1 / 23

HTH HEATECH INC.

HTH HEATECH INC. 8916-44 Str. S.E. Calgary, Alberta, Canada T2C 2P6 Tel. 403-279-1990 Fax. 403-236-5145. ‘fired equipment specialists’. Federally Chartered Founded in 1988 Head Office, Calgary, Alberta Service Office, Edmonton, Alberta Presently over 30 employees on staff.

verna
Télécharger la présentation

HTH HEATECH INC.

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. HTH HEATECH INC. 8916-44 Str. S.E. Calgary, Alberta, Canada T2C 2P6 Tel. 403-279-1990 Fax. 403-236-5145 ‘fired equipment specialists’

  2. Federally Chartered • Founded in 1988 • Head Office, Calgary, Alberta • Service Office, Edmonton, Alberta • Presently over 30 employees on staff Company profile Celebrating 25 years in business! ‘fired equipment specialists’

  3. Core business • Sales of Industrial Heaters, Boilers and WHRUs • Custom Design Fabrication • Skid Packaging • Commissioning Services • Technical Support ‘fired equipment specialists’

  4. WORLDWIDE PRESENCE ‘fired equipment specialists’

  5. Equipment Helical Coil Heaters Flex Tube Water/Glycol Boilers Waste Heat Recovery Units Steam Boilers Atmospheric Heaters ‘fired equipment specialists’

  6. UNILUX – GLYCOL BOILER ‘fired equipment specialists’

  7. UNILUX DESIGN CONSIDERATIONS 5 pass forced gas side flow pattern Combustion side efficiency of 85%+ Four side water wall furnace Generous furnace volume (heat release less than 80,000 btu/hr/ft3 ‘fired equipment specialists’

  8. UNILUX DESIGN CONSIDERATIONS CONT’D Unilux design incorporates external down comer for glycol recirculation, negating the need for minimum flow protection device.

  9. Flexible Water Tube Design Thermal shock resistant Bent tube design absorbs stress due to thermal loads Precision machined tapered ferrules welded to tubes Tubes press fit to machined drums, no welding or tube rolling required ‘fired equipment specialists’

  10. ‘fired equipment specialists’

  11. ‘fired equipment specialists’

  12. FURNACEDESIGN Front wall has 7”of refractory Rear wall has 9” of refractory Castable refractory beneath water wall furnace floor Total heat loss through walls less than 0.5% of efficiency Outer jacket temperature >20oF above ambient ‘fired equipment specialists’

  13. Power Flame Burner ‘fired equipment specialists’

  14. Power Flame Burner FLUE GAS RECIRCULATION FUEL GAS INLET COMBUSTION AIR INLET ‘fired equipment specialists’

  15. Option 1 Proposed Package Glycol Boiler Only • Duty 12 MM Btu/hr • Burner input calculated @ 80% HHV 15 MM Btu/hr of natural gas • Flow rate @ 506 Usgpm 50/50 EG in water ‘fired equipment specialists’

  16. ‘fired equipment specialists’

  17. Option 2 Proposed Package Glycol Boiler with Pump Skid and Building ‘fired equipment specialists’

  18. ‘fired equipment specialists’

  19. ‘fired equipment specialists’

  20. ‘fired equipment specialists’

  21. SHOP CERTIFICATIONS ASME Section I, IV, VIII repairs and alterations Piping to ASME B31.1, B31.3 and B31.9 CWB ABSA registered QC/QA program Health & Safety Certificates (COR, HS&E, ISNetworld, Complyworks) ‘fired equipment specialists’