Shore Station UPS Requirements for the NEPTUNE Power System

frederique avatar
15 diapositives · 319 Views · Dec 01, 2012

Shore Station UPS Requirements for the NEPTUNE Power System. Tim McGinnis UW/APL. Background. 2 Shore Stations – each able to individually power to the network, although with possible reduced capability West Coast of Vancouver Island Planned visitor center at Victoria

Shore Station UPS Requirements for the NEPTUNE Power System - slide 1
01 / 15Shore Station UPS Requirements for the NEPTUNE Power System
1 / 17

Télécharger la présentation

Shore Station UPS Requirements for the NEPTUNE Power System
Une image / un lien ci-dessous est fourni (tel quel) pour télécharger la présentation

Politique de téléchargement : le contenu du site vous est fourni TEL QUEL pour votre information et votre usage personnel ; il ne peut être vendu, concédé sous licence ni partagé sur d’autres sites sans l’accord de son auteur.Le contenu vous est fourni TEL QUEL, pour votre information et votre usage personnel uniquement. Téléchargez la présentation en cliquant sur ce lien. Lors du téléchargement, si vous ne parvenez pas à télécharger une présentation, l’éditeur a peut-être supprimé le fichier de son serveur.Pendant le téléchargement, si vous ne parvenez pas à obtenir une présentation, le fichier a peut-être été supprimé par l’éditeur.

F I N

Plus de contenu associé

Transcription de la présentation
  1. Shore Station UPS Requirements for theNEPTUNE Power System Tim McGinnis UW/APL

  2. Background • 2 Shore Stations – each able to individually power to the network, although with possible reduced capability • West Coast of Vancouver Island • Planned visitor center at Victoria • Existing cable stations at Port Alberni, Bamfield • Oregon Coast • Existing cable stations at Nedonna Beach, Rockaway, Pacific City, Bandon

  3. Local Utility Power Reliability • 2 Substations, each located about 8 miles away • Station currently served by 1, possibility of connecting to both substations with a switch • Several outages of 30-60 minutes per year can be expected – mostly from trees/branches

  4. UPS Alternatives • DC System • Typical for Telecom Systems • Most equipment requires 48 VDC • AC-DC rectifiers supply power to batteries and equipment • If utility power fails, batteries are always on-line • 3-8 hour battery life typical, generator optional • DC-AC inverter for critical AC loads (minimal)

  5. Traditional Telecom Power Feed Equipment (PFE)

  6. UPS Alternatives • AC System • Typical for Information Technology, Network, Hospital, Commercial and similar facilities • Most equipment requires 120VAC • If utility fails, run on battery until generator starts • 10 minute battery life, typical • One or more generators for AC backup

  7. Typical IT UPS System with a backup generator

  8. Selection Criteria • Reliability • Load Voltage and Power Requirements • Cost

  9. Reliability - DC

  10. Reliability - AC

  11. Load Power Requirements • Expected NEPTUNE Shore Station Load is mostly AC equipment • Power Estimate – 120 kW total • 100 kW seafloor cable load • 20 kW terrestrial load • Current Estimates • 48 VDC → 2500 A • 480 VAC, 3Ф → 144 A

  12. Cost • For Loads < 25 kW • Batteries cost less • Batteries have smaller footprint • For Loads > 25 kW • Generator costs less • Generator has smaller footprint

  13. Criteria for selecting a UPS System

  14. Conclusions • Need to learn more about Shore Station power requirements • Need to confirm reliability/availability data • Need to learn more about similar installations