An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Residential New Construction (NC):Slab InsulationUES Measure Update Regional Technical Forum March 18, 2014

  2. Current Category: Proven Current Status: Under Review Current Sunset Date: April 30, 2014 Reason for Update/Review: Response to recommendation memo; update with latest SEEM calibration Baseline Type: Current Practice Residential NC Slab Insulation: Measure Overview

  3. None Staff Highlighted Areas

  4. Recommendation memo updates made • Updated workbook to use latest ProCosttemplate • Updated workbook to include complete SEEM model inputs and outputs for each scenario investigated • Clarified measure definition as only applicable to Montana and Heating Zone 3 • Recalculated savings using the updated and calibrated SEEM Version 0.94 • Updated baseline inputs to reflect the latest Montana Energy Code • Removed extraneous SEEM runs from workbook Summary of Updates

  5. Recommendation memo updates not made directly in measure workbook • Documentation of SEEM calibration • This documentation is captured separately on RTF website • Documentation of all new construction SEEM inputs • Staff has created a centralized workbook with New Construction baseline assumptions • Slab insulation measure workbook contains detailed documentation of SEEM inputs relevant to the measure Summary of Updates (continued)

  6. If foundation is slab-on-grade, and slab is less than 12 inches below grade: • Code requires R-10 slab insulation on perimeter • Insulation needs to extend 4 ft by any combination of vertical and horizontal placement (see next slide for illustration)1 • If slab is greater than 12 inches below grade (e.g. full basement), no slab insulation is required Current Montana Code for Slab Insulation 1 Applies to slabs without in-floor heat. Heated slabs required R-15 slab insulation by MT code.

  7. Current Montana Code for Slab Insulation (continued) Slab-On-Grade Code Options Combination horizontal and vertical case Vertical case Horizontal case

  8. Current Montana Code for Slab Insulation (continued) Baseline and Efficient Cases Modeled

  9. Savings • For heated basements, savings changed by -30% to +50%, depending on HVAC system type • For slab-on-grade, savings changed by -60% to +5%, depending on HVAC system type • No change in incremental costs other than adjustment from 2008$ to 2006$ • All measures remain cost-effective Summary of Changes to Savings, Cost, and TRC

  10. “I _______________ move that the RTF: approve the Residential New Construction: Slab Insulation measure as a Proven UES; Set the measure status to ‘Active;’ and Set the sunset date to December 31, 2016.” Decision