SlideServe
Menu
Préférences
© SlideServe · v2026

Understanding Voltage Regulation in Transformers for ECE 441

urian avatar
17 diapositives · 450 Views · Sep 10, 2014

This document explores voltage regulation concepts essential to ECE 441. It covers no-load output voltage, voltmeter readings during rated apparent power, and the significance of high-side and low-side voltages. Detailed guidelines on measuring voltage regulation, the equivalent circuit approach, and calculations for transformers under varying load conditions are included. An example using a 250kVA transformer illustrates the determination of no-load voltage, input impedance, and phasor diagrams for both lagging and leading power factors.

Understanding Voltage Regulation in Transformers for ECE 441 - slide 1
01 / 17Understanding Voltage Regulation in Transformers for ECE 441
1 / 17

Télécharger la présentation

Understanding Voltage Regulation in Transformers for ECE 441
Une image / un lien ci-dessous est fourni (tel quel) pour télécharger la présentation

Politique de téléchargement : le contenu du site vous est fourni TEL QUEL pour votre information et votre usage personnel ; il ne peut être vendu, concédé sous licence ni partagé sur d’autres sites sans l’accord de son auteur.Le contenu vous est fourni TEL QUEL, pour votre information et votre usage personnel uniquement. Téléchargez la présentation en cliquant sur ce lien. Lors du téléchargement, si vous ne parvenez pas à télécharger une présentation, l’éditeur a peut-être supprimé le fichier de son serveur.Pendant le téléchargement, si vous ne parvenez pas à obtenir une présentation, le fichier a peut-être été supprimé par l’éditeur.

F I N

Plus de contenu associé

Transcription de la présentation
  1. Voltage Regulation ECE 441

  2. Voltage Regulation (continued) • Enl = no-load output voltage • Measure with a voltmeter when no load is connected to the transformer • Vrated = voltmeter reading at the output terminals when the transformer is supplying the rated apparent power • These voltages are all either High-side or Low-side voltages! ECE 441

  3. Voltage Regulation (continued) • Measurements are not always easy to make, so use the equivalent circuit. ECE 441

  4. When the breaker is open, no current flows in Req,LS , jXeq,LS , or ZLOAD,LS , therefore Vout = VLS = E’LS = Enl ECE 441

  5. With rated load on the secondary, E’LS = ILSZeq,LS + VLS ILS = rated low-side current at a specified power factor VLS = rated low-side voltage Zeq,LS = equivalent impedance of the transformer referred to the low-side E’LS = no-load low-side voltage ECE 441

  6. Example 2.7 • The equivalent low-side parameters of a 250kVA, 4160 – 480V, 60 Hz transformer areReq,LS = 0.00920 Ω and Xeq,LS = 0.0433 Ω. The transformer is operated in the step-down mode and is delivering rated current at rated voltage to a 0.840 power-factor lagging load. • Determine ECE 441

  7. the no-load voltage • The actual input voltage on the high-side • The high-side current • The input impedance • The voltage regulation • The voltage regulation if the power factor of the load is 0.840 leading • Sketch the tip-to-tail phasor diagram of the secondary circuit for the 0.840 power factor lagging load. Show all voltage drops. ECE 441

  8. ECE 441

  9. Low-Side Output ECE 441

  10. ECE 441

  11. ECE 441

  12. The high-side current The input impedance ECE 441

  13. The voltage regulation ECE 441

  14. Voltage Regulation if the power factor is 0.840 leading Regulation is negative because of a voltage rise in the transformer due to resonant effects. ECE 441

  15. The “tip-to-tail” phasor diagram for the 0.840 power factor lagging load. ECE 441

  16. Component Phasors ECE 441

  17. Tip-to-Tail Addition ECE 441