1 / 22

Applied Harmonics Control of Harmonics

Applied Harmonics Control of Harmonics. IEEE Standard 519-1992. Harmonic Distortion Evaluations. Limit harmonic current injections from end users so that harmonic voltage distortion is tolerable. Limit harmonic voltage (responsibility of utility). utility system. customer under study. PCC.

wilma
Télécharger la présentation

Applied Harmonics Control of Harmonics

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Applied HarmonicsControl of Harmonics

  2. IEEE Standard 519-1992 Harmonic Distortion Evaluations • Limit harmonic current injections from end users so that harmonic voltage distortion is tolerable. • Limit harmonic voltage (responsibility of utility).

  3. utility system customer under study PCC IL other customers utility system customer under study PCC IL other customers

  4. End users are limited at PCC in terms of • individual harmonic components and • total demand distortion • Utility is mainly responsible for limiting voltage distortion at PCC • Evaluations: • Measurement of currents injected by load (over one week period) • Calculation of frequency response of system impedances (using harmonic calculation software)

  5. Table 6.1 Harmonic voltage distortion limits in % of nominal fundamental- frequency voltage

  6. Table 6.2 Harmonic current limits

  7. Ih is rms magnitude of individual harmonic current • Isc is the short-circuit current at PCC • IL is the fundamental component of the maximum demand current (average max demand over 12 months) • Individual limits apply to odd-order harmonics, even order limits are at 25% of indicated value

  8. For power converters with more than 6 pulses, where q = pulse number, multiply limits in table 6.2 by

  9. Controlling harmonics • Control only when harmonics create a problem. Types of problems: • load harmonic currents are too large • path for harmonic currents is too long electrically (too much impedance) producing voltage distortion or communication-line interference • response of system magnifies one or more harmonics

  10. Options for control • Reduce magnitude of harmonic currents from load • Add filters to do one or more of these: • short out (siphon off) the harmonic • block harmonic currents from entering part of the system • supply the harmonics locally • Modify the frequency response of the system by filters or other means

  11. Reducing load harmonic current • Sometimes transformer connections can be changed, for example: • phase shift on some transformers supplying 6-pulse converters • delta windings block triplen currents • zig-zag transformers can supply triplens

  12. Zig-zag transformer

  13. Zig zag transformer • Place the transformer to supply balanced triplen harmonics (and any other zero-sequence currents) to load • This will unload zero sequence currents on circuits upstream of the ZZ transformer, with little or no effect downstream • Fault study results may be affected

  14. Placement of ZZ transformer a b c I3 n 3I3 Unloads the neutral conductor upstream

  15. Filtering • Shunt passive filter: short-circuit harmonic currents close to their source • Series passive filter: block harmonic currents from power delivery system (may cause large load voltage distortion) • Active shunt filter: electronically supply low-order harmonics to a nonlinear load (used with simple passive filters for higher frequency components).

  16. Passive Filters • Shunt passive filters are • notch filters, tuned to a specific harmonic frequency, or • high-pass filters high-pass filter notch filter

  17. Modifying system frequency response • Add a shunt filter to the system • Add a reactor (e.g., in series with a pf correction capacitor) to de-tune system • Change pf correction capacitor size or placement, or remove capacitor bank entirely

  18. Where to control harmonics • On utility system or end-user facility • utility system is more difficult to filter unless we can move or change the size of or reconnect a capacitor • end-user system may be easier to filter if we can access the feeder(s) where the harmonic currents are being produced

  19. Filters • In-line reactors (or chokes) for ASD • Isolation transformers can help • Isolation transformers can be reconnected with different phase shifts ASD M Xs Xt reactor 0-5% on ASD kVA

  20. Isolation transformers X~5% 480 V bus M ASD M ASD Approximates a 12-pulse converter with 6-pulse converters by putting half on Delta-Delta transformers and the half on Delta-Y. 12-pulse has Ih = 0 for h = 5, 7

  21. Harmonic studies • Perform harmonic studies when • a problem occurs, to find a solution • planning large capacitor bank installation on either utility or industrial system • planning installation of large nonlinear load such as adjustable speed motor drives (ASD) • designing a harmonic filter or converting a capacitor to a harmonic filter

More Related