1 / 65

1. Power and RMS Values

1. Power and RMS Values. + −. Circuit in a box, two wires. + −. Circuit in a box, three wires. + −. Instantaneous power p(t) flowing into the box. Any wire can be the voltage reference.

arissa
Télécharger la présentation

1. Power and RMS Values

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 1. Power and RMS Values

  2. + − Circuit in a box, two wires + − Circuit in a box, three wires + − Instantaneous power p(t) flowing into the box Any wire can be the voltage reference Works for any circuit, as long as all N wires are accounted for. There must be (N – 1) voltage measurements, and (N – 1) current measurements.

  3. Average value ofperiodic instantaneous power p(t)

  4. Two-wire sinusoidal case zero average Power factor Average power

  5. compare Root-mean squared value of a periodic waveform with period T Compare to the average power expression The average value of the squared voltage Apply v(t) to a resistor rms is based on a power concept, describing the equivalent voltage that will produce a given average power to a resistor

  6. Root-mean squared value of a periodic waveform with period T For the sinusoidal case

  7. Given single-phase v(t) and i(t) waveforms for a load • Determine their magnitudes and phase angles • Determine the average power • Determine the impedance of the load • Using a series RL or RC equivalent, determine the R and L or C

  8. Determine voltage and current magnitudes and phase angles Using a cosine reference, Voltage cosine has peak = 100V, phase angle = -90º Current cosine has peak = 50A, phase angle = -135º Phasors

  9. The average power is

  10. Voltage – Current Relationships

  11. Thanks to Charles Steinmetz, Steady-State AC Problems are Greatly Simplified with Phasor Analysis (no differential equations are needed) Time Domain Frequency Domain Resistor voltage leads current Inductor current leads voltage Capacitor

  12. Problem 10.17

  13. Complex power S Projection of S on the imaginary axis Q P Projection of S on the real axis is the power factor Active and Reactive Power Form a Power Triangle

  14. Consider a node, with voltage (to any reference), and three currents IA IB IC Question: Why is there conservation of P and Q in a circuit? Answer: Because of KCL, power cannot simply vanish but must be accounted for

  15. Voltage and Currentin phase Q = 0 Voltage leads Current by 90° Q > 0 Current leads Voltage by 90° Q < 0 Voltage and Current Phasors for R’s, L’s, C’s Resistor Inductor Capacitor

  16. Complex power S Projection of S on the imaginary axis Q P Projection of S on the real axis

  17. Resistor also so Use rms V, I ,

  18. Inductor also so Use rms V, I ,

  19. Capacitor also so , Use rms V, I

  20. Active and Reactive Power for R’s, L’s, C’s (a positive value is consumed, a negative value is produced) Active Power P Reactive Power Q Resistor Inductor Capacitor source of reactive power

  21. Now, demonstrate Excel spreadsheet EE411_Voltage_Current_Power.xls to show the relationship between v(t), i(t), p(t), P, and Q

  22. A Single-Phase Power Example

  23. 0.05 + j0.15 pu ohms PL + jQL PR + jQR /0 ° VR = 1.010 / - 1 0 ° VL = 1.020 IS IcapL IcapR j0.20 pu mhos j0.20 pu mhos A Transmission Line Example Calculate the P and Q flows (in per unit) for the loadflow situation shown below, and also check conservation of P and Q.

  24. 0.05 + j0.15 pu ohms PL + jQL PR + jQR /0 ° VR = 1.010 / - 1 0 ° VL = 1.020 IS IcapL IcapR j0.20 pu mhos j0.20 pu mhos

  25. V 0 0 < D < 1 DT T RMS of some common periodic waveforms Duty cycle controller By inspection, this is the average value of the squared waveform

  26. RMS of common periodic waveforms, cont. Sawtooth V 0 T

  27. V 0 V 0 V 0 V 0 V 0 V 0 0 -V RMS of common periodic waveforms, cont. Using the power concept, it is easy to reason that the following waveforms would all produce the same average power to a resistor, and thus their rms values are identical and equal to the previous example

  28. 2. Three-Phase Circuits

  29. a b c n Three-phase, four wire system Reference Three Important Properties of Three-Phase Balanced Systems • Because they form a balanced set, the a-b-c currents sum to zero. Thus, there is no return current through the neutral or ground, which reduces wiring losses. • A N-wire system needs (N – 1) meters. A three-phase, four-wire system needs three meters. A three-phase, three-wire system needs only two meters. • The instantaneous power is constant

  30. Observe Constant Three-Phase P and Q in Excel spreadsheet 1_Single_Phase_Three_Phase_Instantaneous_Power.xls

  31. Imaginary V V = V – V cn ab an bn V = V – V ca cn an 30° Real V an 120° V bn V = bc V – V b n c n The p hasors are rotating counter - clockwise . 3 The magnitude of line - to - line voltage phasors is times the magnitude of line - to - neutral voltage phas ors.

  32. Imaginary V V = V – V cn ab an bn V = V – V ca cn an I c I ca 30° I ab Real V I an a Line currents I , I , and I a b c I I bc b Delta currents I , I , and I ab bc ca I c c V bn I ca Balanced Sets Add to Zero in Both I bc Time and Phasor Domains I + I + I = 0 a b c I a b I b b a V + V + V = 0 an b n cn V = bc V – V – Vab + bn cn V + V + V = 0 ab bc ca I a 1 Conservation of power requires that the magnitudes of delta currents I , I , and I are ab ca bc 3 times the magnitude of line currents I , I , I . a b c

  33. c c I c I c – V a n n + a a b b I – V + b ab I b – V + ab I a I a The Two Above Sources are Equivalent in Balanced Syst ems (i.e., same line currents I , I , I and phase - to - phase voltages V , V , V in both cases ) a b c ab bc ca

  34. c KCL: I = I + I + I n a b c I c But for a balanced set, I + I + I = 0, so I = 0 Z a b c n I n n Z Z a b – V + ab I b I a Ground (i.e., V = 0) The Experiment: Opening and closing the switch has no effect because I is already zero for a three - phase n balanced set. Since no current flows, even if there is a resistance in the grounding path, we must conclude that V = 0 at the neutral point (or equivalent neutral point) of any balanced three phase load or source in a bala nced n system. This allows us to draw a “one - line” diagram (typically for phase a) and solve a single - phase problem. Solutions for phases b and c follow from the phase shifts that must exist.

  35. 3 Z l ine c c I c 3Z 3Z load load a a b b Z l ine I 3Z a load – V + ab Z l ine I b Balanced three - phase systems, no matter if they are delta connected, wye connected, or a mix, are easy to solve if you follow these steps : Z l ine 1. Convert the entire circuit to an equivalent wye with a a a I a ground ed neutral . 2. Draw the one - line diagram for phase a , recognizing that phase a has one third of the P and Q . 3. Solve th e one - line diagram for line - to - neutral voltages and + line currents . The “One - Line” Z load Van 4. If needed, compute l ine - to - neutral voltages and line currents Diagram – for phases b and c using the ±120° relationships. 5. If needed, compute l ine - to - line voltages and delta currents n using the and ± 30 ° relationships. n

  36. Now Work a Three-Phase Motor Power Factor Correction Example • A three-phase, 460V motor draws 5kW with a power factor of 0.80 lagging. Assuming that phasor voltage Van has phase angle zero, • Find phasor currents Ia and Iab and (note – Iab is inside • the motor delta windings) • Find the three phase motor Q and S • How much capacitive kVAr (three-phase) should be connected in • parallel with the motor to improve the net power factor to 0.95? • Assuming no change in motor voltage magnitude, what will be the new phasor current Ia after the kVArs are added?

  37. Part c. Draw a phasor diagram that shows line currents Ia, Ib, and Ic, and load currents Iab, Ibc, and Ica. Now Work a Delta-Wye Conversion Example

  38. 3. Transformers

  39. Transformer Core Types

  40. High-Voltage Grid Transformers, 100’s of MW

  41. Φ jXs Rs Ideal Transformer jXm Rm 7200:240V Turns ratio 7200:240 (30 : 1) (but approx. same amount of copper in each winding) 7200V 240V Single-Phase Transformer

  42. Isc + Vsc - Short circuit test: Short circuit the 240V-side, and raise the 7200V-side voltage to a few percent of 7200, until rated current flows. There is almost no core flux so the magnetizing terms are negligible. Φ Turns ratio 7200:240 (but approx. same amount of copper in each winding) Short Circuit Test jXs Rs Ideal Transformer jXm Rm 7200:240V 7200V 240V

More Related