Station Control System SINAUT ST7

Station Control System SINAUT ST7. Assembly guide & Configuration Help. Assembly of a TIM in a S7-300-Rack (1). The TIM module can be used in a S7-300 together with any S7-300 CPU with a partyline internal communication bus (K bus). These are: CPU 314 *) > 6ES7 314-1AE02-0AB0

duard
Télécharger la présentation

Station Control System SINAUT ST7

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Station Control System SINAUT ST7 Assembly guide & Configuration Help

  2. Assembly of a TIM in a S7-300-Rack (1) • The TIM module can be used in a S7-300 together with any S7-300 CPU with a partyline internal communication bus (K bus). These are: • CPU 314 *) > 6ES7 314-1AE02-0AB0 • CPU 314 IFM> 6ES7 314-5AE02-0AB0 • CPU 315> 6ES7 315-1AF01-0AB0 • CPU 315-2 DP *) > 6ES7 315-2AF01-0AB0 • CPU 316> 6ES7 316-1AG00-0AB0 • CPU 316-2 DP> 6ES7 316-2AG00-0AB0 The TIM can be inserted into any of the module racks 0 to 3, but only in the expansion racks 1 to 3 if these racks are connected with the CPU via the IM 360/IM 361 interface modules. All slots designed for SM, FM or CP can be used for the TIM. Every TIM is delivered with a bus connector. The TIM is connected to the module left of it via this bus connector. • And the new compact CPUs • CPU 313C > 6ES7 313-5BE00-0AB0 • CPU 313C-2PtP > 6ES7 313-6BE00-0AB0 • CPU 313C-2DP> 6ES7 313-6CE00-0AB0 • CPU 314C-2PtP> 6ES7 314-6BF00-0AB0 • CPU 314C-2DP> 6ES7 314-6CF00-0AB0 *) The new standard CPUs 314/315, available since 10.2002, are released for SINAUT ST7 too.

  3. Assembly of a TIM in a S7-300-Rack (2) • One of the following C7 Control Systems may be used as well instead of a S7-300 CPU: • C7-633/P> 6ES7 633-1DF00-0AE3 • C7-633 DP> 6ES7 633-2BF00-0AE3 • C7-634/P> 6ES7 634-1DF00-0AE3 • C7-634 DP> 6ES7 634-2BF00-0AE3 • C7-626/P> 6ES7 626-1DG02-0AE3 • C7-626/P DP > 6ES7 626-2DG02-0AE3 The TIM can be inserted into any of the expansion racks 1 to 3. These racks are connected to the C7 unit via the IM 360 and IM 361 interface modules (the IM360 is already integrated in the C7 unit). All slots designed for SM, FM or CP can be used for the TIM. Every TIM is delivered with a bus connector. The TIM is connected to the module left of it via this bus connector.

  4. TIM 3 S7-300 WAN S7-300 with one WAN connection The simplest configuration: One SIMATIC S7-300 with one TIM 3 on the partyline, with one WAN connection via the modem integrated in the TIM.

  5. Cable 7701 S7-300 TIM 4 MDx WAN (1) WAN (2) Cable 7701 S7-300 TIM 4 MDx WAN (1) WAN (2) S7-300 with two WAN conections An external modem MD is connected to a TIM via a standard type 7701 cable. The modem can be inserted on a separate S7-300 mounting rail or on a 35 mm standard mounting rail (a suitable adapter is available). The illustration to the left shows such a configuration. The illustration to the left shows a configu-ration where the modem is positioned to the far right in module rack 0. The TIM and modem are placed directly adjacent to one another to provide a better overview.The TIM is connected to the module directly left of it via a bus connector. There is no bus connector between the TIM and the modem.

  6. further expansion racks1 ... 3 S7-300 TIM 4 TIM 4 TIM 4 TIM 4 WAN (2) WAN (3) WAN (4) WAN (1) Cable 7701 MDx MDx MDx MDx WAN (5) WAN (8) WAN (6) WAN (7) Maximum configuration of an S7-300 Depending on the available connection resources up to four TIMs can be inserted to the CPUs 314 to 316. When TIM 4 modules with internal modems are used here and the other four external modem connections are also used, this allows the connection of a total of 8 WANs. The illustration shows such a maximum configuration. However, the actual limitation results from the available working memory in the CPU for user programs, because the greater the network, the greater the memory demands will be for the specific telecontrol user program.

  7. CPU 412-1> 6ES7 412-1XF00-0AB0 (Version 02) • CPU 412-2> 6ES7 412-2XG00-0AB0 (Version 01) • CPU 413-1> 6ES7 413-1XG00-0AB0 (Version 02) • CPU 413-2> 6ES7 413-2XG00-0AB0 (Version 03) • CPU 414-1> 6ES7 414-1XG00-0AB0 (Version 02) • CPU 414-2 > 6ES7 414-2XG00-0AB0 (Version 03) 6ES7 414-2XJ00-0AB0 (Version 01) • CPU 414-3 1)> 6ES7 414-3XJ00-0AB0 (Version 01) • CPU 416-1> 6ES7 416-1XJ00-0AB0 (Version 02) • CPU 416-2 > 6ES7 416-2XK00-0AB0 (Version 01) 6ES7 416-2XL00-0AB0 (Version 01) • CPU 416-3> 6ES7 416-3XL00-0AB0 (Version 01) • CPU 417-4 1)> 6ES7 417-4XL00-0AB0 (Version 01) Assembly of a seperate TIM rack Only TIM 4 type modules can be used together with an S7-400. The TIM is mounted on a separate S7-300 mounting rail (TIM rack) and connected with the S7-400 CPU via its MPI port. All currently available multi-instance capable S7-400 CPUs can be used. The CPU 318-2DP also can only be connected to a TIM via its MPI port, i.e. to a TIM 4 1) Redundant SINAUT solutions based on CPU 414-4H or CPU 417-4H are not possible!

  8. S7-400 TIM 4 MPI-Bus WAN S7-400 with one WAN connection • The simplest configuration: • One SIMATIC S7-400 with one TIM 4 on the MPI-Bus, • with one WAN connection via the modem integrated in the TIM. • The TIM is mounted on a separate S7-300 mounting rail.

  9. S7-400 Cable 7701 TIM 4 MDx MPI-Bus WAN (2) WAN (1) S7-400 with two WAN connections If two WAN connections are required, another external modem can be connected to the TIM 4, for example, a SINAUT ST7 modem. The TIM and the external modem are mounted together on a separate S7-300 mounting rail. The TIM is connected with the CPU via its MPI port. The connection between the TIM and the external MDx modem is made via the standard type 7701 cable.

  10. S7-400 S7-300 TIM 4 MPI-Bus WAN S7-300 and S7-400 with a shared WAN connection As a TIM 4 can communicate not only with one but several CPUs via MPI, regardless of whether they are type S7-400 or S7-300 CPUs, a SINAUT station might also be configu-rated as shown in the illustra-tion. The TIM provides access to the WAN for both the S7-400 and the S7-300. This could be a larger station in which the automation tasks are distributed to several PLCs.

  11. MDx MDx MDx MDx S7-400 WAN (5) WAN (6) WAN (7) WAN (8) Cable 7701 TIM 4 TIM 4 TIM 4 TIM 4 MPI-Bus WAN (1) WAN (2) WAN (3) WAN (4) S7-400 with several WAN connections The illustration shows a larger configuration with four TIM 4 and a total of 8 WAN connec-tions. This could be a control center. The maximum number of TIMs that can be connected through MPI to a S7-400 depends on the connection resources that the CPU has available. However, the working memory of the CPU must also be taken into consideration, because the greater the network, the greater the memory demands for the specific telecontrol user program.

  12. SINAUT ST7cc TIM 4 MPI-Bus WAN SINAUT ST7cc with one WAN connection Via its MPI interface a TIM4 can be connected not only to S7-400 or S7-400 CPUs, but also to the Control Center System SINAUT ST7cc. The picture shows the simplest configuration for a Control Center System SINAUT ST7cc with one WAN connection.

  13. SINAUT ST7cc Steckl. 7701 MDx TIM 4 MPI-Bus WAN (2) WAN (1) SINAUT ST7cc with two WAN connections Similar to an S7-400 a SINAUT ST7cc can be equipped with two WAN connections (see picture). The maximum number of TIM4 modules which can be connected to an ST7cc depends on the communication adapter that is used in ST7cc. For instance, together with the Softnet S7 driver the CP5611 allows the connection of upto eight TIM4, meaning a total of 16 WAN connections.

  14. S7-400 SINAUT ST7cc TIM 4 MPI-Bus WAN ST7cc and S7-400 with a shared WAN connection In addition to the SINAUT ST7cc a local controller, for instance an S7-400, may be connected to the MPI, also running data communication with the telecontrol stations. The TIM provides access to the WAN for both the S7-400 and the ST7cc. The TIM will pass received data to both units in parallel and will send data which either comes from ST7cc or S7-400 to the outstations. For instance, this could be a control center where, apart from the ST7cc, the S7-400 executes central automation tasks and/or controls a display panel or desk.

  15. SINAUT ST7 Configuration Assistance • System Environment TIM 3 • System Environment TIM 4

  16. RS232/RS485 Cable 7701 S7-300 RS232 CPU *) TIM 3 MDx RS485 WAN Connection TIM 3 types with integrated modem TIM 32 6NH7800-3AA20 TIM 32D 6NH7800-3AD20 TIM 33 6NH7800-3AA30 TIM 33D 6NH7800-3AD30 TIM 34 6NH7800-3AA40 TIM 34D 6NH7800-3AD40 TIM 3 x D D = Optional DCF77 radio clock integrated 2 = Dedicated line modem MD2 integrated 3 = Analog telephone modem MD3 integrated 4 = Digital ISDN modem MD4 integrated *) possible S7-300 CPUs: 313C 315 314 316 314 IFM 314C TIM 3 types withoutintegrated modem TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 3 V D D = Optional DCF77 radio clock integrated V = without integrated modem but with one combined RS232/485 interface System Environment TIM 3 (1)In combination with an S7-300 CPU TIM 3 with integrated modem TIM 3 without integrated modem S7-300 RS232 CPU *) TIM 3 RS485 WAN-Anschluss MDx: External modem (e.g. MD1, MD2, MD3, MD4) or other external transmission device (e.g. FO module, GSM-Kit, radio device) Important: TIM 3 can not be combined with CPU 318! CPU 318 needs a TIM 4 which is connected via MPI.

  17. RS232 TIM 3 MDx IM 361 IM 361 TIM 3 RS485 WAN connection TIM 3 types with integrated modem TIM 32 6NH7800-3AA20 TIM 32D 6NH7800-3AD20 TIM 33 6NH7800-3AA30 TIM 33D 6NH7800-3AD30 TIM 34 6NH7800-3AA40 TIM 34D 6NH7800-3AD40 TIM 3 x D D = Optional DCF77 radio clock integrated 2 = Dedicated line modem MD2 integrated 3 = Analog telephone modem MD3 integrated 4 = Digital ISDN modem MD4 integrated TIM 3 types withoutintegrated modem TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 3 V D D = Optional DCF77 radio clock integrated V = without integrated modem but with one combined RS232/485 interface Systemumgebung TIM 3 (2)In combination with a C7 Control System TIM 3 with integrated modem TIM 3 without integrated modem RS232/RS485 Cable 7701 C7-633, 634, 626 C7-633, 634, 626 WAN connection MDx: External modem (e.g. MD1, MD2, MD3, MD4) or other external transmission device (e.g. FO module, GSM-Kit, radio device) Important : TIM 3 can not be combined with C7-621, 621 ASi! C7-621, 621 ASi need a TIM 4 which is connected via MPI.

  18. TIM 4 types withoutintegrated modem TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 TIM 4 x D D = Optional DCF77 radio clock integrated 2 = Dedicated line modem MD2 integrated 3 = Analog telephone modem MD3 integrated 4 = Digital ISDN modem MD4 integrated V = without integrated modem but with one combined RS232/485 interface R = without integrated modem but with two combined RS232/485 interfaces MDx TIM 4 *) mögliche S7-300 CPUs: 313C 315 314 316 314 IFM 318 314C System Environment TIM 4 (1)Via MPI bus connected to one or several S7-400 / S7-300 TIM 4 types with integrated modem TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 S7-400 Cable 7701 RS232 S7-300 RS232/485 CPU *) MPI MPI bus RS485 WAN connection (2) WAN connection (1) Optional MDx:External modem (e.g. MD1, MD2, MD3, MD4) or other external transmission device (e.g. FO module, GSM-Kit, radio device) Important: WAN connection (1) is not available in TIM 4V / 4VD. Note: More TIM 4 can be connected via MPI when required.

  19. TIM 4 types withoutintegrated modem TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 TIM 4 x D D = Optional DCF77 radio clock integrated 2 = Dedicated line modem MD2 integrated 3 = Analog telephone modem MD3 integrated 4 = Digital ISDN modem MD4 integrated V = without integrated modem but with one combined RS232/485 interface R = without integrated modem but with two combined RS232/485 interfaces MDx TIM 4 System Environment TIM 4 (2)Via MPI bus connected to a C7 Control System TIM 4 types with integrated modem TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 C7-633, 634, 626 Cable 7701 RS232 RS232/485 MPI MPI bus RS485 WAN connection (2) WAN connection (1) Optional MDx:External modem (e.g. MD1, MD2, MD3, MD4) or other external transmission device (e.g. FO module, GSM-Kit, radio device) Important: WAN connection (1) is not available in TIM 4V / 4VD. Note: More TIM 4 can be connected via MPI when required.

  20. CPU *) TIM 4 MDx TIM 4 types withoutintegrated modem TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 TIM 4 x D D = Optional DCF77 radio clock integrated 2 = Dedicated line modem MD2 integrated 3 = Analog telephone modem MD3 integrated 4 = Digital ISDN modem MD4 integrated V = without integrated modem but with one combined RS232/485 interface R = without integrated modem but with two combined RS232/485 interfaces *) mögliche S7-300 CPUs: 313C 315 314 316 314 IFM 314C System Environment TIM 4 (3)Build in S7-300 rack as CP (in combination with a S7-300 CPU) TIM 4 types with integrated modem TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 Cable 7701 RS232/RS485 S7-300 RS232 RS485 (MPI) WAN- connection (1) WAN- connection (2) Optional MDx:External modem (e.g. MD1, MD2, MD3, MD4) or other external transmission device (e.g. FO module, GSM-Kit, radio device) Important: WAN connection (1) is not available in TIM 4V / 4VD. Note: MPI connector of the TIM is without any function when TIM 4 is build in S7-300 rack as CP. Note: More TIM 4 can be build in the S7-300 rack as CP when required.

  21. TIM 4 MDx IM 361 TIM 4 types withoutintegrated modem TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 TIM 4 x D D = Optional DCF77 radio clock integrated 2 = Dedicated line modem MD2 integrated 3 = Analog telephone modem MD3 integrated 4 = Digital ISDN modem MD4 integrated V = without integrated modem but with one combined RS232/485 interface R = without integrated modem but with two combined RS232/485 interfaces (MPI) WAN- connection (1) WAN- connection (2) System Environment TIM 4 (4)Build in S7-300 rack as CP (in combination with a C7 Control System) TIM 4 types with integrated modem TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 Cable 7701 RS232/RS485 RS232 RS485 C7-633, 634, 626 Optional MDx:External modem (e.g. MD1, MD2, MD3, MD4) or other external transmission device (e.g. FO module, GSM-Kit, radio device) Important: WAN connection (1) is not available in TIM 4V / 4VD. Note: MPI connector of the TIM is without any function when TIM 4 is build in S7-300 rack as CP. Note: More TIM 4 can be build in the S7-300 rack as CP when required.

  22. SINAUT ST7 Configuration Assistance • SINAUT ST7 - Software • SINAUT ST7cc • Connection to DCF77/GPS Radio Clock

  23. SINAUT ST7 Software Software for PG/PC STEP7 V4.02 see SIMATIC Catalog SINAUT Configuration Software < V2.2 runs under STEP7 V4.02 and V5.0orSTEP7 V5.0 see SIMATIC Catalog orSTEP7 V5.1 see SIMATIC CatalogSINAUT Configuration Software > V3.0 needs STEP7 V5.1, for PG-Routing STEP7 V5.1, SP2 or later must be installed SW ST7 6NH7997-0CA15-0AA0 SINAUT ST7 Software package consisting of (current version: 3.2) • SINAUT TD7 Library (CPU blocks)• SINAUT ST7 Configuration and Diagnostics software for the PG• SINAUT ST7 Software for the TIM Manuals for the ST7-Software MANUAL ST7 D 6NH7998-0AA13 (german) MANUAL ST7 E 6NH7998-0AA23 (english)

  24. MPI TIM 4 SINAUT ST7cc, Single System Software for PC Windows NT 4.0 / 2000 see SIMATIC Catalog WinCC Complete Package see SIMATIC Catalog Runtime package possible if there is no need for project configuration on the end-user PC SW ST7cc S 6NH7997-7CA15-0AA1 Max. 6 stations or Licence ext. possible SW ST7cc M 6NH7997-7CA15-0AA2 Max. 12 stations or Licence ext. possible SW ST7cc L 6NH7997-7CA15-0AA3 More than 12 stations Manuals for the ST7cc Software MANUAL ST7cc D 6NH7998-7AA11 (german) MANUAL ST7cc E 6NH7998-7AA21 (english) MPI Connection CP5613 with SIMATIC NET see SIMATIC Catalog max. 30 TIMs at the MPI of ST7cc PC-Software > V6.0 or CP5x11 with SIMATIC NET see SIMATIC Catalog max. 8 TIMs at the MPI of ST7cc PC-Software > V6.0 Minimum Layout for TIM 4 Rack 300er Rail see SIMATIC Catalog PS 24 V DC see SIMATIC Catalog TIM 4x 6NH7800-4ADx0 (min. one TIM with DCF receiver) MPI Cable PC  TIM see SIMATIC Catalog Additionally required for ST7 Project(s) SW ST7 6NH7997-0CA15-0AA0 SINAUT ST7 Software package ST7cc Control Center MPI-Bus more TIM 4 PS TIM 4 MPI DCF77 or GPS MPI-Bus

  25. Ethernet bus MPI MPI MPI-Bus more TIM 4 PS TIM 4 TIM 4 MPI DCF77 or GPS MPI-Bus SINAUT ST7cc Redundant Redundant ST7cc Control Center Software for PC 2 x Windows NT 4.0 / 2000 see SIMATIC Catalog WinCC Complete Package see SIMATIC Catalog Runtime package possible if there is no need for project confi- guration on the end- user PC WinCC Runtime Package see SIMATIC Catalog WinCC Redundancy Pack. see SIMATIC Catalog Contains 2 licences ST7cc Redundancy Licence 6NH7997-8CA15-0AA0 Contains 2 licences 2 x SW ST7cc S 6NH7997-7CA15-0AA1 Max. 6 stations or Licence ext. possible 2 x SW ST7cc M 6NH7997-7CA15-0AA2 Max. 12 stations or Licence ext. possible 2 x SW ST7cc L 6NH7997-7CA15-0AA3 More than 12 stations Manuals for the ST7cc Software (see SINAUT ST7cc Single System) MPI Connection (see SINAUT ST7cc Single System) Minimum Layout for TIM 4 Rack (see SINAUT ST7cc Single System; at present no redundant TIMs possible!) Additionally required for ST7 Project(s) (see SINAUT ST7cc Single System)

  26. TIM with DCF77 receiver module TIM TIM 3VD 6NH7800-3AD00 TIM 32D 6NH7800-3AD20 TIM 33D 6NH7800-3AD30 TIM 34D 6NH7800-3AD40 TIM 4VD 6NH7800-4AD00 TIM 42D 6NH7800-4AD20 TIM 43D 6NH7800-4AD30 TIM 44D 6NH7800-4AD40 TIM 4RD 6NH7800-4AD90 Connection to DCF77 Radio Clock Indoor antenna incl. 10m antenna cable DCF INANT 6NH9831-0AA or Adapter cable (1,5m) will be supplied with TIM (spare part order no. 6NH7700-0AD15) Outdoor antenna incl. 20m antenna cable DCF AUTANT-D Flatroof or wall mounting 6NH9831-0BA DCF AUTANT-M Mast mounting 6NH9831-0DA BNC DCF IND-BS 6NH9831-2AA Indirect lightning protection

  27. TIM with DCF77 receiver module TIM TIM 3VD 6NH7800-3AD00 TIM 32D 6NH7800-3AD20 TIM 33D 6NH7800-3AD30 TIM 34D 6NH7800-3AD40 TIM 4VD 6NH7800-4AD00 TIM 42D 6NH7800-4AD20 TIM 43D 6NH7800-4AD30 TIM 44D 6NH7800-4AD40 TIM 4RD 6NH7800-4AD90 • • Connection to GPS Radio Clock GPS receiver module Output DCF77 simulation signal Input GPS signal BNCadapterconnecter BNC Indirect lightning protection GPSoutdoor antenna for wall or mast moutingincl. 25m antenna cable Adapter cable (1,5m) will be supplied with TIM (spare part order no. 6NH7700-0AD15) GPS IND-BS 6NH9831-8LA • GPS-Kit • 6NH9831-8AA • GPS all-in package to simulate • the DCF77 time signal, consisting of: • GPS receiver module • GPS outdoor antenna incl. 25 m cable • BNC adapter connector • Configuration software • PC adapter cable • Documentation

  28. Connection to Dedicated Lines Copper Cables Private Cables PTT Leased Lines Fibre Optic Cable Private Radio Systems Omnidirectional Radio optionally with Directional Radio time slotmethod Spread Spectrum Radio Mixed Networks SINAUT ST7 Configuration Assistance

  29. TIM with integrated modem MD2 External modem MD2 TIM with RS232 interface 6NH7810-0AA20 TIM TIM 32 6NH7800-3AA20 TIM 32D 6NH7800-3AD20 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 LTOP1 LTOP1 Connection to Dedicated Lines (Copper Cable) Point-to-Point Connection with MD2, 2-wire half-duplex Connection cable (1,5m) 6NH7701-4AL Master-TIM Station-TIM RS232 RS232 TIM MD2 or Connection cable (6m) MD2  LTOP will be supplied with TIM (spare part order no. 6NH7700-2AR60) Connection cable (6m) MD2  LTOP will be supplied with MD2 (spare part order no. 6NH7700-2AR60) Overvoltage protection 6NH9821-0BC11 6NH9821-0BC11 Terminal point 2-wire dedicated line Terminal point

  30. TIM with integrated modem MD2 TIM with RS232 interface TIM TIM 32 6NH7800-3AA20 TIM 32D 6NH7800-3AD20 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 External modem MD2 6NH7810-0AA20 LTOP2 LTOP2 Connection to Dedicated Lines (Copper Cable) Point-to-Point Connection with MD2, 4-wire duplex Connection cable (1,5m) 6NH7701-4AL Master-TIM Station-TIM RS232 RS232 TIM MD2 or Connection cable (6m) MD2  LTOP will be supplied with TIM (spare part order no. 6NH7700-2AR60) Connection cable (6m) MD2  LTOP will be supplied with MD2 (spare part order no. 6NH7700-2AR60) Overvoltage protection 6NH9821-0BC12 6NH9821-0BC12 4-wire dedicated line Terminal point Terminal point

  31. TIM with integrated modem MD2 TIM with RS232 interface TIM TIM 32 6NH7800-3AA20 TIM 32D 6NH7800-3AD20 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 External modem MD2 6NH7810-0AA20 LTOP2 LTOP1 LTOP1 Connection to Dedicated Lines (Copper Cable) Multi-drop Line Connection with MD2, 2-wire half-duplex Connection cable (1,5m) 6NH7701-4AL Master-TIM Station-TIM RS232 RS232 TIM MD2 or Connection cable ( 6m) MD2  LTOP will be supplied with TIM (spare part order no.6NH7700-2AR60) Connection cable ( 6m) MD2  LTOP will be supplied with MD2 (spare part order no. 6NH7700-2AR60) Station-TIM Overvoltage protection 6NH9821-0BC11 6NH9821-0BC12 6NH9821-0BC11 2-wire dedicated line 2-wire dedicated line Terminal point Terminal point Tapping-in point

  32. TIM with integrated modem MD2 TIM with RS232 interface TIM TIM 32 6NH7800-3AA20 TIM 32D 6NH7800-3AD20 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 External modem MD2 LTOP2 LTOP2 6NH7810-0AA20 LTOP2 LTOP2 Connection to Dedicated Lines (Copper Cable) Multi-drop Line Connection with MD2, 4-wire duplex Connection cable (1,5m) 6NH7701-4AL Master-TIM Station-TIM RS232 RS232 TIM MD2 or Connection cable ( 6m) MD2  LTOP will be supplied with TIM (spare part order no. 6NH7700-2AR60) Connection cable ( 6m) MD2  LTOP will be supplied with MD2 (spare part order no. 6NH7700-2AR60) Station-TIM Overvoltage protection 6NH9821-0BC12 2x 6NH9821-0BC12 6NH9821-0BC12 4-wire dedicated line 4-wire dedicated line Terminal point Terminal point Tapping-in point

  33. TIM with integrated modem MD2 TIM TIM 32 6NH7800-3AA20 TIM 32D 6NH7800-3AD20 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 LTOP2 LTOP1 LTOP1 Connection to Dedicated Lines (Copper Cable) Repeater in Multi-drop Line and Point-to-Point Connections with MD2, 2-wire Connection cable (0,3m) 6NH7701-1CB Repeater configuredwith 2 x MD2 6NH7810-0AA20 Station-TIM RS232 RS232 MD2 MD2 Connection cable ( 6m) MD2  LTOP will be supplied with TIM (spare part order no. 6NH7700-2AR60) 2 x Connection cable ( 6m) MD2  LTOP will be supplied with MD2 (spare part order no. 6NH7700-2AR60) Overvoltage protection 6NH9821-0BC12 6NH9821-0BC11 6NH9821-0BC11 2-wire dedicated line 2-wire dedicated line Tapping-in point

  34. TIM with integrated modem MD2 TIM TIM 32 6NH7800-3AA20 TIM 32D 6NH7800-3AD20 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 RS232 MD2 LTOP2 Overvoltage protection 6NH9821-0BC12 6NH9821-0BC12 6NH9821-0BC12 4-wire dedicated line 4-wire dedicated line Tapping-in point LTOP2 LTOP2 Connection to Dedicated Lines (Copper Cable) Repeater in Multi-drop Line and Point-to-Point Connections with MD2, 4-wire Connection cable (0,3m) 6NH7701-1CB Repeater configuredwith2 x MD2 6NH7810-0AA20 Station-TIM RS232 MD2 Connection cable ( 6m) MD2  LTOP will be supplied with TIM (spare part order no. 6NH7700-2AR60) 2 x Connection cable ( 6m) MD2  LTOP will be supplied with MD2 (spare part order no. 6NH7700-2AR60)

  35. TIM with RS232 interface TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 RS232 TIM External modem MD3 External modem MD3 6NH7810-0AA30 (Hardware version > 4) 6NH7810-0AA30 (Hardware version > 4) LTOP1 LTOP1 Connection to Dedicated Lines (Copper Cable)Point-to-Point Connection with MD3 1) up to 33.600 bit/s 2-wire duplex (Voiceband) Connection cable (1,5m) 6NH7701-4AL Connection cable (1,5m) 6NH7701-4AL Master-TIM Station-TIM TIM with RS 232interface RS232 RS232 RS232 MD3 TIM MD3 Connection cable ( 6m) MD3  LTOP will be supplied with MD3 (spare part order no. 6NH7700-3BR60) Connection cable ( 6m) MD3  LTOP will be supplied with MD3 (spare part order no. 6NH7700-3BR60) Overvoltage protection 6NH9821-0BC11 6NH9821-0BC11 2-wire dedicated line Terminal point Terminal point 1) MD3 on dedicated line only possible with version 4 or higher (no multi-drop possible)

  36. External modem MD2 TIM with RS485 interface MD2 n x 6NH7810-0AA20 TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 RS485 RS485 TIM MD2 MD2 RS485 RS485 6NH9821-0BC12 2-wire dedicated line(1st line) 2-wire dedicated line (2nd line) LTOP2 LTOP2 LTOP1 Connection to Dedicated Lines (Copper Cable) Star Network with MD2, 2-wire halfduplex or 4-wire duplex Master-TIM Important: Terminating resistor must be set on last connector! 1 x Connectioncable (1,5m) 6NH7701-4DL Connector n-1 x 6ES7 972-0BA11-0XA0 Connector + cable required to connect every further modem MD2 Connection cable ( 6m) MD2  LTOP will be supplied with MD2 (spare part order no. 6NH7700-2AR60) Cable n-1 x 6XV1 830-0AH10 Overvoltage protection 6NH9821-0BC11 6NH9821-0BC12 2-wire dedicated line 4-wire dedicated line

  37. External modem MD3 TIM with RS485 interface MD3 n x 6NH7810-0AA30 (Hardware version > 4) TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 RS485 RS485 TIM MD3 MD3 RS485 RS485 2-wire dedicated line 2-wire dedicated line 2-wire dedicated line LTOP1 LTOP1 LTOP1 Connection to Dedicated Lines (Copper Cable) Star Network with MD3, up to 33.600 bit/s 2-wire duplex (Voiceband) Master-TIM Important: Terminating resistor must be set on last connector! 1 x Connectioncable (1,5m) 6NH7701-4DL Connector n-1 x 6ES7 972-0BA11-0XA0 Connector + cable required to connect every further modem MD3 Connection cable ( 6m) MD3  LTOP will be supplied with MD3 (spare part order no. 6NH7700-3BR60) Cable n-1 x 6XV1 830-0AH10 Overvoltage protection 6NH9821-0BC11 6NH9821-0BC11 6NH9821-0BC11

  38. TIM with integrated modem MD2 TIM with RS232 interface RS232 TIM TIM TIM 32 6NH7800-3AA20 TIM 32D 6NH7800-3AD20 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 External modem MD2 Connection to4-fold transformerrequires adaptation 6NH7810-0AA20 600 4 x 600 Attenuation 6,5 dB LTOP2 LTOP2 LTOP2 LTOP2 Connection to Dedicated Lines (Copper Cable) Star Network with MD2 and 4-fold line transformer, 2-wire half-duplex Master-TIM Connection cable (1,5m) 6NH7701-4AL or Master-TIM RS232 MD2 Connection cable ( 6m) MD2  LTOP will be supplied with TIM (spare part order no. 6NH7700-2AR60) Connection cable ( 6m) MD2  LTOP will be supplied with MD2 (spare part order no. 6NH7700-2AR60) Connection to4-fold line transformerrequires adaptation 4-fold Transformer 6NH9821-4GA Important: only for transmissionin voiceband, i.e. max.1200 or 2400 bps 600 4 x 600 Attenuation 6,5 dB 4-fold Transformer 6NH9821-4GA Important: only for transmissionin voiceband, i.e. max.1200 or 2400 bps Important: Not used outputs must be terminated with 600! Overvoltage protection Overvoltage protection 6NH9821-0BC12 6NH9821-0BC12 6NH9821-0BC12 6NH9821-0BC12 4 x 2-wire dedicated line 1st 2nd line 3rd 4th line 4 x 2-wire dedicated line 1st 2nd 3rd 4th

  39. TIM with RS485 interface TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 FO transmission line (2 fibers) FO transmission line (2 fibers) FO transmission line (2 fibers) Connection to Dedicated Lines Fiber Optic Cable RSM - S Note: TheOptical Link Modules (OLM) offered for PROFIBUS are not suitable for data transmission with the TIM! RS485 RSM-S optical link module with F-SMA fiber-optic cable connector for S980/1000 plastic fibers HIR-943291001 Technical Data: Wavelength : 665 nm Range : 50m / 164 ft Note: With the RSM modules transmission speeds of 9600 and 19200 bps can be used. Master-or Station-TIM or RSM - G RS485 RSM-G optical link module with BFOC fiber-optic cable connector for G50/125 and G62.5/125 glass fibers HIR-943290021 RS485 TIM Technical Data: Wavelength : 850 nm Range : G50/125  2.0 km / 1.25 miles G62.5/125  2.8 km / 1.75 miles Connection cable (1,5m) 6NH7701-4DL or RSM - E RS485 RSM-E optical link module with BFOC fiber-optic cable connector for G50/125, G62.5/125 and E10/125 glass fibers HIR-943405021 Technical Data: Wavelength : 1300 nm Range : G50/125  14 km / 8.75 miles G62.5/125  9.3 km / 5.8 miles E10/125  20 km / 12.5 miles Important: The RSM modules will only work with the individual listed fiber types.Data transmision is not possible via a better fiber quality!

  40. TIM with integrated modem MD2 TIM with RS232 interface RS232 TIM TIM TIM 32 6NH7800-3AA20 TIM 32D 6NH7800-3AD20 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 External modem MD2 Connection cable (6m) MD2  LTOP will be supplied with TIM (spare part order no. 6NH7700-2AR60) Connection to LF input requires adaptation 6NH7810-0AA20 Radio device Radio device LF input LF input Connection to Dedicated Lines Private Radio (1) Connection cable (1,5m) 6NH7701-4AL Master-TIM Station-TIM or RS232 MD2 Connection cable ( 6m) MD2  LTOP will be supplied with MD2 (spare part order no. 6NH7700-2AR60) Connection to LF input requires adaptation Private radio network Omnidirectional Radio Directional Radio Note: Omnidirectional and directional radio systems are in principle suitable for data transmission using the time slot methode. e.g. Motorola GM 350, GM 950

  41. RS232 RS232 TIM TIM Connection to Dedicated Lines Private Radio (2) TIM with RS232 interface Master-TIM Station-TIM TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 TIM with RS232interface Omnidirectional Radio Directional Radio Private radio network Connection cable (2,5m) 6NH7701-4BN (requires adaptation to RS232 interfaceof radio device) or Connection cable (2,5m) 6NH7701-5AN (see next page)for radio devices withstandard RS232 Connection cable (2,5m) 6NH7701-4BN (requires adaptation to RS232 interfaceof radio device) or Connection cable (2,5m) 6NH7701-5AN (see next page)for radio devices withstandard RS232 Radio device Radio device Note: Omnidirectional and directional radio systems are in principle suitable for data transmission using the time slot methode. e.g. Bosch MR11 SD-R DataRadio T-96SR Satel Satelline 2ASxE RS232 RS232

  42. RS232 RS232 TIM TIM Connection to Dedicated Lines Private Radio (3) TIM with RS232 interface Master-TIM Station-TIM TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 TIM with RS232interface Spread Spectrum radio Private radio network Connection cable (2,5m) 6NH7701-5AN for radio devices withstandard RS232 (e.g. with Data Radio) oder Connection cable (2,5m) 6NH7701-4BN (see page above;requires adaptation to RS232 interfaceof radio device) Connection cable (2,5m) 6NH7701-5AN for radio devices withstandard RS232 (e.g. with Data Radio) oder Connection cable (2,5m) 6NH7701-4BN (see page above;requires adaptation to RS232 interfaceof radio device) Radio device Radio device Note: Spread spectrum radio systems are in principle not suitable for data transmission using the time slot methode. e.g. Data-Linc SRM 6000Data-Linc SRM 6100 RS232 RS232

  43. Connection to Dial-up Networks Fixed Networks Analog Telephone Network ISDN Mobile Radio GSM (900 and 1800 MHz) Short Message Service (SMS) SINAUT ST7 Configuration Assistance

  44. TIM with RS232 interface RS232 TIM with integrated modem MD3 TIM TIM TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 TIM 33 6NH7800-3AA30 TIM 33D 6NH7800-3AD30 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 External modem MD3 6NH7810-0AA30 TAE6 TAE6 Connection to Dial-up NetworksFixed Network: Analog Telephone Network Connection cable (1,5m) 6NH7701-4AL Master-or Station-TIM Master-or Station-TIM or RS232 MD3 Connection cable ( 6m) MD3  TAE6N will be supplied with TIM (spare part order no. 6NH7700-3BR60) Telephone network (plug for Germany) (plug for Germany) Connection cable ( 6m) MD3  TAE6N will be supplied with MD3 (spare part order no. 6NH7700-3BR60) Telephone socket *) Telephone socket *) RJ12 RJ12 *) at best with overvoltage protection, e.g. from Phoenix or Dehn (both Germany)

  45. TIM with RS232 interface RS232 TIM with integrated modem MD4 TIM TIM TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 TIM 34 6NH7800-3AA40 TIM 34D 6NH7800-3AD40 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 External modem MD4 6NH7810-0AA40 ISDNnetwork Connection to Dial-up NetworksFixed Network: ISDN Connection cable (1,5m) 6NH7701-4AL Master-or Station-TIM Master-or Station-TIM or RS232 MD4 Connection cable ( 6m) MD4  S0 will be supplied with TIM (spare part order no. 6NH7700-4AR60) Connection cable ( 6m) MD4  S0 will be supplied with MD4 (spare part order no. 6NH7700-4AR60) RJ45 RJ45 ISDN socket (S0) *) ISDN- socket(S0) *) *) at best with overvoltage protection, e.g. from Phoenix or Dehn (both Germany)

  46. TIM with RS232 interface RS232 RS232 TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 TIM TIM TC35 TC35 GSM-network 24 V 24 V GSM-Kit TC35 with antenna GSM-Kit TC35 with antenna 6NH9840-3DB35 6NH9840-3DB35 Antenna cable (5m) GSM Kit  antenna,antenna and 24V cablewill be supplied with kit Antenna cable (5m) GSM Kit  antenna,antenna and 24V cablewill be supplied with kit Connection to Dial-up NetworksMobile Network: GSM Network (900 and 1800 MHz) Master-or Station-TIM Master-or Station-TIM Connection cable (2,5m) 6NH7701-5AN Connection cable (2,5m) 6NH7701-5AN TIM with RS232interface Important: For each GSM module a SIM card is required that is activated for data transmission Note: The TC35 GSM module is suitable for 900 and 1800 MHz. The former M20 GSM module is only suitable for the 900 MHz network.

  47. TIM TIM with integrated modem MD3 or MD4 ISDNnetwork TIM 33 6NH7800-3AA30 TIM 33D 6NH7800-3AD30 TIM 34 6NH7800-3AA40 TIM 34D 6NH7800-3AD40 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 Short Message Service (SMS) Telephone network GSM mobilephone TAE6 Connection to Dial-up NetworksShort Message Service (SMS) , Access via Fixed Network (1) Master-or Station-TIM Connection cable ( 6m) MD4  S0 will be supplied with TIM (spare part order no. 6NH7700-4AR60) RJ45 (for TIM with MD4) ISDN socket (S0) *) (for TIMwith MD3) Connection cable ( 6m) MD3  TAE6N will be supplied with TIM (spare part order no. 6NH7700-3BR60) SMS Center (plug for Germany) Telephone socket *) RJ12 *) at best with overvoltage protection, e.g. from Phoenix or Dehn (both Germany)

  48. TIM with RS232 interface RS232 TIM TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 External modem MD3 or External modem MD4 6NH7810-0AA30 ISDNnetwork 6NH7810-0AA40 Short Message Service (SMS) TAE6 Telephonenetwork GSM mobilephone Connection to Dial-up NetworksShort Message Service (SMS), Access via Fixed Network (2) Connection cable (1,5m) 6NH7701-4AL Master-or Station--TIM RS232 MD3/ MD4 Connection cable ( 6m) MD4  S0 will be supplied with MD4 (spare part order no. 6NH7700-4AR60) RJ45 (for MD3) (for MD4) ISDN socket (S0) *) SMS Center (plug for Germany) Connection cable ( 6m) MD3  TAE6N will be supplied with MD3 (spare part order no. 6NH7700-3BR60) Telephone socket *) RJ12 *) at best with overvoltage protection, e.g. from Phoenix or Dehn (both Germany)

  49. TIM with RS232 interface RS232 TIM 3V 6NH7800-3AA00 TIM 3VD 6NH7800-3AD00 TIM 4V 6NH7800-4AA00 TIM 4VD 6NH7800-4AD00 TIM 42 6NH7800-4AA20 TIM 42D 6NH7800-4AD20 TIM 43 6NH7800-4AA30 TIM 43D 6NH7800-4AD30 TIM 44 6NH7800-4AA40 TIM 44D 6NH7800-4AD40 TIM 4R 6NH7800-4AA90 TIM 4RD 6NH7800-4AD90 TIM TC35 GSMnetwork 24 V GSM-Kit TC35 with antenna Short Message Service (SMS) 6NH9840-3DB35 Antenna cable (5m) GSM Kit  antenna,antenna and 24V cablewill be supplied with kit GSM mobilephone Connection to Dial-up NetworksShort Message Service (SMS), Access via Mobile Network (GSM 900 and 1800 MHz) Master-or Station-TIM Important: Only SMS messages sent via TC35 can be acknowledged! Connection cable (2,5m) 6NH7701-5AN Important: For each GSM module a SIM card is required that is activated for data transmission SMS Center Note: The TC35 GSM module is suitable for 900 and 1800 MHz. The former M20 GSM module is only suitable for the 900 MHz network.

  50. Station Control System SINAUT ST7 Assembly guide & Configuration Help