Lecture Objectives:
Explore the concepts of desiccant-based cooling systems, HVAC control, and PID loops. Learn about different control types and their applications in HVAC systems. Understand the importance of commissioning and optimization for energy savings.
Lecture Objectives:
E N D
Presentation Transcript
Lecture Objectives: • Discuss HW2 • Finish with desiccant systems • Learn about HVAC control • PID loop • Sequence of operation
Figure 3 – A desiccant-based cooling system combined with regenerative heat exchanger, vapor compression cooling, and evaporative humidifier (hybrid system). Desiccant wheel
Variation in Cycles Much more in the paper I gave you (Technical development of rotary desiccant dehumidification and air conditioning)
Control • Process controls • Self-powered controls • Pneumatic and electro-mechanical controls • Electronic controls • Direct digital control (DDC) • Predictive control • ….
Terminology • Sensor • Measures quantity of interest • Controller • Interprets sensor data • Controlled device • Changesbased on controller output Figure 2-13
outdoor Direct Closed Loop or Feedback Indirect Open Loop or Feedforward
Set Point • Desired sensor value • Control Point • Current sensor value • Error or Offset • Difference between control point and set point
Two-Position Control Systems • Used in small, relatively simple systems • Controlled device is on or off • It is a switch, not a valve • Good for devices that change slowly
Example: Heat exchanger control Modulating (Analog) control Cooling coil air water Modulating Control Systems x (set point temperature)
Electric (pneumatic) motor Position fluid Volume flow rate Vfluid = f(position) - linear or exponential function Modulating Control Systems • Used in larger systems • Output can be anywhere in operating range • Three main types • Proportional • PI • PID
Proportional Controllers x is controller output A is controller output with no error (often A=0) Kis proportional gain constant e = is error (offset)
Unstable system Stable system
Issues with P Controllers • Always have an offset • But, require less tuning than other controllers • Very appropriate for things that change slowly • i.e. building internal temperature
Proportional + Integral (PI) K/Ti is integral gain If controller is tuned properly, offset is reduced to zero Figure 2-18a
Issues with PI Controllers • Scheduling issues • Require more tuning than for P • But, no offset
Proportional + Integral + Derivative (PID) • Improvement over PI because of faster response and less deviation from offset • Increases rate of error correction as errors get larger • But • HVAC controlled devices are too slow responding • Requires setting three different gains
The control in HVAC system – only PI Proportional Integral value Set point Proportional affect the slope Integral affect the shape after the first “bump” Set point
The Real World • 50% of US buildings have control problems • 90% tuning and optimization • 10% faults • 25% energy savings from correcting control problems • Commissioning is critically important
HVAC Control Example : Dew point control (Relative Humidity control) fresh air damper filter cooling coil heating coil filter fan mixing T & RH sensors Heat gains Humidity generation We should supply air with lower humidity ratio (w) and lower temperature We either measure Dew Point directly or T & RH sensors substitute dew point sensor
Relative humidity control by cooling coil Cooling Coil Mixture Room Supply TDP Heating coil
Relative humidity control by cooling coil (CC) • Cooling coil is controlled by TDP set-point if TDP measured > TDP set-point → send the signal to open more the CC valve if TDP measured < TDP set-point → send the signal to close more the CC valve • Heating coil is controlled by Tair set-point if Tair < Tair set-point → send the signal to open more the heating coil valve if Tair > Tair set-point → send the signal to close more the heating coil valve Control valves Fresh air mixing cooling coil heating coil Tair & TDP sensors
Mixture 3 DPTSP Set Point (SP) Mixture 2 Mixture 1 DBTSP Sequence of operation(PRC research facility) Control logic: Mixture in zone 1: IF (( TM<TSP) & (DPTM<DPTSP) ) heating and humidifying Heater control: IF (TSP>TSA) increase heating or IF (TSP<TSA) decrease heating Humidifier: IF (DPTSP>DPTSA) increase humidifying or IF (DPTSP<DPTSA) decrease humid. Mixture in zone 2: IF ((TM>TSP) & (DPTM<DPTSP) ) cooling and humidifying Cool. coil cont.: IF (TSP<TSA) increase cooling or IF (TSP>TSA) decrease cooling Humidifier: IF (DPTSP>DPTSA) increase humidifying or IF (DPTSP<DPTSA) decrease hum. Mixture in zone 3: IF ((DPTM>DPTSP) ) cooling/dehumidifying and reheatin Cool. coil cont.: IF (DPTSP>DPTSA) increase cooling or IF (DPTSP<DPTSA) decrease cooling Heater control: IF (TSP>TSA) increase heating or IF (TSP<TSA) decrease heating