category in Figures 4 and 5 includes materials such as high- density polyethylene, galvanized steel, and copper. Eighty percent of the installed water mains are a combination of cast-iron at 28%, ductile-iron at 28%, and polyvinyl chloride (PVC) pipe at 23%. The  amount of concrete pressure pipe (CPP), steel, and asbestos–cement  (AC)  material  types  were  also  reported. The length of high-den- sity polyethylene pipe reported rep- survey sample size is significant and should provide reliable results. The Canadian provinces comprised 8,423 mi of pipe in this survey, or 7.4% of the total. amount of installed water main pipe in the United States to be more than 1 million mi. The current population of the United States is 312 million (US Census, 2011). Using the esti- mate from the previous section of 264 people served per mile of water main, the length of water mains can be estimated to be 1.18 million mi ([312 million people]/[264 people/ mile]). With the use of this last esti- mate, the total length of pipe in the PARTICIPANTS CLASSIFIED IN FOUR CATEGORIES The average utility surveyed had 626 mi of water main, with the largest having 4,468 mi and the smallest having 2 mi. This survey Total miles of pipe by region responding to the basic and detailed surveys FIGURE 1 Basic survey 25,000 20,000 Pipe—mi 15,000 10,000 5,000 0 1 2 3 4 5 6 7 8 9 Region Detailed survey 8,000 6,000 Pipe—mi 4,000 2,000 0 1 2 3 4 5 6 7 8 9 Region 72OCTOBER 2012 | JOURNAL AWWA • 104:10 | FOLKMAN ET AL 2012 © American Water Works Association

  4. point in their systems during a typical day. The survey indicated that approximately 83% of respondents are able to limit pressure fluctuations to less than 20 psi, 11% had pressure fluctuations between 20 and 40 psi, Respondents were also asked to  break down the fraction of total installed pipe length by five pipe-diam- eter categories. Figure 8, which shows the percentage of water mains that fit into each size range, indicates that resented only 0.14% of the total and thus was not tracked as a sepa- rate group. Figure 6 shows the regional distri- bution of pipe material type as a percentage of the total length of pip- ing in that region. Significant differ- ences can be seen in the type of pipe material used in the regions. Cast and ductile iron represent approxi- mately 90% of the pipe in regions 6  and 8. PVC has a dominant role in  region 9 and is a significant player in  regions 2–5, and 7. Pipe age and diameter. The detailed survey asked respondents to provide the age distribution of installed pipe. Four age groups were provided: 0–10 years, 10–20 years, 20–50  years, and more than 50 years. Fig- ure 7, which lists the percentage of water main length that fits in each age category, indicates that approxi- mately 43% of installed pipes are in the 20–50-year age category and  22% are more than 50 years old. the total miles of pipe covered by this survey is almost 10% of that in use in the United States. and 6% have pressure fluctuations in excess of 40 psi. approximately 66% of the installed pipe is 8 in. or less in diameter. Delivery pressure.On the basis of results received inthe detailed survey, the average delivery pressure was determined to be 77 psi. The range of values reported for average delivery pressure was 45–150 psi. Respon- dents were asked to select one of three ranges provided in the detailed survey to indicate how much the water pressure fluctuates at any given PIPE FAILURE Most common failure mode, mate- rial, and age.The detailed survey asked the respondents to identify the most common water main failure mode by selecting from one of the following categories: circumferential crack, corrosion (pits or holes), lon- gitudinal crack, leakage at joints, Population served relative to total pipeline miles from the basic survey FIGURE 2 1,400,000 y = 263.78x R2 = 0.8014 1,200,000 1,000,000 800,000 Population 600,000 400,000 200,000 0 0 1,000 2,000 3,000 4,000 5,000 Pipe—mi FOLKMAN ET AL | 104:10 • JOURNAL AWWA | OCTOBER 201273 2012 © American Water Works Association

  5. fatigue, or other. Figure 9 shows that  circumferential cracks are the most common mode of failure, followed by corrosion. The detailed survey also asked respondents to identify which pipe material failed most often. Figure 10 shows that slightly more than 55% of respondents iden- tified cast iron as the pipe material that failed most often (likely because  it is one of the two most commonly used pipe materials and on average is the oldest pipe material in use),  followed by AC at 17%. Respon- dents also reported that the typical age of a failing water main was 47 years, with a range of values from 20–86 years. The survey also asked  what the respondents believed the expected life should be for newly installed pipe. Respondents expected  new pipe to have an average life span of 79 years, with responses ranging  from 30 to 200 years. Computing failure rates. The basic survey asked respondents to consider a water main failure as one in which leakage was detected and repairs were made. However, they were asked not to report failures caused by joint leakage, construction dam- age, or tapping of service lines. The goal of the survey was only to exam- ine the performance of properly installed pipe. Utilities reported the number of failures over a recent 12-month period according to pipe material and the installed length of pipe mate- rial. The failure rate was computed by dividing the total number of fail- ures from all utilities for a particular pipe material by the total length of that pipe material. For example, the survey reported a total of 12,963  failures of water mains during a recent 12-month period for all pipe materials. The total installed water main length from the survey was 117, 603 miles (or 1,176.03 hun- dreds of miles). Thus the overall fail- ure rate is 12,963/1,176.03 = 11.0  failures/(100 miles)/year. Figure 11  shows the failure rate at each utility for all pipe materials and indicates that utilities can experience widely TABLE 1 Summary of failure data over a 12-month period Number of Failures Failure Rate Number/(100 mi)/(year) Pipe Material Length—mi Cast iron 33,611.0 8,204 24.4 Ductile iron 33,238.7 1,620 4.9 Polyvinyl chloride 26,840.3 689 2.6 Concrete pressure pipe 2,355.3 128 5.4 Steel 4,300.1 581 13.5 Asbestos–cement 13,502.8 954 7.1 Other 3,755.3 787 21.0 Total 117,603.4 12,963 11.0 Total miles of pipe in each size group FIGURE 3 35,000 30,000 Total Length of Pipe—mi 25,000 20,000 15,000 10,000 5,000 0 0–500 500–1,500 1,500–3,000 3,000–5,000 Utility Size Group (in miles of pipe) Total length of pipe classifed according to material type from the basic survey FIGURE 4 40,000 35,000 Other includes HDPE, galvanized steel, and copper 30,000 25,000 Pipe—mi 20,000 15,000 10,000 5,000 0 CI DI PVC CPP Steel AC Other AC—asbestos–cement, CI—cast iron, CPP—concrete pressure pipe, DI—ductile iron, HDPE—high-density polyethylene, PVC—polyvinyl chloride 74OCTOBER 2012 | JOURNAL AWWA • 104:10 | FOLKMAN ET AL 2012 © American Water Works Association

  6. the maximum life out of a water main. The survey asked whether the respondents’ utilities used contractor experience as a weighting factor dur- ing the selection process. Sixty-six percent of respondents do consider contractor experience. Many of those respondents who do not con- sider contractor experience reported that state or local laws prevented them from doing so. and AC pipes, PVC was shown to  have the lowest overall failure rate. Plans for replacing water mains. The detailed survey asked whether respondents had a plan for regular replacement of water mains that are nearing their end of useful life. More than 77% reported they do have a replacement plan in place. The survey also asked what percentage of water mains are beyond their useful life but different failure rates for the same pipe material. This finding should not be surprising. Several significant variables affect pipe performance, including age, soil types (corrosive  or noncorrosive), corrosion preven- tion techniques, installation prac- tices, and climate. Thus a utility may have a significantly different failure rate from those reported here. To compute an average failure rate for a given pipe material, a large num- ber of respondents are needed. Failure rates for each pipe material. The basic survey measured pipe fail- ures over a recent 12-month period, broken down by material type. Table 1 lists the total length of pipe by material type, the number of fail- ures over a recent 12-month period, and the failure rate for each pipe material. Figure 12 shows the failure rates as a function of material type, and Figure 13 classifies the failure rates by material type and by US and Canadian respondents. When the  failure rates per 100 mi of pipe per year were compared for cast-iron, ductile-iron, PVC, concrete, steel,  it is imperative that utilities make wise choices when repairing and replacing pipe, and benchmarking can provide guidance in making those decisions. Allowed pipe materials.Results  from the survey indicated that 87.2% of utilities would allow installation of ductile iron, 59.6% of  PVC, 38.3% of concrete pressure,  and 36.2% of steel pipe. Typical comments regarding pipe exclusion included “corrosion issues for duc- tile iron and steel” and “strength, have yet to be repaired/replaced  because of a lack of funds. Respon- dents reported that from zero to 75% of their pipe was beyond its useful life. The average of all respondents showed that 8.4% of the pipe is beyond its useful life. Contractor experience.Proper installation is important to getting Percentage of total length of pipe classifed by material type from the surveys FIGURE 5 Basic Detailed 35 30 29 28 28 27 25 25 23 Total Length—% 20 15 12 11 10 5 4 3 3 3 2 2 0 Other CI Steel PVC CPP DI AC AC—asbestos–cement, CI—cast iron, CPP—concrete pressure pipe, DI—ductile iron, PVC—polyvinyl chloride FOLKMAN ET AL | 104:10 • JOURNAL AWWA | OCTOBER 201275 2012 © American Water Works Association

  7. FIGURE 6 Regional percentage of length of pipe classifed by material type from the basic survey CI PVC DI Other AC Steel CPP 9 8 7 6 Region 5 4 3 2 1 0 10 20 30 40 50 60 Installed Length—% AC—asbestos–cement, CI—cast iron, CPP—concrete pressure pipe, DI–ductile iron, PVC—polyvinyl chloride 76OCTOBER 2012 | JOURNAL AWWA • 104:10 | FOLKMAN ET AL 2012 © American Water Works Association

  8. tapping difficulties, and bedding concerns  for  PVC.”  Comments  regarding CPP included “difficult to install, tap, and repair” and “has corrosion issues.” Leak-detection methods.The detailed survey asked respondents whether regular leak-detection methods were used at their utility, and 57% indicated that they were. The methods of leak detection used included acoustic leak detectors, visual inspection of lines, digital correlation sensors, and eddy cur- rent detectors. Corrosive soils and corrosion pre- vention treatments.The detailed sur- vey asked respondents whether there are one or more regions in their service area with soils that are corrosive. A total of 75% of the respondents reported that they have at least one area with corrosive soils. Thus, corrosion is a signifi- cant problem for most of the re - spondents. The survey also asked what kind of corrosion treatments they are currently using. Typical corrosion prevention treatments for DI pipe included polywrap and the installation of magnesium anodes. Covered bedding improvements, type 50 concrete, coatings, and the use of anodes were common treat- ments for CPP. Steel pipe corrosion treatments listed impressed current, anodes, and protective coatings. Effect of ambient temperature on fail- ures. The detailed survey asked whether the utility observed an increase in water main failures with extreme ambient temperatures, either warm or cold. The results indicated that 72% of the respondents did note an increase in pipe failures with extreme cold ambient temperatures and only 13% reported a correlation with warm temperatures. Clearly this result would be dependent on the cli- mate at each utility. Percent of pipe length classifed according to age from the detailed survey FIGURE 7 50 43.3 40 Total Length—% 30 22.2 18.4 20 14.9 10 1.3 0 0–10 10–20 20–50 > 50 Unknown Pipe Age—years Percentage of pipe length classifed according to pipe diameter from the detailed survey FIGURE 8 70 65.9 60 50 Total Length—% 40 30 18.4 20 10.1 10 3.4 2.2 0 ?8 10–14 16–24 30–36 ? 36 Pipe Diameter—in. FIGURE 9 Percent of respondents selecting a most common failure mode 60 50 50 Respondents—% 40 28.3 30 20 13.0 10 4.3 2.2 2.2 0 CONCLUSION To capture statistically signifi- cant water main break data that can provide an accurate portrayal of current pipe behavior and water Circumferential Corrosion Fatigue Other Longitudinal Crack Leak Crack FOLKMAN ET AL | 104:10 • JOURNAL AWWA | OCTOBER 201277 2012 © American Water Works Association

  9. •  The primary water main pipe  materials in use today are cast iron (28% of the installed base), ductile  iron (28%), and PVC (23%). The  survey results indicate that the type of pipe material installed varies sig- nificantly across the regions; approx- imately 90% of the pipe in the  northeastern United States is either ductile or cast iron, whereas PVC is  the dominant pipe in Canada. •  Water main pipe characteristics  uncovered by the survey indicate that more than 22% of currently installed pipe is more than 50 years old and that about 66% of water mains are 8 in. or less in diameter. The average age of a failing water main was only 47 years, with 8.4% of pipes classified as being beyond their useful life. These results are in sharp contrast to respondents’ beliefs that new pipe should last 79  years on average. •  The average delivery pressure is  77 psi and 83% of utilities keep water pressure fluctuations at less than 20 psi. •  The survey also found various  limitations placed by utilities on pipe materials. The percentage of utilities allowing installation of specific pipe materials is as follows: ductile-iron pipe—87%, PVC pipe—60%, con- crete pressure pipe—38%, and steel  pipe—36%. •  Utilities exhibit a large variation  in water main failure rates. •  Approximately 75% of utilities  have at least one region in their ser- vice area with corrosive soils. •  This survey found that on the  basis of the number of failures per 100 mi of pipe per year, PVC pipe  currently has the lowest overall failure rate. Information from this survey is intended to assist utilities in seeing how they compare with national norms. The amount of pipe ap - proaching the end of its life is grow- ing. It is imperative that utilities make wise choices when repairing and replacing pipe, and benchmark- ing can provide guidance in making those decisions. individual utilities as possible internal benchmarks. •  There are approximately 264  people who are served per mile of water main pipe, which is an average number representing both rural and urban populations. utility practices requires a large number of participants. The total miles of pipe covered by this sur- vey is almost 10% of that in use in the United States. From these data many observations can be made at a national level and applied to FIGURE 10 Percent of respondents selecting a most common failure material 60 55.3 50 40 Respondents—% 30 20 17.0 10 6.4 6.4 4.3 4.3 2.1 0 CI DI PVC CPP Steel AC Other AC—asbestos–cement, CI—cast iron, CPP—concrete pressure pipe, DI–ductile iron, PVC—polyvinyl chloride FIGURE 11 Total failure rates at each utility relative to miles of pipe for all pipe materials 70 60 (Number of Failures)/(100 mi)/year 50 40 30 Average 20 10 0 1,000 2,000 3,000 4,000 5,000 0 Pipe—mi 78OCTOBER 2012 | JOURNAL AWWA • 104:10 | FOLKMAN ET AL 2012 © American Water Works Association

  10. ACKNOWLEDGMENT This work was completed with support from Uni-Bell PVC Pipe  Association and the Water Finance  Research Foundation. FIGURE 12 Failure rates of each pipe material per 100 mi over a one-year period 30 ABOUT THE AUTHORS 24.4 25 Steven Folkman is an associate professor at Utah State University, 4130 Old Main Hill, Logan, UT 84332-4130; steven.folkman@ 21.0 Failures/(100 mi)/year 20 15 13.5 10 7.1 5.4 4.9 5 2.6 usu.edu. A member of AWWA, Folkman has oversight of Utah State’s Buried Structures Laboratory, is co-author of Buried Pipe Design, and has been involved with analysis and testing of buried structures for more than 20 years. His work has been published previously in Journal of Civil Engineering and Architecture and Transportation Research Record. He received his BS, MS, and PhD degrees from Utah State University. John Rice is an assistant professor and Ammon Sorensen and Nathan Braithwaite are research assistants, all at Utah State University. 0 CI DI PVC CPP Steel AC Other AC—asbestos–cement, CI—cast iron, CPP—concrete pressure pipe, DI–ductile iron, PVC—polyvinyl chloride FIGURE 13 Failure rates reported in this survey by US and Canadian respondents US Canada REFERENCES Royer, M.D., 2008. Condition Assessment of Drinking Water Transmission and Distri- bution Systems. Presented at EPA Sci- ence Forum 2008, Washington, D.C., May 20–22, 2008. www.epa.gov/awi/ pdf/600f09030.pdf (accessed Aug. 31, 2012). 40 35.0 35 30 Failures/(100 mi)/year 23.9 25 21.3 US Census, 2011. www.census.gov/ (accessed Oct. 5, 2011). 20 15.2 USEPA (US Environmental Protection Agency), 2007. Distribution System Inventory, Integrity and Water Quality. www.epa.gov/ogwdw/disinfection/tcr/ pdfs/issuepaper_tcr_ds-inventory.pdf (accessed Aug. 31, 2012). 13.8 15 13.4 10 7.07.5 6.2 4.3 3.9 5 2.9 0.9 0.7 0 CI DI PVC CPP Steel AC Other http://dx.doi.org/10.5942/jawwa.2012.104.0135 AC—asbestos–cement, CI—cast iron, CPP—concrete pressure pipe, DI–ductile iron, PVC—polyvinyl chloride Journal AWWA welcomes comments and feedback at journal@awwa.org. FOLKMAN ET AL | 104:10 • JOURNAL AWWA | OCTOBER 201279 2012 © American Water Works Association