An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Chimney FundamentalsAnd Operation The Art of Venting Flue Gases Or How Not To Kill Your Client Presenter: Earl Hicks

  2. Objectives • Review New York WAP policy regarding venting systems • BPI Standards • Review combustion process • Define & understand combustion air • How does a vent system work • Identify venting categories and materials • Using venting rules-of-thumb • Inspection of existing flues • Alternative venting methods

  3. NYS WAP Policy • Ensure safe elimination of flue gases from the building

  4. BPI StandardsBuilding Performance Institute • Any combustion appliance chimney/vent system that is in use must be visually evaluated for defects • A deteriorated chimney should be repaired or relined and causes corrected before reusing.

  5. Principles Of Combustion • Three essential components for combustion • Fuel • Oxygen • Heat • Fuel – Fossil fuels • Oxygen – Air is 20.9% O2 • Heat – Pilot, spark, or igniter

  6. Combustion Principles

  7. The Chemical Reaction • CH4 + 4O2 + heat = CO2 + 2H2O + heat • Complete combustion • Natural gas • 1 Cu Ft of CH4 + 10 Cu Ft of air for complete combustion • 11 Cu Ft of flue gases

  8. Combustion Air • Must supply sufficient air for complete combustion when all appliances are in operation simultaneously. • Must determine whether CAZ is a confined or unconfined space per NFPA. • Tightening a dwelling too much may result in the need to bring in outside air for combustion regardless of NFPA classification. • Must follow established standards for bringing in combustion air.

  9. Confined / Unconfined • Confined Space • Not enough air in the combustion appliance zone to provide for complete combustion when all appliances are operating and the building is set in worst case criteria. • Unconfined Space • Enough air is present to provide for complete combustion when all combustion appliances are operating and the house is set for worst case criteria.

  10. Standard 1/20 Rule • Measure the volume of the CAZ. • Add all input Btu ratings of appliance in the CAZ. • If dryer is in CAZ • Electric – consider input rate of 100,000 • Gas – consider input rate of 125,000 • Divide this total Btu by 20. • The resulting number is the Cu. Ft. separating confined from unconfined space. • Volume of CAZ below result = confined space • Volume of CAZ above result = unconfined space

  11. Example • CAZ = 10’L X 14’W X 8’H • Appliances • Gas furnace – 75,000 Btu input • Hot water heater – 40,000 Btu input • Gas dryer - 125,000 Btu input

  12. Solution • CAZ = 10’L X 14’W X 8’H • Volume = 1120 Cu’ • Total appliance input Btu • 240,000 Btu • 1/20 • 240,000 ÷ 20 = 12,000 cu ft. • Actual volume is below 12,000 cu ft • CAZ is a confined space • Results: Additional combustion air must be brought into the CAZ

  13. Other Than Standard: • IMPORTANT! The above standard is based on a known infiltration rate of less than .4 air changes per hour • When the ACH is known • For appliances other than fan-assisted, consult NFPA 54 8.3.2.2(1) • For fan-assisted appliances, consult NFPA 54 8.3.2.2(2)

  14. Table 9.3.2.2(a) Natural Draft Appliances

  15. Table 9.3.2.2(b)Fan Assisted Appliances

  16. Methods of Bringing In Combustion Air • Within the dwelling, from other zones • Ducted in horizontally from OD • Directly from OD above and or below

  17. What is Draft • Negative pressure within a flue that pulls products of combustion out from the dwelling.

  18. Factors That Affect Draft Pressure • Delta T, Indoors to Outdoors • Height of Vent • Interior Volume • Restrictions • Atmospheric Conditions • Pressure Imbalances in the CAZ

  19. How Does A VentingSystem Work? Air Flow Combustion Gases

  20. What is Considered Adequate Draft? • OD temp >800F, >-1 Pa or - .005”WC • OD temp 300 – 800F, >-2.5 Pa or -.01”WC • OD temp below 300F, >-5 Pa or -.02”WC • (250 pascal = 1”W.C.)

  21. Most Common Poor Draft Factors Found in the Field • Return air leaks in the basement • Long horizontal vent connectors • Blocked vents • Deteriorated flue • Bird nests • Outside masonry flues with fan assisted heating appliances • Fireplaces with no outside combustion air and without front enclosures. • Overly tight houses

  22. Venting Categories

  23. Venting Categories • NFPA 54 and 58 criteria • Standardized • Category I • Negative pressure, non-condensing • Category II • Negative Pressure, condensing • No longer produced • Category III • Positive pressure, non-condensing • Category IV • Positive pressure, condensing

  24. Non-Condensing Condensing

  25. Category I • What we normally think of when we think chimney • Negative pressure sucks products of combustion from the appliance breech and deposits them outdoors

  26. Category II • No longer manufactured • Negative pressure vent with combustion gases at or below the dew point • Heavy gases at the dew point are not buoyant enough to vent with a negative pressure flue

  27. Category III • Direct sidewall vented without additional apparatus. • Positive pressure requires joints in flue material to be sealed • Because these 80% appliance flue gases are close to the dew point, and the vent material is single wall, corrosion resistant materials must be used • Drains are typically incorporated to remove flue condensation before it enters the heat exchanger

  28. Category III • Has been used to solve installation problems where no appropriate flue is available • Positive pressure requires joints in flue material to be sealed

  29. Category IV • Positive pressure condensing appliances, joints must be sealed • 90%+ AFUE • Appliances are designed to dispose of flue condensate as well as condensate formed within the secondary heat exchanger • May be able to sidewall vent at reduced distances to openings in the building than NFPA suggests • Sealed combustion • Combustion air intake in same pressure plane

  30. Category I Vent MaterialsFound With Older Heating Appliances • Single wall galvanized pipe, 26 gauge • Only as a connector on 70% AFUE and lower gas appliances and all oil appliances • Connector for oil appliances • Masonry • Vitreous clay liner • Oil appliances • Transite • Rated as single wall • Asbestos • Does not meet any venting requirements

  31. Category I Vent Materialscont. • “B” Vent – double wall • Galvanized steel outside, aluminum inner pipe • Rated only for gas appliances • Used as a vent connector for all 78% and 80% AFUE appliances • May not be run outside of the building • Used as a liner in an existing flue chase

  32. Category I Vent Materialscont. • Flexible liner • Aluminum – gas appliances • Stainless Steel – gas and oil appliances • Used to retrofit existing flue passages to meet code or a specific application • “L” Vent – double wall • Inner and outer pipes are stainless steel • Oil appliances • All Fuel, double wall insulated • Oil • Solid Fuels

  33. Category III Flue Materials • Aluminum • No longer recommended because of corrosion problems • Stainless Steel • Use type specified by manufacturers to reduce corrosion issues • High temperature plastic • Was the most common material specified by manufacturers • Have been involved in recall • Manufacturer specific installation protocol • Sealed joints, High temperature sealant • Hanger spacing • Pitch back to appliance ¼” per Ft.

  34. Category IV Flue Materials • PVC • Low cost • Sealed joints • Must be provided with adequate hanging support • Pitch – back to appliance ¼” per Ft. • CPVC • Higher operating temperatures than PVC • Follow manufacturer instructions • Manufacturer specific • Sealed Joints

  35. Water In The Flue • Water is a byproduct of combustion • Key for category I appliances is to maintain water in a gaseous state within the flue so that it exits to the outdoors. • Category IV appliances are engineered to remove liquid water from within the secondary heat exchanger and flue.

  36. 93#(lbs) ~ 10 gallons • Million Btu = 100,000 Btu @ 10 Hrs run time • 10 Hr run time for natural gas = 10 gallons of water that must be removed from the flue.

  37. 70% AFUE Gas Furnace Overview • 21 Cu Ft flue gases for every 1 Cu Ft of natural gas burned • Draft diverter mixes the extra ~10 Cu Ft of air with the flue gases before entering the flue • Reduced efficiency means more heat going up the chimney, hot flue gases (4500 – 6000F) • Dilution gases reduce the relative humidity and increases the dew point

  38. Draft Hood Appliances • 1 Cu Ft CH4 + 10 Cu Ft air + 10 Cu Ft of dilution air mixed at draft hood • 21 Cu Ft of flue gases up chimney under maximized conditions • Draft hood • aids in minimizing fluctuation of draft • Prevents backdraft from affecting burner Spill Switch

  39. 78% & 80% AFUE Furnace Venting Overview • Draft induced fan does not force flue gasses into the vent. • A category I flue of adequate design must be used • More heat in the building and less up the chimney yields a colder chimney • Cycle time is longer than older furnaces to adequately warm the flue and keep moisture in a gaseous state.

  40. TO WARM UP A CHIMNEY • If firing rate = 100,000 Btu/hr and SSE = 75%, then 75,000 Btu/hr go to the distribution system and 25,000 Btu/hr go through the vent.If the burner on-cycle is 12 minutes (.2 hrs), then during one cycle the vent receives: .2 hr x 25,000 Btu/hr = 5,000 Btu/cycle MASONRY CHIMNEY:A masonry chimney (block or brick + tile liner) requires about 4570 Btu/.ft. to go from 0o to 120o. So, on a very cold day, about one foot of chimney will be warmed in one burner cycle: 5,000 Btu/cycle @4,570Btu/ft = 1 ft/cycle TYPE B-VENT CHIMNEY:A 6" B-vent chimney requires about 90 Btu/.ft. to go from 0o to 120o. So,5,000 Btu/cycle @ 90Btu/ft = 55 ft/cycle

  41. After Weatherization with aNew Furnace: • If firing rate = 75,000 Btu/hr and SSE =82%, then 61,500 Btu/hr go to the distribution system and 13,500 Btu/hr go through the vent. • If the burner on-cycle is 6 minutes (.1hrs), then during one cycle the vent receives: • .1hr x 13,500 Btu/hr =1,350 Btu/cycle • EXISTING MASONRY CHIMNEY: • About four inches of the existing masonry chimney will be warmed during one burner cycle: • 1,350 Btu/cycle @ 4,570Btu/ft = .3 ft/cycle • TYPE B-VENT CHIMNEY: • During each burner on cycle, enough heat to warm 15feet of B vent goes into the chimney: • 1,350 Btu/cycle @ 90Btu/ft = 15 ft/cycle

  42. Draft Induced Category I Venting Guidelines • No exterior masonry chimneys without a properly sized metal liner. • Flex or “B” • No interior masonry chimneys over 2 stories • No transite chimneys • No unlined masonry chimneys • No masonry chimneys unless common vented with a draft hood type appliance without a vent damper

  43. Draft Induced Category I Venting Guidelines (cont.) • Must have double wall “B” vent connector • Furnace must be properly sized • Furnace must be set up correctly • Temperature rise • Gas input • Heat anticipator or cycle rate set @ 3 cycles per hour • Vent sizing should be in accordance with tables supplied with the furnace or NFPA • When sidewall venting a power vent kit must be used unless the manufacturer specifies otherwise.

  44. New Category I Venting Rules-Of-Thumb • Use “B” vent as connector from the appliance to the flue • Reduce heat loss in the connector • Pitch connector down toward appliance ¼” per Ft. • Warm air rises • Maximum horizontal distance (Table 13.2.2) • 1 ½ times the diameter of the connector in feet • 4” connector = 6’ maximum horizontal distance

  45. Rule-Of-Thumb Continued • Follow NFPA 54 sizing charts • Never used unlined masonry flue • Don’t use outside masonry flue • Never use Transite • If you take the heating appliance out of the flue and leave the water heater in, you are responsible to ensure the water heater will vent properly • Line the flue